2308302

© PHOENIX CONTACT 2011-03-09
104059_en_05
MCR-SL-CUC-...-...
Data sheet
1Description
MCR-SL-CUC-...-I and MCR-SL-CUC-...-U active current
transducers convert DC, AC, and distorted currents into
standard analog signals.
Output signal: 4 ... 20 mA.
Output signal: 0 ... 10 V
Features
Electrical isolation of input and output signals
Contact-free measurement of live conductors
Large input signal opening
Designation Input current Order No.
MCR-SL-CUC-100-I 0 ... 100 A 2308027
MCR-SL-CUC-200-I 0 ... 200 A 2308030
MCR-SL-CUC-300-I 0 ... 300 A 2308043
MCR-SL-CUC-400-I 0 ... 400 A 2308072
MCR-SL-CUC-500-I 0 ... 500 A 2308085
MCR-SL-CUC-600-I 0 ... 600 A 2308098
Designation Input current Order No.
MCR-SL-CUC-100-U 0 ... 100 A 2308108
MCR-SL-CUC-200-U 0 ... 200 A 2308205
MCR-SL-CUC-300-U 0 ... 300 A 2308302
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog
.
This data sheet is valid for all products listed on the following page:
Universal current transducer
MCR-SL-CUC-...-...
104059_en_05 PHOENIX CONTACT 2
2Table of contents
1 Description.................................................................................................................................. 1
2 Table of contents ........................................................................................................................ 2
3 Ordering data.............................................................................................................................. 3
4 Technical data ............................................................................................................................ 3
5 Safety notes and warning instructions ........................................................................................ 5
6 Block diagram............................................................................................................................. 6
7 Structure ..................................................................................................................................... 6
8Mounting................................................................................................................................................................... 6
9 Installation................................................................................................................................................................ 7
9.1 Power supply.................................................................................................................................................. 7
9.2 Connecting the cables.................................................................................................................................... 7
10 Current monitoring ...................................................................................................................... 7
MCR-SL-CUC-...-...
104059_en_05 PHOENIX CONTACT 3
3Ordering data
4 Technical data
Products
Description Type Order No. Pcs./Pkt.
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 100 A input current, 4 ... 20 mA output current
MCR-SL-CUC-100-I 2308027 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 200 A input current, 4 ... 20 mA output current
MCR-SL-CUC-200-I 2308030 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 300 A input current, 4 ... 20 mA output current
MCR-SL-CUC-300-I 2308043 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 400 A input current, 4 ... 20 mA output current
MCR-SL-CUC-400-I 2308072 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 500 A input current, 4 ... 20 mA output current
MCR-SL-CUC-500-I 2308085 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 600 A input current, 4 ... 20 mA output current
MCR-SL-CUC-600-I 2308098 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 100 A input current, 0 ... 10 V output voltage
MCR-SL-CUC-100-U 2308108 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 200 A input current, 0 ... 10 V output voltage
MCR-SL-CUC-200-U 2308205 1
Universal current transducer for measuring DC, AC, and distorted currents,
0 ... 300 A input current, 0 ... 10 V output voltage
MCR-SL-CUC-300-U 2308302 1
Accessories
Description Type Order No. Pcs./Pkt.
Flat zack marker strip marking material (without color print, white) ZBF10:UNBEDRUCKT 0044187 1
DIN rail adapter for mounting the universal current transducer PACT MCR-RA 2277598 12
Input
MCR-SL-CUC-100-I MCR-SL-CUC-200-I MCR-SL-CUC-300-I
Nominal input current I
IN
0 … 100 A 0 … 200 A 0 … 300 A
Overload capacity 6 x I
IN
, maximum 3 x I
IN
, maximum 3.33 x I
IN
, maximum
MCR-SL-CUC-400-I MCR-SL-CUC-500-I MCR-SL-CUC-600-I
Nominal input current I
IN
0 … 400 A 0 … 500 A 0 … 600 A
Overload capacity 2.5 x I
IN
, maximum 3.6 x I
IN
, maximum 3 x I
IN
, maximum
MCR-SL-CUC-100-U MCR-SL-CUC-200-U MCR-SL-CUC-300-U
Nominal input current I
IN
0 … 100 A 0 … 200 A 0 … 300 A
Overload capacity 6 x I
IN
, maximum 3 x I
IN
, maximum 3.33 x I
IN
, maximum
Frequency range DC, 20 … 6000 Hz
Signal form Any
Connection method Through connection of 32 mm
Output
MCR-SL-CUC-...-I MCR-SL-CUC-...-U
Output signal I
OUT
4 … 20 mA 0 ... 10 V
Maximum output signal < 25 mA < 14 V
Load < 300 Ω
10 kΩ
Connection method FKCN 2.5/ 4-ST COMBICON connector

2308302

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Current Transformer Sensors Current Transformers MCR-SL-CUC-300-U
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet