PSR-PS20
106252_en_02 PHOENIX CONTACT 7
5.1 Installation in the Ex area (class I, zone 2) Ambient temperature in hazardous areas
(class I, zone 2)
Observe the derating curves.
Observe the special temperature conditions according to
the rating plate.
5.2 Installation in areas with a danger of dust
explosions
WARNING: Explosion hazard
The device should be installed in a housing
(control or distributor box) that fulfills the re-
quirements of EN60079-15:2010
(IEC60079-15:20104th ED.) and at least
IP54 (EN/IEC60529) degree of protection.
WARNING: Explosion hazard
The device must be used in no more than a
pollution degree2 environment as defined by
EN/IEC60664-1.
WARNING: Explosion hazard
When installing and connecting the supply
and signal circuits observe the requirements
of EN/IEC60079-14. Only devices suitable
for operation in Ex zone2 and the conditions
at the application site may be connected to
the circuits in zone2.
In potentially explosive areas, only connect
and disconnect cables when the power is dis-
connected.
WARNING: Explosion hazard
The device must be stopped and immediately
removed from the Ex area if it is damaged or
was subject to an impermissible load or
stored incorrectly or if it malfunctions.
WARNING: Explosion hazard
The device is not designed for use in atmo-
spheres with a danger of dust explosions.
Output
250 V AC / 24 V DC
6 A, Resistive
B300, R300
24 V DC
100 mA
Ambient
Temperature
-20 °C to 65 °C
NO-contact DO-contact
Resistive
PSR-PS20
106252_en_02 PHOENIX CONTACT 8
6 Basic circuit diagram
Figure 1 Block diagram
Key:
7Derating
7.1 Vertical mounting position
Figure 2 Derating curve - vertical mounting position with
connected modules
Expanded ambient temperature range (with no distance): up
to +70°C
Conditions:
7.2 Horizontal mounting position
Figure 3 Derating curve - horizontal mounting position
with connected modules
Expanded ambient temperature range (with no distance): up
to +70°C
Conditions:
Designation Explanation
A1 +24V control input with active error ac-
knowledgment
A2 0 V (GND)
M1 Signal output (PNP)
21 +24V diagnostics input
22 Diagnostic output +24V
13/14 Enabling current path, undelayed
Confirmation current path 21/22 (N/C contact)
is not an electrically isolated current path and
may only be connected to a maximum voltage
of 26.4V in relation to A2.
M1
A1
A2
PWR
24V DC
PSR-PS20
ERR
DGN
K1/2
K1
K2
13
14
21
22
Max. rated control supply voltage 24VDC
Max. total current of the enabling current path 1A
2
Max. rated control supply voltage 24VDC
Max. total current of the enabling current path 250mA
2
10 20 30 40 50 60 70
20
30
40
0
T[°C]
A
I[A]
TH
²
2
36
12
4
55
65
25
10
10 20 30 40 50 60 70
10
20
30
40
0
T[°C]
A
I[A]
TH
²²
1
36
16
6
55 65
PSR-PS20
106252_en_02 PHOENIX CONTACT 9
7.3 Mounting position with module front at the top
Figure 4 Derating curve - mounting position with module
front at the top and aligned modules
Expanded ambient temperature range (with no distance): up
to +70°C
Conditions:
8Load curve
8.1 Ohmic load
Figure 5 Relay load curve - ohmic load
Max. rated control supply voltage 24VDC
Max. total current of the enabling current path 250mA
2
10 20 30 40 50 60 70
20
30
40
0
2
36
12
2
55
65
25
10
T [°C]
A
I[A]
TH
²
2
I [A]
DC
U[V]
DC
10
0,1
20
50
100
200
500
1000
0,20,5 1 2 510