FLM DI 8 M12
697000 7
Programming Data/Configuration Data
INTERBUS
Other Bus Systems
Process Data
Assignment of the Connection Points to the IN Process Data
ID code BE
hex
(190
dec
)
Length code 81
hex
Process data channel 8 bits
Input address area 8 bits
Parameter channel
(PCP)
0 bits
Register length (bus) 8 bits
For the programming data of other
bus systems, please refer to the
appropriate electronic device data
sheet (GSD, EDS). For additional
information, please refer to the user
manuals, see "Ordering Data" on
page 12.
(Byte.bit)
view
Byte Byte 0
Bit 76543210
Device Input 87654321
For the assignment of the illustrated (byte.bit) view for your INTERBUS control or
computer system, please refer to data sheet DB GB IBS SYS ADDRESS,
Part No.9000990.
FLM DI 8 M12
8 697000
Technical Data
Device Dimensions
General Data
Order designation FLM DI 8 M12
Order no. 27 36 28 8
Housing dimensions (width x height x depth) 70 mm x 178 mm x 49.3 mm
(2.756 x 7.008 x 1.941 in.)
Weight 290 g, approximately
Operating mode Process data mode with 8 bits
Type of sensor connection 2, 3 or 4-wire technology
Permissible temperature (operation) -25°C to +60°C (-13°F to +140°F)
Permissible temperature (storage/transport) -25°C to +85°C (-13°F to +185°F)
Permissible humidity (storage/transport) 95%
Permissible air pressure (operation) 80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level)
Permissible air pressure (storage/transport) 70 kPa to 106 kPa
(up to 3000 m [9843 ft.] above sea level)
Degree of protection IP65/IP67 according to IEC 60529
Class of protection Class 3 according to VDE 0106, IEC 60536
F L M D I 8
I N
L B
D
U S
L B
O U T
U
L S
I 2
I 4
I 6
I 8
I 1
I 3
I 5
I 7
U
L S
E
1 6 8 m m
( 6 . 6 1 4 ' ' )
7
0
m m
( 2 . 7 5 6 ' ' )
3 1 m m
( 1 . 2 2 0 ' ' )
1 7 8 m m
( 7 . 0 0 8 ' ' )
4 0 m m
( 1 . 5 7 5 ' ' )
4 9 . 3 m m
( 1 . 9 4 1 ' ' )
For a short period, slight condensation may appear on the housing.
FLM DI 8 M12
697000 9
Mechanical Requirements
Vibration test
Sinusoidal vibrations according to EN 60068-2-6
5g load in each space direction
Shock test according to EN 60068-2-27 30g load, half sinusoidal wave positive and
negative in each space direction
For additional information on mechanical requirements and ambient conditions, please
contact Phoenix Contact.
Voltage Supply
Nominal value 24 V DC
Tolerance ±25%
Current consumption at U
L
at 24 V DC
At 500 kbaud 35 mA, typical (50 mA, maximum)
At 2 Mbaud 40 mA, typical (50 mA, maximum)
Current consumption at U
S
at 24 V DC 5 mA, typical, + sensor current
(600 mA, maximum)
Digital Inputs
Number 8
Input design According to IEC 61131-2 Type 1
Definition of switching thresholds
Maximum low level voltage
Minimum high level voltage
U
Lmax
< 5 V
U
Hmin
> 11 V
Nominal input voltage 24 V DC
Range -30 V DC < U
IN
< +30 V DC
Nominal input current 5 mA
Current flow Linear in the range 2 V < U
IN
< 30 V
Delay time t
ON
= 3.1 ms, typical
t
OFF
= 4.1 ms, typical
Permissible cable length to the sensor < 30 m (98.43 ft.)

2736288

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules FLM DI 8 M12 M12, 8 INPUTS
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet