https://www.phoenixcontact.com/us/products/2903116
04/26/2016Page3/8
Hybrid motor starter-ELR H5-IES-SC-SWD/500AC-0,6-2903116
Technical data
Connection data, input side
Connection name Control circuits
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Torque 0.5 Nm ... 0.6 Nm
Connection data, output side
Connection name Load circuit
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Torque 0.5 Nm ... 0.6 Nm
Standards/regulations
Designation Standards/regulations
Standards/regulations IEC60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Insulation characteristics
Rated insulation voltage 500 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Designation
Insulation characteristics between the control input and control supply
voltage, and auxiliary circuit to the main circuit
Insulation Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Safe isolation (EN 50178) at operating voltage ≤ 300 V AC
Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
Designation
Isolation characteristics between the control input and control supply
voltage to auxiliary circuit
Insulation Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC