CIO-MLPII-PR

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
FOLLOW NATIONAL, STATE AND LOCAL CODES.
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.
The CIO-MLPII-PR Module is a convenient and cost-effective Profibus interface capable of providing
discrete control and monitoring of motor starters, drives, and other devices over a Profibus network.
The CIO-MLPII-PR is designed to provide the following benefits in both new and existing
installations:
§ reduced field wiring
§ greater operator efficiency
§ ease in system startup and commissioning
The CIO-MLPII-PR Profibus module can be DIN rail mounted, or mounted directly to a back panel.
The CIO-MLPII-PR’s compact size, ease of wiring and Profibus communications capability makes the
use of traditional discrete devices on Profibus cost-effective and simple.
The CIO-MLPII-PR Module is compatible with Square D’s Model MLPII overload relay. It simply
connects to the side of the MLPII and permits remote monitoring and control of the MLPII over a
Profibus network.
CONNECTIONS
1. Mount the CIO-MLPII-PR in a convenient location in a properly rated enclosure. The CIO-MLPII-
PR can be mounted to a back panel using screws or can be snapped onto DIN rail.
2. Connect the five Profibus wires to the 5-pin connector on the front of the CIO-MLPII-PR Module.
24VDC should be connected to V+ and V-. Connect the other three wires to A, B and Shield.
3. The PBus LED indicates communication is established between the CIO-MLPII-PR and the
Profibus master, and OLC indicates communication is established with the MLPII overload.
4. Connect the Profibus SUB-D connector to the Profibus network.
FIGURE 1: Typical Wiring Diagram
MODEL CIO-MLPII-PR
PROFIBUS COMMUNICATIONS MODULE
PROGRAMMING GUIDE
2880 North Plaza Drive, Rapid City, South Dakota 57702
(800) 843-8848 · (605) 348-5580 · fax (605) 348-5685
www.symcom.com
DEPLUGGABLE
TERMINAL BLOCK
PROFIBUS
SUB-D CONNECTOR
PROFIBUS
NETWORK
V-
A
SHIELD
B
V+
IND. CONT. EQ.
LISTED
784X
¨
PROFIBUS NETWORK STATUS
OVERLOAD COMM. STATUS
PROFIBUS Communication and I/OCIO-MLPII-PR
SCREW TORQUE RATING 0.5 Nm (5.0 in.-lbs.)
2
1/07
DIAGNOSTIC INDICATOR LIGHTS
The unit is energized when power is applied between V+ and V- on the connector. The PBus and
OLC lights will flash until communication is established. The PBus communication status indicator
light will come on steady when a Profibus master is communicating with the unit. The OLC
communications status indicator light will come on steady when it is communicating to an MLPII
overload relay.
OPERATION
The CIO-MLPII-PR Module is a DP-V0 device. Cyclical I/O is supported for the transfer of input and
output information.
PROFIBUS NETWORK CONFIGURATION
Cable Routing
Follow these general cable-routing guidelines:
Avoid areas of high temperature, moisture, vibration, or other mechanical stress.
Secure the cable where necessary to prevent damage.
Use cable ducts, raceways, or other structures to protect the cable.
Never route cables over or around sharp edges.
Avoid sources of electrical interference that can induce noise into the cable. Use the maximum
practicable separation from such sources.
Maintain a minimum separation of 3.3 ft. (1m) from the following equipment:
o air conditioners and large blowers
o elevators and escalators
o radios and televisions
o intercom and security systems
o fluorescent, incandescent, and neon lighting fixtures
Maintain a minimum separation of 10 ft. (3m) from the following equipment:
o Line and motor power wiring
o Transformers
o Generators
o Alternators
Terminating Resistors
Profibus segments must be bus terminated as shown.
FIGURE 3: Bus Termination
390
220
390
+5V
Line B
Line A
Data Ground
3
1/07
Profibus Cable
The Profibus Cable must be connected as follows:
Description
Pin Signal
Cable Device
Specification
1 ––– ––– Not used
2 ––– ––– Not used
3 RxD/TxD-P Receive/Transmit data; line B (red) Mandatory
4 CNTR-P Control of repeater direction Optional
2
5 DGND Data ground (reference voltage to VP) Mandatory
7 ––– ––– ––– Not used
6 VP
1
Power supply +5V (e.g. bus termination) Mandatory
8 RxD/TxD-N Receive/Transmit data; line A (green) Mandatory
1
Minimum current capability is 10mA
2
These signals should be provided by the device if converters from RS-485 to fiber optic transmission are
to be supported.
12345
6789
FIGURE 3: 9-Pin Sub-D
Connector Pin Assignment

CIO-MLPII-PR