E5EK
■ Accessories (Order Separately)
Note: No CT is required unless the heater burnout alarm function is used.
Unit Label
Specifications
■ Ratings
Note: 1. All control outputs are insulated from the input circuit.
2. Fuzzy self-tuning is available when using the Digital Controller in standard control operation with temperature input.
■ Input Ranges
Platinum Resistance Thermometer
Name Model Hole diameter
Current Transformer E54-CT1 5.8 mm
E54-CT3 12.0 mm
Name Model Connectable models
Terminal Cover E53-COV08 E5EK
Model Y92S-L1
Item AC100-240V type AC/DC24V type
Supply voltage AC100 to 240V, 50/60 Hz AC/DC24V, 50/60 Hz
Power consumption E5EK: 15 VA 12 VA, 8 W
Operating voltage range 85% to 110% of rated supply voltage
Input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
Current input: 4 to 20 mA, 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V
Input impedance Current input: 150 :; Voltage input: 1 M: min.
Control output Standard Model, Programmable Model
According to Output Unit (see Output Unit Ratings and Characteristics)
Position-proportional Model
2 Relay outputs: SPST-NO, 1 A at 250 VAC (including inrush current) (See note 1.)
Auxiliary output SPST-NO, 3 A at 250 VAC (resistive load)
Control method (See note 2.) ON/OFF or 2-PID control (with auto-tuning)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and LEDs
Potentiometer 100 : to 2.5 k:
Event input Contact input: ON: 1 k: max., OFF: 100 k: min.
No-contact input: ON: residual voltage: 1.5 V max., OFF: leakage current: 0.1 mA max.
Transfer output 4 to 20 mA, permissible load impedance: 600 : max., resolution: approx. 2,600
Remote SP input Current input: 4 to 20 mA (Input impedance: 150 :)
Current Transformer input Connect an exclusive Current Transformer (E54-CT1 or E54-CT3)
Other functions Standard
Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP ramp, MV limiter, MV
change rate limiter, input digital filter, input shift, run/stop, protect functions, scaling function.
Option
Multiple SP, run/stop selection, transfer output functions
Degree of protection Conforms to IEC IP66 and NEMA4 (Indoor use)
Input (switch selectable) JPt100 Pt100
Range qC 199.9 to 650.0 199.9 to 650.0
qF 199.9 to 999.9 199.9 to 999.9
Setting 01