PSR-PS20
106252_en_02 PHOENIX CONTACT 4
Switching capacity min. 60 mW
Mechanical service life 10 x 10
6
cycles
Output fuse 6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)
150 mA fast blow (Confirmation current path)
Output data
Alarm outputs
Number of outputs 1 (digital, PNP)
Voltage 22 V DC (U
D
-2V)
Current max. 100 mA
Maximum inrush current 500 mA (t=1ms at U
s
)
Short-circuit protection no
General data
Relay type Electromechanically forcibly guided, dust-proof relay.
Nominal operating mode 100% operating factor
Degree of protection IP20
Min. degree of protection of inst. location IP54
Mounting type DIN rail mounting
Mounting position vertical, horizontal, with front of module upward
Assembly instructions See derating curve
Dimensions (W/H/D) 6.8 x 93.1 x 102.5 mm
Type of housing PBT yellow
Clearances and creepage distances between the power circuits DINEN50178, EN60079-15
Rated insulation voltage 250 V AC
Rated surge voltage/insulation Safe isolation, 6kV reinforced insulation from control circuit, start circuit, confir-
mation current path, signal output to the enabling current path; 4 kV/basic insula-
tion between all current paths and housing
Pollution degree 2
Surge voltage category III
Connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 26 ... 12
Stripping length 12 mm
Screw thread M3
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Maximum altitude max. 2000 m (Above sea level)
Shock 15g
Vibration (operation) 2g
Conformance / approvals
Conformance CE-compliant
Approvals
UL, USA / Canada ( E140324 ) cULus
PSR-PS20
106252_en_02 PHOENIX CONTACT 5
UL, USA / Canada ( E360692 ) Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X
Shipbuilding GL applied for
Functional Safety in accordance with IEC 61508 to SIL 3
Conformance / approvals
Safety data
Stop category according to IEC 60204 0
Safety parameters for IEC 61508 - High demand
Equipment type Type A
HFT 1
SIL 3 (<15%of the overall SIL)
PFH
d
1.95x10
-10
(4ADC13; 5AAC15; 8760switching cycles/year)
Demand rate < 12 Months
Proof test interval 240 Months
Duration of use 240 Months
For use in high-demand applications, the diagnostics function must be implemented via the confirmation current path.
Alternative illustration of the device as 1001 structure for process customers
Equipment type Type A
HFT 0
SIL 3 (<15%of the overall SIL)
Safe Failure Fraction (SFF) 99.98 %
SD 989.32 FIT
SU 148.96 FIT
DD 52.58 FIT
DU 0.20 FIT
Total 1191.06 FIT
MTBF 80.63 Years
PFH 1.95x10
-10
(4ADC13; 5AAC15; 8760switching cycles/year)
Safety parameters for IEC 61508 - Low demand
Equipment type Type A
HFT 1
SIL 3 (<15%of the overall SIL)
PFD
avg
1.27 x 10
-4
Proof test interval 72 Months
Duration of use 240 Months
Alternative illustration of the device as 1001 structure for process customers
Equipment type Type A
HFT 0
SIL 3 (<15%of the overall SIL)
Safe Failure Fraction (SFF) 99.66 %
SD 0 FIT
SU 1579 FIT
DD 0 FIT
DU 5.392 FIT
Total 1584 FIT
MTBF 63 Years
PFD
avg
2.36 x 10
-5
(For T1 = 1 year)
PSR-PS20
106252_en_02 PHOENIX CONTACT 6
5Safety notes
WARNING: Risk of electric shock
During operation, parts of electrical switching
devices carry hazardous voltages.
Before working on the switching device, dis-
connect the power.
Please observe the safety regulations of elec-
trical engineering and industrial safety and lia-
bility associations!
Disregarding these safety regulations may re-
sult in death, serious personal injury or dam-
age to equipment.
Startup, mounting, modifications, and up-
grades should only be carried out by a skilled
electrical engineer!
WARNING: Risk of automatic machine re-
start!
For emergency stop applications, the ma-
chine must be prevented from restarting auto-
matically by a higher-level control system.
Protective covers must not be removed when
operating electrical switching devices.
WARNING: Danger due to faulty devices!
The devices may be damaged following an er-
ror and correct operation can no longer be en-
sured.
In the event of an error, replace the device im-
mediately.
Repairs to the device, especially if the hous-
ing must be opened, may only be carried out
by the manufacturer or authorized persons.
Otherwise the warranty is invalidated.
WARNING: Risk due to incorrect installa-
tion
For reliable operation, the safety relay must
be installed in housing protected from dust
and humidity (IP54).
Carry out wiring according to the application.
Refer to the “Application examples” section
for this.
WARNING: Risk due to welded relay con-
tacts
A suitable and effective protective circuit is to
be provided for inductive loads. This is to be
implemented parallel to the load and not par-
allel to the switch contact.
WARNING: danger due to magnetic inter-
ference!
Do not use the device in the vicinity of strong
magnetic fields (e.g.,caused by transformers
or magnetic iron). The magnetic field strength
of the environment must not exceed 30A/m.
NOTE: Risk of damage to equipment due
to noise emissions
When operating relay modules the operator
must meet the requirements for noise emis-
sion for electrical and electronic equipment
(EN 61000-6-4) on the contact side and, if re-
quired, take appropriate measures.
NOTE: Risk of damage to equipment due
to noise emissions
This is a Class A product. In a domestic envi-
ronment it may cause radion inteference, in
which case the user may be required to take
adequate measures.
Only use power supply units with safe isola-
tion and SELV/PELV in accordance with EN
50178/VDE 0160 (SELV/PELV).
NOTE: Electrostatic discharge!
The device contains components that can be
damaged or destroyed by electrostatic dis-
charge. When handling the device, observe
the necessary safety precautions against
electrostatic discharge (ESD) according to
EN 61340-5-1 and EN 61340-5-2.

2700356

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Safety Relays PSR-PS20-1NO-1NC- 24DC-SC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet