UNO-PS/1AC/24DC/30W
105516_en_00 PHOENIX CONTACT 4
4 Technical data
Input data
Nominal input voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
AC frequency range 45 Hz ... 65 Hz
Current consumption 0.5 A (120 V AC)
0.3 A (230 V AC)
Inrush current limitation < 20 A (typical)
I
2
t < 0.4 A
2
s
Typical response time < 1 s
Power failure bypass > 25 ms (120 V AC)
> 115 ms (230 V AC)
Protective circuit Transient surge protection Varistor
Input fuse, integrated 2 A (slow-blow, internal)
Choice of suitable fuses 6 A ... 16 A (Characteristics B, C, D, K)
Input connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Stripping length 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Output data
Nominal output voltage 24 V DC ±1%
Output current 1.25 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (Dynamic load change 10% ... 90%, 10 Hz)
< 0.1 % (change in input voltage ±10%)
Ascent time < 0.5 s (U
OUT
(10% ... 90%))
Residual ripple < 60 mV
PP
(with nominal values)
Connection in parallel yes, with redundancy module
Connection in series Yes
Protection against surge voltage on the output 35 V DC
Resistance to reverse feed < 35 V DC
Output connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Connection method 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
UNO-PS/1AC/24DC/30W
105516_en_00 PHOENIX CONTACT 5
Power consumption
Efficiency > 88 % (for 230 V AC and nominal values)
Maximum power dissipation NO-Load < 0.3 W
Power loss nominal load max. < 5 W
General data
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
MTBF > 500000 h (According to EN 29500)
Housing material polycarbonate
Foot latch material Plastic POM
Dimensions W / H / D 22.5 mm / 90 mm / 84 mm
Weight 0.15 kg
Security
Degree of protection IP20
Protection class II (in an enclosed control cabinet)
SELV IEC 60950-1 (SELV) and EN 60204 (PELV)
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 30 g in each direction, according to IEC 60068-2-27
Pollution degree 2
Climatic class 3K3 (in acc. with EN 60721)
Inflammability class in acc. with UL 94 (housing) V0
Standards
Electrical Equipment for Machinery EN 60204-1
Electrical safety (of information technology equipment - Safety - Part 1) IEC 60950-1/VDE 0805 (SELV)
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV IEC 60950-1 (SELV) and EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
Protection against electric shock DIN 57100-410
Limitation of mains harmonic currents EN 61000-3-2
Network version/undervoltage EN61000-4-11
Information technology equipment - Safety (CBScheme) CB Scheme
Approvals
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
NEC Class 2 as per UL 1310
CSA CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
UNO-PS/1AC/24DC/30W
105516_en_00 PHOENIX CONTACT 6
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
EN 61000-6-2 requirement Tested
Electrostatic discharge EN 61000-4-2
Housing contact discharge 4 kV (Test intensity 2) 6 kV (Test intensity 3)
Housing air discharge 8 kV (Test intensity 3) 8 kV (Test intensity 3)
Comments Criterion B Criterion B
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz ... 1 GHz 80 MHz ... 1 GHz
Test field strength 10 V/m 10 V/m
Frequency range 1.4 GHz ... 2 GHz 1 GHz ... 2 GHz
Test field strength 3 V/m 10 V/m
Frequency range 2 GHz ... 2.7 GHz 2 GHz ... 3 GHz
Test field strength 1 V/m 10 V/m
Comments Criterion A Criterion A
Fast transients (burst) EN 61000-4-4
Input 2 kV (Test intensity 3 - asymmetrical) 4 kV (Test intensity 4 - asymmetrical)
Output 2 kV (Test intensity 3 - asymmetrical) 2 kV (Test intensity 3 - asymmetrical)
Comments Criterion B Criterion A
Surge current loads (surge) EN 61000-4-5
Input 1 kV (Test intensity 2 - symmetrical)
2 kV (Test intensity 3 - asymmetrical)
2 kV (Test intensity 3 - symmetrical)
4 kV (Test intensity 4 - asymmetrical)
Output 0.5 kV (Test intensity 1 - symmetrical)
0.5 kV (Test intensity 1 - asymmetrical)
1 kV (Test intensity 2 - symmetrical)
2 kV (Test intensity 3 - asymmetrical)
Comments Criterion B Criterion A
Conducted interference EN 61000-4-6
Frequency range 10 kHz ... 80 MHz 10 kHz ... 80 MHz
Voltage 10 V (Test intensity 3) 10 V (Test intensity 3)
Comments Criterion A Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device it-
self.
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1
All technical specifications are nominal values and refer to a room temperature of 25°C and 70% relative hu-
midity at 100 m above sea level.
Current approvals can be found for the product in the download area.

2902991

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Power Supplies UNO-PS/1AC/24DC/30W PRIM SWCH SNGL PHASE
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union