AXL E PB DI16 M12 6M
8431_en_03 PHOENIX CONTACT 13
11 Process data
11.1 Assignment of the terminal points to the IN process data
The I/O data are mapped as follows:
Key:
11.2 Status module
The device has a status module in slot 1.
The status is mapped as follows.
12 Parameterization
This section provides a detailed description of the format of the parameters for the input devices.
This may be useful when setting parameters using acyclic services or if there is no user interface for the simple selection of
parameters.
Input process data
Byte Byte 0 Byte 1
Bit 7654321076543210
IN 07 06 05 04 03 02 01 00 17 16 15 14 13 12 11 10
Connection X04 X03 X02 X01 X08 X07 X06 X05
Pin 2424242424242424
DI 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9
Bit: Process data assignment
IN: LED marking
DI: Input of the device
Bit 31 ... Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Supply of the module electronics and sensors (U
S
) Reserved
Reserved Undervoltage Overload Reserved
Byte Meaning
1 ... 7 DP standard
8 ... 10 DP/V1 standard
11 Module parameter
Module parameter
Byte Meaning Contents
11 Behavior of the device Bit 0 Reserved
Bit 1 Reserved
Bit 2 Byte order (Endianness)
00
bin
: Motorola format (Big Endian)
01
bin
: Intel format (Little Endian)
Other Reserved
AXL E PB DI16 M12 6M
8431_en_03 PHOENIX CONTACT 14
13 I&M functions
The following Information & Maintenance functions are supported:
I&M 0
I&M 1
I&M 2
I&M 3
I&M data Access / data type Presets
MANUFACTURER_ID Read / 2 bytes B0
hex
(Phoenix Contact GmbH & Co. KG)
ORDER_ID Read / 20 bytes -
SERIAL_Number Read / 16 bytes -
HARDWARE_Revision Read / 2 bytes -
SOFTWARE_Revision Read / 4 bytes -
REVISION_Counter Read / 2 bytes 0000
hex
(reserved)
PROFILE_ID Read / 2 bytes F600
hex
(generic device)
PROFILE_SPECIFIC_TYPE Read / 2 bytes 0003
hex
(IO module)
IM_VERSION Read / 2 bytes 0102
hex
(Version 1.2)
IM_SUPPORTED Read / 2 bytes 000E
hex
(I&M 1 ... 3)
I&M data Access / data type Presets
TAG_FUNCTION Read/write / 32 bytes “20
hex
” (empty)
TAG_LOCATION Read/write / 22 bytes “20
hex
” (empty)
I&M data Access / data type Presets
INSTALLATION_DATE Read/write / 16 bytes “20
hex
” (empty)
RESERVED Read/write / 38 bytes 0
hex
I&M data Access / data type Presets
DESCRIPTOR Read/write / 54 bytes “20
hex
” (empty)
AXL E PB DI16 M12 6M
8431_en_03 15
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
14 Sync/freeze mode
The device supports sync and freeze mode.
The functions must be activated by the PROFIBUS master
in the parameter data.
Input and output data is written or read at defined times with
the sync and freeze commands.
If the device receives a sync command from the PROFIBUS
master at any given time, the current OUT process data is
transferred and frozen until the next sync command.
Similarly, the states of the inputs are transferred on the re-
spective freeze command and are frozen until the next
freeze command.
15 Diagnostic alarms
PROFIBUS enables the PROFIBUS device to store diag-
nostic information together with the error location and error
type.
In the default upon delivery the alarms are enabled, how-
ever, they can be disabled with parameters on startup.
An incoming alarm informs the PROFIBUS device that diag-
nostic information has been entered.
When the diagnostic information has been removed, an out-
going alarm is sent to the device.
If at least one piece of diagnostic information is stored, the
SF LED is on. If no diagnostic information is present, the
SF LED is off.
The following PROFIBUS diagnostic messages are indi-
cated by the PROFIBUS device:
Overtemperature of the device
–Surge voltage of U
S
Overload of U
S

2701505

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL E PB DI16 M12 6M