1Description
Configurable 3-way isolating amplifier
MINI MCR-SL-U-UI
© PHOENIX CONTACT
Data sheet
The 6.2 mm wide MINI MCR-SL-U-UI(-SP)(-NC) configurable
3-way isolating amplifier is used to electrically isolate, condi-
tion, amplify, and filter standard signals.
On the input side, 0 ... 24 V and 0 ... 30 V signals can be pro-
cessed.
The standard analog signals 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V,
2 ... 10 V, 0 ... 5 V or 1 ... 5 V are available electrically isolated
on the output side.
The DIP switches, which can be accessed on the side of the
housing, are used to configure the input and output signal
ranges.
The power supply (19.2..30 V DC) can be supplied either via
connection terminal blocks "3"/"4" or "7"/"8" on the modules
or in conjunction with the DIN rail connector. Please refer to
the section titled "Power supply" for more information.
Features
Configurable 3-way isolating amplifier
Input and output signal range configurable via DIP
switches
Approval for Ex-zone 2 (nA)
Screw or spring-cage connection can be provided
Can be supplied configured or unconfigured
Attention: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog
.
This data sheet is valid for all products listed on the following page:
101744_en_05
2012-01-05
MINI MCR-SL-U-UI
101744_en_05 PHOENIX CONTACT 2
2Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
3.1 Order key .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 4
5 Safety regulations and installation notes.................................................................................. 6
5.1 Installation notes ................................................................................................................. 6
5.2 Installation in the Ex area (zone 2)............................................................................................ 6
6 Installation ............................................................................................................................... 7
6.1 Connection notes ................................................................................................................ 7
6.2 Structure ........................................................................................................................... 7
6.3 Block diagram..................................................................................................................... 7
6.4 Power supply...................................................................................................................... 7
6.5 Assembly........................................................................................................................... 8
6.6 Connecting the wires ............................................................................................................ 8
7 Configuration ........................................................................................................................... 9
7.1 Configuration table............................................................................................................... 9
8 Adjustment .............................................................................................................................. 9
9 Connection/application example ........................................................................................... 10
MINI MCR-SL-U-UI
101744_en_05 PHOENIX CONTACT 3
3.1 Order key
(standard configuration entered as example)
Description Type Order No. Pcs. / Pkt.
MCR 3-way isolation amplifier, with configurable input/output, for electrical
isolation and conversion of analog signals up to 30 V, with screw connec-
tion, order configuration
MINI MCR-SL-U-UI 2864053 1
MCR 3-way isolation amplifier, with configurable input/output, for electrical
isolation and conversion of analog signals up to 30 V, with spring-cage con-
nection, order configuration
MINI MCR-SL-U-UI-SP 2811213 1
MCR 3-way isolation amplifier, with configurable input/output, for electrical
isolation and conversion of analog signals up to 30 V, with screw connec-
tion, standard configuration
MINI MCR-SL-U-UI-NC 2865007 1
MCR 3-way isolation amplifier, with configurable input/output, for electrical
isolation and conversion of analog signals up to 30 V, with spring-cage con-
nection, standard configuration
MINI MCR-SL-U-UI-SP-NC 2810078 1
3Ordering data
Accessories Type Order No. Pcs. / Pkt.
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rails according to EN60715
ME 6,2 TBUS-2 1,5/5-ST-3,81 GN 2869728 10
MCR power terminal block for supplying several MINI Analog modules via
the DIN rail connectors, with screw connection, current consumption up to
max. 2A
MINI MCR-SL-PTB 2864134 1
MCR power terminal block for supplying several MINI-ANALOG modules
via the DIN rail connectors, with spring-cage connection, current consump-
tion up to max. 2A
MINI MCR-SL-PTB-SP 2864147 1
Eight MINI analog signal converters with screw connection method can be
connected to a control system using a system adapter and system cabling
with a minimum of wiring and very low error risk.
MINI MCR-SL-V8-FLK 16-A 2811268 1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A
MINI-SYS-PS-100-240AC/24DC/1.5 2866983 1
DIN rail power supply unit, primary-switched mode, slim design, output: 24
V DC / 1.5 A, ATEX approval
MINI-PS-100-240AC/24DC/1.5/EX 2866653 1
Label for extended marking of MINI MCR modules in connection with the
MINI MCR-DKL
MINI MCR-DKL-LABEL 2810272 10
Fold up transparent cover for MINI MCR modules with additional labeling
option using insert strips and flat Zack marker strip 6.2 mm
MINI MCR DKL 2308111 10
2864053 = IN38 = 0 ... 24 V OUT01 = 0 ... 20 mA NONE = Without factory
...-U-UI IN39 = 0 ... 30 V OUT02 = 4 ... 20 mA
OUT03 = 0 ... 10 V
2811213 = OUT04 = 2 ... 10 V
...-U-UI-SP OUT05 = 0 ... 5 V
OUT06 = 1 ... 5 V
Order No.
Input Output Factory calibration certificate
2864053 / IN39 / OUT01 / NONE

2810078

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules MINI MCR-SL-U-UI- SP-NC
Lifecycle:
New from this manufacturer.