E5EK
Thermocouple
Note: Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Input (switch
selectable)
(See note.)
K1 K2 J1 J2 T E L1 L2 U N R S B W PLII
Range qC 200
to
1,300
0.0 to
500.0
100
to 850
0.0 to
400.0
199.9
to 400.0
0 to
600
100
to 850
0.0 to
400.0
199.9
to 400.0
200
to
1,300
0 to
1,700
0 to
1,700
100 to
1,800
0 to
2,300
0 to
1,300
qF 300
to
2,300
0.0 to
900.0
100
to
1,500
0.0 to
750.0
199.9
to 700.0
0 to
1,100
100
to
1,500
0.0 to
750.0
199.9
to 700.0
300
to
2,300
0 to
3,000
0 to
3,000
300 to
3,200
0 to
4,100
0 to
2,300
Setting 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Input (switch selectable) Current input Voltage input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Range One of following ranges depending on results of scaling
1999 to 9999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
Setting 17 18 19 20 21
http://www.ia.omron.com/
5
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
E5EK
Characteristics
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of 100qC or less is r2qC r1 digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is r2qC r1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400qC or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200qC or less is r3qC r1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (r0.3% of the indicated value or r3qC, whichever is greater) r1digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (r0.3% or r2qC, whichever is greater) r1 digit maximum.
2. For Programmable Models.
3. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
Indication accuracy (See note 1.) Thermocouple:
(r0.3% of indication value or r1qC, whichever greater) r1 digit max.
Platinum resistance thermometer:
(r0.2% of indication value or r0.8qC, whichever greater) r1 digit max.
Analog input: r0.2% FS r1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 or 199.9 or 999.9 (decimal point position dependent on input type or result of scaling)
Set time (See note 2.) 0 to 99 hrs 59 min or 0 to 99 min 59 s
Program capacity (See note 2.) 4 p
atterns, 16 steps
Programming method (See note 2.) Time or ramp setting method
Time accuracy (See note 2.) r0.2% (r500 ms) of the set value
Sampling period (See note 3.) Temperature input: 250 ms
Current/voltage input: 100 ms
Insulation resistance 20 M: min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance
Malfunction: 10 to 55 Hz, 10 m/s
2
(approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s
2
(approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction: 200 m/s
2
min. (approx. 20G), 3 times each in 6 directions
(100 m/s
2
(approx. 10G) applied to the relay)
Destruction: 300 m/s
2
min. (approx. 30G), 3 times each in 6 directions
Ambient temperature Operating: 10qC to 55qC (with no icing)/3-year warranty period: –10qC to 50qC
Storage: 25qC to 65qC (with no icing)
Ambient humidity Operating: 35% to 85%
Degree of protection Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight E5AK: approx. 450 g
E5EK: approx. 320 g
Mounting bracket: approx. 65 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL1092, CSA22.2 No. 142, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
http://www.ia.omron.com/
6
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
E5EK
Output Unit Ratings and Characteristics
Note: An output relay (1 A at 250 VAC) is mounted on the position-proportional model. (When replacing, use the E53-R.)
Option Unit Ratings and Characteristics
Note: Event input is used for switching the target value, run or stop command, or automatic and manual mode with an external signal input.
Current Transformer Ratings
Heater Burnout Alarm
Note: 1. Use the K2CU-F@@A-@GS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.
Model Specifications
E53-R Relay output 5 A at 250 VAC (resistive load)
E53-S SSR output 1 A at 75 to 250 VAC (resistive load)
E53-Q Voltage output NPN: 40 mA at 12 VDC (with short-circuit protection)
E53-Q3 NPN: 20 mA at 24 VDC (with short-circuit protection)
E53-Q4 PNP: 20 mA at 24 VDC (with short-circuit protection)
E53-C3 Linear current output 4 to 20 mA, permissible load impedance: 600 : max., resolution: approx. 2,600
E53-C3D 0 to 20 mA, permissible load impedance: 600 : max., resolution: approx. 2,600
E53-V34 Linear voltage output 0 to 10 VDC, permissible load impedance: 1 k: min., resolution: approx. 2,600
E53-V35 0 to 5 VDC, permissible load impedance: 1 k: min., resolution: approx. 2,600
Model Specifications
E53-AKB Event input Contact input:
ON: 1 k: max., OFF: 100 k: min.
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
E53-EN01 Communications RS-232C Transmission method: Half-duplex
Synchronization method: Start-stop synchronization (asynchronous method)
Baud rate: 1.2/2.4/4.8/9.6/19.2 kbps
Transmission code: ASCII
E53-EN02 RS-422
E53-EN03 RS-485
E53-AKF Transfer output 4 to 20 mA:
Permissible load impedance: 600 : max.
Resolution: approx. 2,600
Dielectric strength 1,000 VAC (for 1 min)
Vibration resistance
50 Hz, 98 m/s
2
(10G)
Weight E54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g
Accessories (E54-CT3 only) Armature: 2; Plug: 2
Max. heater current Single-phase 50 A VAC (See note 1.)
Heater current value display accuracy r5% FSr1 digit max.
Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A) (See note 2.)
Min. detection ON time 190 ms (See note 3.)

E54-CT3

Mfr. #:
Manufacturer:
Description:
Current Transformer Sensors Current Transformers Transformer for TC Heater curr 50A max