Application Note
Typical Application
AGQ200
EMI Filter
Fuse
Vdc
In+
In-
Out+
Out-
C1 C2
Vin+
CNT
Vin-
Vo+
S+
Trim
S-
Vo-
C3 C4
Load
Figure 11 Typical application
C1: 100µF/100V electrolytic capacitor, P/N: UVZ2A101MPD (Nichicon) or equivalent caps
C2: 1µF/100V X7R ceramic capacitor
C3: 1µF/25V X7R ceramic capacitor
C4: 470µF/25V electrolytic capacitor, P/N: UPM1E471MPD (Nichicon) or equivalent caps
External fast blow fuse with a rating of 15A should be used in the application.
If the load is far from the unit, connect S+ and S- to the terminal of the load respectively to
compensate the voltage drop on the transmission line.
Remote ON/OFF
Either positive or negative remote ON/OFF logic is available in AGQ200B-48S3V3.
The following figure is the detailed internal circuit and reference in AGQ200B-48S3V3.
PWM
controller
PWM
controller
UVLO
12V
19.7k
4.7k
Remote
ON/OFF
Negative logic Positive logic
12V +Vin
15k 85.6k
6.8k
15k
Remote
ON/OFF
Figure 12 Remote ON/OFF internal diagram