E5EK
Nomenclature
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Accessories (Order Separately)
E5EK
A/M Key
Display Key
No. 1 display
No. 2 display
Operation indicators
Up Key/Down Key
E5EK
Panel Cutouts
120 min.
60 min.
Note: 1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal
mounting space between each Unit. Units must
not be closely mounted vertically or horizontally.
Terminal Cover
E53-COV0809 E53-COV08
http://www.ia.omron.com/
8
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
E5EK
40 × 40
Current Transformer
E54-CT1 E54-CT3
5.8 dia.
12 dia.
2.36 dia.
Two, M3 (depth: 4)
Unit Label (Order Separately)
Y92S-L1
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
http://www.ia.omron.com/
C-1
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
1
Safety Precautions for All Temperature Controllers
Refer to the precautions of individual product for more specific details.
The following products contain lithium batteries. Do not
disassemble, deform under pressure, heat to over
100°C, or incinerate these products. The lithium bat-
tery may ignite or explode. Applicable models: E5ZE,
E5LD, and E5LC.
1. Do not use the Temperature Controller in the following locations:
Locations exposed to radiated heat from heating devices
Locations subject to exposure to water or oil
Locations subject to direct sunlight
Locations subject to dust or corrosive gases (in particular,
sulfide gas and ammonia gas)
Locations subject to severe changes in temperature
Locations subject to icing or condensation
Locations subject to excessive shock or vibration
2. Use and store the Temperature Controller within the rated
temperature or humidity range specified for each model.
When two or more Temperature Controllers are mounted hor-
izontally close to each other or vertically next to one another,
the internal temperature will increase due to the heat they
radiate and the service life of the products will decrease. In
such cases, forced cooling by fans or other means of air ven-
tilation will be required to cool down the Temperature Con-
trollers.
3. Allow enough space around the Temperature Controller to
ensure proper heat dissipation. Do no block the ventilating
holes.
4. Be sure to wire properly with correct polarity of terminals.
5. To wire the E5AN, E5EN, or E5CN using crimp terminals, use
crimp terminals designed for M3.5 screws and with a width of
7.2 mm max.
6. When wiring the E5GN, use a cable gauge of AWG24
(0.205 mm
2
) to AWG14 (2.081 mm
2
) for terminals 1 to 6, and
use a cable gauge of AWG28 (0.081 mm
2
) to AWG22
(0.326 mm
2
) for terminals 7 to 9. The exposed current-carry-
ing part to be inserted into terminals must be 5 to 6 mm.
7. After wiring is completed, do not pull on or bend a terminal
block lead wire with a force of 30 N or higher.
8. Do not connect anything to unused terminals.
9. Make sure that the power supply voltages and loads are
within specification and rating ranges before using the Tem-
perature Controller.
10. To avoid inductive noise, keep the wiring for the Temperature
Controller's terminal board away from power cables carrying
high voltages or large currents. Also, do not wire power lines
together with or parallel to Temperature Controller wiring.
Using shielded cables to separate pipes and ducts is recom-
mended.
Attach surge absorbers or noise filters to peripheral devices
that generate noise (e.g., motors, transformers, solenoids,
magnetic coils, or other equipment that has an inductance
element). If using a noise filter with the power supply, be sure
to confirm the voltage and the current, and then mount the
power supply as near as possible to the Temperature Con-
troller.
Set up the Temperature Controller, along with its power sup-
ply, as far away as possible from devices that generate
strong, high-frequency waves, such as high-frequency weld-
ers and high-frequency machines, and from devices that gen-
erate surges.
11. Make sure that the rated voltage is attained within two sec-
onds of turning the power ON.
12. Allow at least 30 seconds for the Temperature Controller to
warm up.
13. When using self-tuning, turn ON power for the load (e.g.,
heater) at the same time as or before supplying power to the
Temperature Controller. If power is turned ON for the Tem-
perature Controller before turning ON power for the load,
self-tuning will not be performed properly and optimum con-
trol will not be achieved.
Warning
Caution
Do not touch any of the terminals while the power is
being supplied. Doing so may result in electric shock.
Do not allow pieces of metal or wire cuttings to get
inside the Temperature Controller. Doing so may
result in electric shock, fire, or malfunction.
Do not attempt to disassemble, repair, or modify the
Temperature Controller. Any attempt to do so may
result in electric shock, fire, or malfunction.
Do not use the Temperature Controller in locations
subject to flammable or explosive gases. Doing so
may result in an explosion.
The switching capacity and switching conditions will
significantly affect the longevity of the output relays.
Use the Temperature Controller within the rated load,
and do not use the Temperature Controller beyond the
number of operations specified under electrical life.
Using the Temperature Controller beyond its electrical
life may result in contact welding or burning.
Use Temperature Controller settings that are
appropriate for the controlled system. Failure to do so
may cause unexpected operation resulting in damage
to equipment or personal injury
Prepare a circuit with an overheating prevention alarm
and implement other safety measures to ensure safe
operation in the event of a malfunction. Loss of
operational control due to malfunction may result in a
serious accident.
Tighten the terminal screws to the following
torque:
M3.5 screws: 0.74 to 0.90 N·m
M3 screws: 0.40 to 0.56 N·m
E5GN: Terminals 1 to 6: 0.23 to 0.25 N·m
Terminals 7 to 9: 0.12 to 0.14 N·m
Failure to tighten terminal screws to the correct torque
may result in fire or malfunction.
Make sure there will be no adverse affects from the
device connected to the Temperature Controller
before using the hardware test mode. Devices
connected to the Temperature Controller may reach a
dangerous state during the test.
Operating Environment Precautions
7.2 mm max.

E5EK-AA2-500 AC/DC24