E5EK
■ Characteristics
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of 100qC or less is r2qC r1 digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is r2qC r1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400qC or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200qC or less is r3qC r1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (r0.3% of the indicated value or r3qC, whichever is greater) r1digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (r0.3% or r2qC, whichever is greater) r1 digit maximum.
2. For Programmable Models.
3. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
Indication accuracy (See note 1.) Thermocouple:
(r0.3% of indication value or r1qC, whichever greater) r1 digit max.
Platinum resistance thermometer:
(r0.2% of indication value or r0.8qC, whichever greater) r1 digit max.
Analog input: r0.2% FS r1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 or 199.9 or 999.9 (decimal point position dependent on input type or result of scaling)
Set time (See note 2.) 0 to 99 hrs 59 min or 0 to 99 min 59 s
Program capacity (See note 2.) 4 p
atterns, 16 steps
Programming method (See note 2.) Time or ramp setting method
Time accuracy (See note 2.) r0.2% (r500 ms) of the set value
Sampling period (See note 3.) Temperature input: 250 ms
Current/voltage input: 100 ms
Insulation resistance 20 M: min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance
Malfunction: 10 to 55 Hz, 10 m/s
2
(approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s
2
(approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction: 200 m/s
2
min. (approx. 20G), 3 times each in 6 directions
(100 m/s
2
(approx. 10G) applied to the relay)
Destruction: 300 m/s
2
min. (approx. 30G), 3 times each in 6 directions
Ambient temperature Operating: 10qC to 55qC (with no icing)/3-year warranty period: –10qC to 50qC
Storage: 25qC to 65qC (with no icing)
Ambient humidity Operating: 35% to 85%
Degree of protection Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight E5AK: approx. 450 g
E5EK: approx. 320 g
Mounting bracket: approx. 65 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL1092, CSA22.2 No. 142, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.