PHOENIX CONTACT page 7 of 10
3-Phase Power Supply, Primary Switch Mode for Universal Use – QUINT 48 V DC/10 A
6.4. Connection of Various Types of Network: 3 x 400 - 500 V AC Networks
Figure 09
TN-S network TN-C network TT network IT network
+–
QUINT
L1
L2
L3
N
PE
L1 PEL2 L3
+–
QUINT
L1
L2
L3
PEN
L1 PEL2 L3
+–
QUINT
L1
L2
L3
N
L1 PEL2 L3
L1
L2
L3
+
L1 PE
L2 L3
QUINT
Outpu
tD
+
DC
OK
13
D
Adjust
42-56V
Input 3AC 400-500V
L1 L2
5
Q
14
L3
11
11
55
55
Figure 10
Connection Cable:
The following cable cross sections can be connected:
For reliable and safe-to-touch
connection: Strip 8 mm (0.31 in.)
from the input side connector ends
and 10 mm (0.39 in.) from the output/signal connector
ends.
6.5. Input (
11
11
, Figure 10)
The 3 x 400 - 500 V AC connection is made using
screw connections L1, L2, L3, and
55
55
.
Protecting the Primary Side
The device must be installed according to the
specications of EN 60 950. It must be possible to
switch off the device using a suitable disconnecting
device outside the power supply. For example, primary
side line protection could be used.
Three external thermomagnetic fuses are required to
protect the device. Even in the event of a phase failure,
continuous operation is ensured with nominal power.
Recommended Fuse:
3 x circuit breaker 6 A, 10 A or 16 A, Characteristic B
(or equivalent). A suitable fuse must be tted for DC
applications.
Solid
[mm
2
]
Flexible
[mm
2
]
AWGTorque
[Nm] [Ib in.]
11
11
Input:
0.2 - 6 0.2 - 4 25 - 10 0.5 - 0.6 4.4 - 5.3
22
22
Output:
0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 10.6 - 13.3
33
33
Signal:
0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 10.6 - 13.3
[L] mm
If an external fuse is blown, this is most
probably due to a device fault.
In this case, the device should be
checked in the factory.
PHOENIX CONTACT page 8 of 10
3-Phase Power Supply, Primary Switch Mode for Universal Use – QUINT 48 V DC/10 A
Figure 11
Output DC 48V 10A
+ +
– –
DC
OK
13
DC OK
Adjust
42-56V
V
14
3
A
U
DC OK
O
I
n
O
44
44
33
33
22
22
66
66
DC OK
+ + – –
Output 48V DC
DC OK
13 14
Figure 12
Electrically isolated contact
60 V AC/DC
0.5 A, maximum
6.6. Output (Figure 11)
The 48 V DC connection is made using the "+" and
"–" screw connections on the screw connection
22
22
. The
output voltage set upon delivery is 48 V DC.
The output voltage can be adjusted from 40 to
56 V DC on the potentiometer
55
55
.
Protecting the Secondary Side:
The device is electronic short-circuit-proof and idling-
proof. In the event of an error, the output voltage is
limited to a maximum of 60 V DC.
It should be ensured that all output cables are the
correct size for the maximum output current or have
separate fuse protection.
The secondary side cables should have large cross
sections to keep voltage drops on the cables to a
minimum.
6.7. Signaling
Both DC OK outputs are used for preventive function
monitoring of the power supply. An electrically isolated
signal contact 44
44
and an active DC OK signal 33
33
are
available. In addition, the DC OK LED 66
66
can be used
to evaluate the function of the power supply directly at
the installation location.
Electrically Isolated Contact (Figure 12)
When opened, the electrically isolated signal contact
indicates that the output voltage has fallen more than
10% below the set value. Signals and ohmic loads up
to a maximum of 60 V and currents up to a maximum
of 0.5 A can be switched.
With heavy inductive loads, e.g., a relay, a suitable
protective circuit (e.g., free-wheeling diode) is required.
Active Signal Output (Figure 13)
The 24 V DC signal is between the "DC OK" and "-"
connection terminal blocks and can be loaded with
20 mA maximum. This signal output indicates that the
output voltage has fallen more than 10% below the set
value when "active high" changes to "low".
The DC OK signal is isolated from the power output.
This ensures that a separate supply does not enter
from devices connected in parallel.
The 24 V DC signal can be connected directly to the
logic input for evaluation.
Green "DC OK" LED
ON Flashing OFF
Active signal output U = 24 V U = 0 V U = 0 V
Electrically isolated Closed Open Open
Meaning Output voltage
greater than 90%
of the set voltage
Output voltage
less than 90% of
the set voltage
No voltage at the
output
Description Output voltage
and current OK
QUINT POWER
operating, but:
Error at the load
Current
consumption
greater than
I
BOOST
Output short
circuit
QUINT POWER
not operating,
because:
No mains
voltage present
•Primary side
fuse is blown
•Device is faulty
DC OK
+ + – –
Output 48V DC
DC OK
13 14
Figure 13
Active signal output
24 V DC
20 mA,
maximum
PHOENIX CONTACT page 9 of 10
3-Phase Power Supply, Primary Switch Mode for Universal Use – QUINT 48 V DC/10 A
DC OK
24 V DC
40 mA
+ + – –
Output 24V DC
DC OK
13 14
+ + – –
Output 24V DC
DC OK
13 14
Figure 14
Device 1 Device 2
I
BOOST
U
OUT
[
V
]
I
OUT
[
A
]
I
N
< 40 °C< 60 °C
U
N
Figure 15
480 W 620 W
48
10 13
Signal Loop (Figure 14)
The two signal outputs mentioned above can be
combined easily.
Example: Monitoring two devices
Use the active alarm output of device 1 and loop in
the electrically isolated alarm output of device 2. In the
event of an error, a group error message is generated.
It is possible to loop any number of devices.
This signal combination saves on wiring costs and
logic inputs.
DC OK LED
The green DC OK LED enables local function
evaluation in the control cabinet.
7. Function
7.1. Output Characteristic Curve
At ambient temperatures T
amb
< +40°C (+104°F),
the device can continuously supply 13 A with a 48 V DC
output voltage (P
out
= 620 W).
With heavy loads, the working point demonstrates
the U/I characteristic curve shown in Figure 14. The
output current is limited to I
BOOST
.
The secondary voltage is reduced until the short
circuit on the secondary side is removed.
The U/I characteristic curve ensures that both heavy
capacitive loads and devices with DC/DC converters
can be supplied by QUINT POWER in the input circuit
without any problems.
Connected fuses are reliably tripped. The selectivity
in your system conguration is ensured at all times.
7.2. Temperature Response
At an ambient temperature of up to +40°C (+104°F)
the device continuously supplies an output current of
13 A.
The device can supply a nominal output current of
10 A up to an ambient temperature of +60°C (+140°F).
The output power must be decreased by 2.5% per
Kelvin temperature increase for ambient temperatures
above +60°C (+140°F).
At ambient temperatures above +70°C (+158°F) or in
the event of a thermal overload, the device does not
switch off. The output power is decreased so low that
device protection is provided. Once the device has
cooled, the output power is increased again.
LED ON Normal operation of the power supply
LED
ashing
The output voltage has fallen by more than 10%.
There is a secondary load short circuit or overload
outside the POWER BOOST area.
LED OFF No mains voltage is present or there is a device fault.
0
0
40 6020
Figure 16
Output current [A]
13
10
Ambient temperature [°C]
U
OUT
= 48 V

2938219

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Power Supplies QUINT 3PHS 48VDC 10A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet