UNO-PS/1AC/24DC/30W
105516_en_00 PHOENIX CONTACT 10
7.3 Mounting on a DIN rail
The power supply unit can be installed on all 35 mm DIN rails
according to EN 60175.
Figure 3 Mounting on a DIN rail
7.4 Normal mounting position
When installed, the input terminal blocks must be at the bot-
tom and the output terminal blocks at the top.
If the power supply unit is installed in a mounting position
other than the normal mounting position, the output power
must be reduced.
Figure 4 Normal mounting position
AB
UNO-PS/1AC/24DC/30W
105516_en_00 PHOENIX CONTACT 11
8 Installing the power supply unit
8.1 Safety regulations and installation notes 8.2 Mains connection
The device can be connected to single-phase AC or three-
phase power grids (TN-S, TN-C, TT, and IT) while consider-
ing the nominal input voltage.
Figure 5 Network types
WARNING: risk of electric shock!
Only qualified specialist personnel may in-
stall, start up, and operate the device. Ob-
serve the national safety and accident
prevention regulations.
Prior to installation, disconnect the input volt-
age and make sure that it cannot be switched
on again unintentionally.
Mains connection must be performed by spe-
cialist personnel and protection against elec-
tric shock ensured.
Make sure that the device can be switched off
outside the power supply according to the
regulations in EN 60950 (e.g., by line protec-
tion on the primary side).
Cover termination area after installation in or-
der to avoid accidental contact with live parts
(e.g., by installing in a control cabinet).
Protect the device against ingress by foreign
bodies, e.g., paper clips or metal parts.
WARNING:
Make sure that all supply lines are sufficiently
dimensioned and have sufficient fuse protec-
tion.
Make sure that all output cables are dimen-
sioned accordingly for the maximum device
output current or have separate fuse protec-
tion.
NOTE:
Never open or repair the device yourself.
Internal fuses will only blow in the event of de-
vice malfunction. Do not modify or attempt to
repair the device. Send the device to the fac-
tory for examination.
For operation on two of the phase conductors
of a three-phase system, an isolating facility
for all poles must be provided.
TN-S TN-C
L
N
PE
+
LN
-
L
PEN
+
LN
-
TT iT
+
LN
-
L
N
+-
L
N
L1
L2
L3
UNO-PS/1AC/24DC/30W
105516_en_00 PHOENIX CONTACT 12
8.3 Device connections
Screw connection for input AC L/N
Figure 6 Screw connection for input AC L/N
Screw connection for output DC +/-
Figure 7 Screw connection for output DC +/-
8.4 Connecting cables
Figure 8 Connecting cables
1. Connect the supply lines to the input AC L/N connection
terminal blocks.
2. Connect the output cables to the output DC +/- connec-
tion terminal blocks.
The power supply unit is operational as soon as the input ter-
minal blocks are supplied with voltage.
Use copper cables with an operating temper-
ature > 75°C (ambient temperature < 55°C)
and > 90°C (ambient temperature < 75°C).