https://www.phoenixcontact.com/us/products/2903116
04/26/2016Page4/8
Hybrid motor starter-ELR H5-IES-SC-SWD/500AC-0,6-2903116
Technical data
Insulation characteristics
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Approvals/conformities
Safety Integrity Level according to IEC 61508 SIL 3 (safe shutdown)
SIL 2 (motor protection)
Category acc. to EN ISO 13849 3 (Safe shutdown)
Performance level according to ISO 13849 e (Safe shutdown)
ATEX II (2) G [Ex e] [Ex d] [Ex px]
II (2) D [Ex t] [Ex p]
EU type-examination certificate PTB 07 ATEX 3145
UL data
SCCR 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA 0.6 A (480 V AC)
Group installation 20 A (class RK5, SCCR 5kA, 24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, 24 - 14 AWG max, solid and stranded)
Category code NLDX / NRNT
Standards and Regulations
Designation Standards/regulations
Standards/regulations IEC60947-1
EN 60947-4-2
IEC 61508
ISO 13849
ATEX II (2) G [Ex e] [Ex d] [Ex px]
II (2) D [Ex t] [Ex p]
Classifications
eCl@ss
eCl@ss 4.0 27142001
eCl@ss 4.1 27142001
eCl@ss 5.0 27142001
eCl@ss 5.1 27371601
eCl@ss 6.0 27371601
eCl@ss 7.0 27371601
eCl@ss 8.0 27370905
eCl@ss 9.0 27370905