PMC-05V015W1AA

TECHNICAL DATASHEET
PMC Panel Mount Power Supply
5V 15W 1
Phase
/ PMC-05V015W1AA
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (March 2013, Rev. 00)
4
Safety Standards / Directives
Electrical Safety
SIQ Bauart to EN60950-1, UL/cUL recognized to
UL60950-1 and CSA C22.2 No. 60950-1, CB scheme to
IEC60950-1, CCC to GB4943
CE In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
Material and Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input to Output 3.0 KVac
Input to Ground 1.5 KVac
Output to Ground 500 Vac
EMC
EMC / Emissions CISPR22, EN55022, FCC Title 47: Class B, GB9254
Immunity to
Electrostatic Discharge IEC61000-4-2 Level 4 Criteria A
1)
Air Discharge: 15kV
Contact Discharge: 8kV
Radiated Field IEC61000-4-3 Level 3 Criteria A
1)
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst IEC61000-4-4 Level 3 Criteria A
1)
2kV
Surge IEC61000-4-5 Level 3 Criteria A
1)
Common Mode
2)
: 2kV
Differential Mode
3)
: 1kV
Conducted IEC61000-4-6 Level 3 Criteria A
1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields IEC61000-4-8 Criteria A
1)
10A/Meter
Voltage Dips IEC61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave) IEC61000-4-12 Level 3 Criteria A
1)
Common Mode
2)
: 2kV
Differential Mode
3)
: 1kV
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
TECHNICAL DATASHEET
PMC Panel Mount Power Supply
5V 15W 1
Phase
/ PMC-05V015W1AA
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (March 2013, Rev. 00)
5
Block Diagram
Device Description
1) Input & Output terminal block connector
2) DC Voltage adjustment potentiometer
3) DC OK control LED (Green)
TECHNICAL DATASHEET
PMC Panel Mount Power Supply
5V 15W 1
Phase
/ PMC-05V015W1AA
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (March 2013, Rev. 00)
6
Dimensions
H x W x D: 77 x 51 x 28 mm
Engineering Data
De-rating VS surrounding air temperature
Note
1. Power supply components may degrade, or be
damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2. If the output capacity is not reduced when the
surrounding air temperature > 60°C, the device
may run into Over Temperature Protection.
When activated, the output voltage will go into
bouncing mode and will recover when the
surrounding air temperature is lowered or the
load is reduced as far as necessary to keep the
device in working condition.
3. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
4. In order for the device to function in the manner
intended, it is also necessary to keep a safety
distance of 20mm with adjacent units while the
device is in operation.
5. Depending on the surrounding air temperature
and output load delivered by the power supply,
the device housing can be very hot!
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation
> 60°C de-rate power by 2.5% / °C