CIO-MLPII-PR

7
1/07
Import the Network Configuration into the PLC
When Concept software is used, follow these steps to import the network configuration:
1. Open a project.
2. Select Project > Configurator and double-click I/O Map.
3. Click the edit button next to the PLC.
4. Select the Profibus scanner and click the Params button.
5. Click the Import button and choose the desired .cnf file.
6. In the scanner configuration window assign registers to all I/O data for all devices.
7. Continue clicking OK and YES in the I/O Map dialog box to update the changes.
CYCLICAL INPUT RECORDS
Record 204
Byte.Bit Name Description
0-1 Average Current
2. MLP2OPRSTAT
2.0 Out A
2.1 Out B
2.2 Running
2.3 Modbus Comm Loss
2.4 Fault
2.5 Overcurrent
2.6 Ground Fault
2.7 Warning
3.0 Trip Relay Closed
3.1 In 1
3.2 In 2
3.3 In 3
3.4 In 4
3.5 PTC Warning
3.6 PTC Trip
3.7 PTC Short
Record 208
Byte.Bit Name Description
8
1/07
0–8 Proprietary
Record 250
Byte.Bit Name Description
0-1 Current / OC Setpoint % current of oc setpoint
2-3 Average Current
4-5 IC
6-7 IB
8-9 IA
10-11 CUB
12-13 Thermal Capacity
14-15 I GF
16-17 MLP2OPRSTAT
16.0 Out A
16.1 Out B
16.2 Running
16.2 Modbus Comm Loss
16.4 Fault
16.5 Overcurrent
16.6 Ground Fault
16.7 Warning
17.0 Trip Relay Closed
17.1 In 1
17.2 In 2
17.3 In 3
17.4 In 4
17.5 PTC Warning
17.6 PTC Trip
17.7 PTC Short
18-19 Fault Status same as Modbus 40408
18.0 Reverse Phase
18.1 PTC Overtemp
18.2 Reserved
18.3 Undercurrent
18.4 Overcurrent
18.5 Ground Fault
18.6 Current Unbalance
18.7 Single Phase
19.0 Reserved
19.1 PTC Shorted
19.2 Internal Error
19.3 No AC Power
19.4 Reserved
19.5 Reserved
19.6 Reserved
19.7 Reserved
9
1/07
Record 232
Byte.Bit Name Description
0-1 Current / OC Setpoint % current of OC setpoint
2-3 Average Current
4-5 IC
6-7 IB
8-9 IA
10-11 CUB
12-13 Thermal Capacity
14-15 I GF
16-17 RD1
18-19 RD2
20-21 RD3
22-23 MLP2OPRSTAT
22.0 Out A
22.1 Out B
22.2 Running
22.3 Modbus Comm Loss
22.4 Fault
22.5 Overcurrent
22.6 Ground Fault
22.7 Warning
23.0 Trip Relay Closed
23.1 In 1
23.2 In 2
23.3 In 3
23.4 In 4
23.5 PTC Warning
23.6 PTC Trip
23.7 PTC Short
24-25 Last 4 faults same as Modbus 40425
24.0–24.3 Last Fault
24.4–24.7 2nd last fault
25.0–25.3 3rd last fault
25.4–25.7 4th last fault
26-27 Fault Status same as Modbus 40408
26.0 Reverse Phase
26.1 PTC Overtemp
26.2 Reserved
26.3 Undercurrent
26.4 Overcurrent
26.5 Ground Fault
26.6 Current Unbalance
26.7 Single Phase
27.0 Reserved
27.1 PTC Shorted
27.2 Internal Error
27.3 No AC Power
27.4 Reserved
27.5 Reserved
27.6 Reserved
27.7 Reserved
28-29 Holdoff Status same as Modbus 40410
28.0 Reverse Phase
28.1 Thermal Capacity Not enough thermal capacity available
28.2 PTC Overtemp
28.3 PTC Shorted
28.4 Test Trip (Local) Local reset button
28.5 Test Trip (Remote) remote reset button
28.6 Reserved
28.7 Reserved
29.0 Reserved
29.1 Reserved
29.2 Internal Error
29.3 No AC Power