AXL E PB DI16 M12 6M
8431_en_03 PHOENIX CONTACT 4
General data
Housing material Zinc die-cast
Weight 750 g
Ambient temperature (operation) -25 °C ... 60 °C
CAUTION: Risk of burns
If the device is used at an ambient temperature above50°C, the contact temperature of metal surfaces may exceed70°C.
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP65/IP67
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Connection method M12 connector
Interface PROFIBUS DP
Number 2
Connection method 2x M12 connectors, B-coded
Designation connection point Copper cable
Number of positions 5
Transmission speed 9,6 kBit/s ... 12 MBit/s (Automatic baud rate detection)
Transmission physics PROFIBUS-DP-compliant copper cable
PROFIBUS DP
Equipment type PROFIBUS slave
PROFIBUS protocols DP V1
Supply: Module electronics and sensors (U
S
)
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Typical current consumption 165 mA ±15 % (at 24 V DC)
Current consumption max. 12 A
Supply: Actuators (U
A
) for additional devices
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Typical current consumption 3 mA ±15 % (at 24 V DC)
Current consumption max. 12 A
AXL E PB DI16 M12 6M
8431_en_03 PHOENIX CONTACT 5
Digital inputs
Number of inputs 16 (EN 61131-2 types 1 and 3)
Connection method M12 connector, double occupancy
Connection method 2, 3, 4-wire
Nominal input voltage 24 V DC
Nominal input current typ. 3 mA
Sensor current per channel typ. 0.75 mA (from U
S
)
Total sensor current max. 1.2 A (per device)
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Input filter time < 1000 µs
Permissible conductor length to the sensor 30 m
Overload protection, short-circuit protection of sensor supply Yes
Configuration data
ID number 0E5C
Input address area 16 Bit
Output address area 0 Bit
Electrical isolation/isolation of the voltage areas
Test section Test voltage
24 V supply (communications power and sensor supply, digital inputs)/
bus connection
500 V AC, 50 Hz, 1 min
24 V supply (communications power and sensor supply, digital inputs)/FE 500 V AC, 50 Hz, 1 min
Bus connection / FE 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/
24 V supply (communications power and sensor supply, digital inputs)
500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/bus connection 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply)/FE 500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4
Radio interference properties EN 55022 Class A
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
AXL E PB DI16 M12 6M
8431_en_03 PHOENIX CONTACT 6
5 Internal circuit diagram
Figure 1 Internal wiring of connections
Key:
Key:
Green area: Network
Blue area: U
S
Yellow area: U
A
X21
X22
X31
X32
X01 X02
X03 X04
X05 X06
X07 X08
2
##
##
2
2
2
2 2
2
##
##
2
16
24 V
3.3 V
µC
U OUT
S
U OUT
A
UIN
S
UIN
A
BUS IN BUS OUT
Optocoupler
Power supply unit with electrical isolation
Microcontroller
Digital input
LED
µC

2701505

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL E PB DI16 M12 6M
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union