2903116

https://www.phoenixcontact.com/us/products/2903116
04/26/2016Page1/8
Hybrid motor starter-ELR H5-IES-SC-SWD/500AC-0,6-2903116
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Hybrid motor starter for reversing 3~AC motors up to 550VAC, 0.6A output current, adjustable overload
shutdown and safe emergency stop up to PLe/SIL 3 and SmartWire-DT
adapter as a set.
Key Commercial Data
Packing unit 1 pc
Custom tariff number 85371099
Country of origin Germany
Technical data
Dimensions
Width 22.5 mm
Height 165 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -5 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Degree of protection IP20
Device supply
Rated control circuit supply voltage U
S
24 V DC
Control supply voltage range 19.2 V DC ... 30 V DC
Rated control supply current I
S
40 mA
Protective circuit Reverse polarity protection Parallel polarity protection diode
Surge protection
Input data
Input name Control input right/left
https://www.phoenixcontact.com/us/products/2903116
04/26/2016Page2/8
Hybrid motor starter-ELR H5-IES-SC-SWD/500AC-0,6-2903116
Technical data
Input data
Rated actuating voltage U
C
24 V DC
Voltage range 19.2 V DC ... 30 V DC
Rated actuating current I
C
5 mA
Switching threshold 9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level < 5 V DC (For EMERGENCY STOP)
Typical turn-off time < 30 ms
Output data load output
Output name AC output
Rated operating voltage U
e
500 V AC
Operating voltage range 42 V AC ... 550 V AC
Mains frequency 50 Hz
60 Hz
Load current range 75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947 Class 10A
Cooling time 20 min. (for auto reset)
Leakage current 0 mA
Protective circuit Surge protection
Output data reply output
Output name Acknowledge output
Note Confirmation: floating change-over contact, signal contact
Contact type 1 PDT
Switching capacity according to IEC 60947-5-1 3 A (230 V, AC15)
2 A (24 V, DC13)
General
Switching frequency ≤ 2 Hz (Load-dependent)
Mounting position vertical (horizontal DIN rail, motor output below)
Assembly instructions alignable, for spacing see derating
Operating mode 100% operating factor
Maximum power dissipation 2.5 W
Minimum power dissipation 0.88 W
Operating voltage display Green LED
Status display Yellow LED
Indication Red LED
Connection data, input side
https://www.phoenixcontact.com/us/products/2903116
04/26/2016Page3/8
Hybrid motor starter-ELR H5-IES-SC-SWD/500AC-0,6-2903116
Technical data
Connection data, input side
Connection name Control circuits
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Torque 0.5 Nm ... 0.6 Nm
Connection data, output side
Connection name Load circuit
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Torque 0.5 Nm ... 0.6 Nm
Standards/regulations
Designation Standards/regulations
Standards/regulations IEC60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Insulation characteristics
Rated insulation voltage 500 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Designation
Insulation characteristics between the control input and control supply
voltage, and auxiliary circuit to the main circuit
Insulation Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
Designation
Isolation characteristics between the control input and control supply
voltage to auxiliary circuit
Insulation Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC

2903116

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules ELR H5-IES-SC SWD/500AC-0 6
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union