RST-10000-24

10000W Power Supply with Single Output
RST-10000 series
Model Encoding
Description
RST-10000 is a 10KW single output enclosed type AC/DC power supply. This series operates for the wide
range three phase AC input (3 phase 3 wire / 196~305VAC or 3 phase 4 wire / Y 340~530VAC) and offers
the models with the DC output mostly demanded from the industry. Each model is cooled by the built-in
fan with fan speed control, working for the temperature up to ,70 . Moreover, RST-10000 provides vast
design flexibility by equipping various built-in functions such as the output programming, active current
sharing, remote ON-OFF control, auxiliary power, etc.
Features
3 3-wire / 196~305VAC or 3 4-wire / Y 340~530VAC ψ△ ψ
wide input range
Built-in active PFC function
High efficiency up to 91%
Forced air cooling by built-in DC fan
Output voltage and constant current level programmable
Active current sharing up to 20000W (1+1)
Built-in remote ON-OFF control / Remote sense
/ Auxilary power / Alarm signal
Protections: Short circuit / Overload / Over voltage /
Over temperature / Fan fail
5 years warranty
Bauar
Sicherheit
egel gema
t gepru ft
od
be
www.
ID 2000000000
tuv.com
wac g
os
16.7
Dimension
L
540
21.3
W
424
H
83.5(2U)
(2U)
mm
inch3.29
*
*
*
*
*
*
Safety: UL/EN/IEC 60950-1
EMC: EN 55022 / 55024
Factory control or automation apparatus
Test and measurement instrument
Laser related machine
Burn-in facility
RF application
Electric scooter or vehicle charger station
Constant current source
Certificates
Applications
File Name:RST-10000-SPEC 2018-01-15
RST -- 10000 24
Output voltage (24V/36V/48V)
Output wattage
Series name
SPECIFICATION
10000W Power Supply with Single Output
RST-10000 series
File Name:RST-10000-SPEC 2018-01-15
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
ALARM SIGNAL OUTPUT
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD(OLP)
OVER VOLTAGE
AC CURRENT (Typ.)
2200ms, 80ms at full load
20ms / 230VAC at 75% load 14ms / 230VAC at full load
3 3-wire / 196 ~ 305VAC or 3 4-wire / Y 340 ~ 530VACψ△ ψ
47 ~ 63Hz
30A/230VAC( ) 18A/400VAC( / Y)
3 3-wire / 3 4-wireψ△ ψ
150A/230VAC( ) 100A/400VAC( / Y)3 3-wire / 3 4-wireψ△ ψ
<7mA / 305VAC(Y 530VAC)
100 ~ 112% rated output power
User selectable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70 (Refer to "Derating Curve")
AC fail, DC OK, fan fail, OTP. Please refer to the Function Manual.
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
±℃ 0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
50K hrs min. Telcordia SR-332 (Bellcore) ; 17K hrs min. MIL-HDBK-217F (25 )
540*424*83.5mm (L*W*H)
23.5Kg; 1pcs/23.5Kg/2.82CUFT
89% 91%90%
1. All parameters NOT specially mentioned are measured at 230VAC(Y 400VAC) input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. During withstand voltage and isolation resistance testing, the screw A shall be temporarily removed, and shall be installed back after the testing.
5. There is high possibility to trigger the floating over voltage protection when PV voltage is trimmed from a high voltage level to a lower voltage level at light
load or no load condition. It is suggested that turn off the power supply and set PV voltage to the lowest level, then adjust output voltage to a desired value.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.1300 900 2 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
POWER FACTOR (Typ.) 0.95/230VAC(400VAC) at full load
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
WITHSTAND VOLTAGE Note.4
ISOLATION RESISTANCE
Note.4
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 6)
PROTECTION
Shut down o/p voltage, recovers automatically after temperature goes down
30 ~ 33.6V 60 ~ 67.2V45 ~ 50.4V
±0.5% ±0.5%±0.5%
±0.5% ±0.5%±0.5%
±1.0%
Can be adjusted via built-in potentiometer
±1.0%±1.0%
150mVp-p
23.5 ~ 28.8V
200mVp-p200mVp-p
47 ~ 57.6V35 ~ 43.2V
24V
400A
0 ~ 400A
9600W
48V36V
210A276A
0 ~ 210A0 ~ 276A
10080W9936W
RST-10000-24 RST-10000-48RST-10000-36
REMOTE SENSE
Compensate voltage drop on the load wiring up to 0.3V. Please refer to the Function Manual.
REMOTE ON-OFF CONTROL
AUXILIARY POWER
CURRENT SHARING
By electrical signal or dry contact Power ON:open Power OFF:short. Please refer to the Function Manual.
12V@0.1A(Only for Remote ON/OFF control)
Up to 20000W or (1+1) units. Please refer to the Function Manual.
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class A
Class A
-----
-----
EMC IMMUNITY
EMC EMISSION
CONSTANT CURRENT LEVEL PROGRAMMABLE
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Adjustment of output voltage is allowable to between 20 ~ 120% of nominal output voltage. Please refer to the Function Manual.
Adjustment of constant current level is allowable to between 20 ~ 100% of rated current. Please refer to the Function Manual.
OUTPUT VOLTAGE PROGRAMMABLE
78
80
82
84
86
88
90
92
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
400V(Y )
230V(? )
PFC fosc : 70KHz
PWM fosc : 100KHz
O.V.P.
FG
I/P
-V
-S
CS
PV
+V
+S
RECTIFIERS
&
FILTER
SWITCHING
CIRCUIT
POWER
CONTROL
PFC
CONTROL
&
RECTIFIERS
PFC
FILTER
EMI
DETECTION
CIRCUIT
O.T.P.
CURRENT
LIMIT
PC
DC-OK
Remote ON-OFF
ISOLATOR
&
RELAY
AC-FAIL
FAN-FAIL
OTP
AUX POWER
(+12V/0.1A)
RECTIFIERS
AUX
&
FILTER
POWER
FAN
LOAD (%)
20
40
60
50
80
100
100
90
80
70
60
50
LOAD (%)
-30010203040506070
196 210 220 230 240 250 260 270 280 290 305
91.07%/230VAC ( )
91.26%/400VAC(Y)
(HORIZONTAL)
3ψ△
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (V) 60Hz
340 360 380 400 420 440 460 480 500 515 530
3Yψ
Derating Curve
Static Characteristics
EFFICIENCY (%)
LOAD
MODEL
INPUT
24V
9600W 9936W 10080W
400A 276A 210A
196~305VAC
340~530VAC
36V 48V
Efficiency vs Load (48V Model)
10000W Power Supply with Single Output
RST-10000 series
File Name:RST-10000-SPEC 2018-01-15
Block Diagram

RST-10000-24

Mfr. #:
Manufacturer:
MEAN WELL
Description:
Switching Power Supplies 9600W 24V 400A 3 Phase AC input
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet