59
Switching Power Supply S82K
Specifications Table – continued from previous page
Item Single output Dual
outputs
Single output
Power rating 3 W 7.5 W 7.5 W 15 W 30 W 50 W
90 W
100 W 240 W
Additional functions
Overload protection 105% to 160% (105% to 250% for dual outputs model, 101% to 111% for 90-W model) of rated load
current, automatic reset (See Note 6.)
Overvoltage protection
(See Note 7.)
No S82K-
24024T model only
Undervoltage alarm
indicator (DC LOW
indicator)
Yes (color: red) S82K-
24024T model only
Undervoltage alarm
output (DC LOW output)
No Yes S82K-
24024T model only
Parallel operation Not possible Possible (2 units max.)
Characteristics
Ambient
Operating See the derating curve in the Engineering Data section (no condensation or icing)
temperature
Storage –25qC to 65qC (-13qF to 149qF) with no condensation or icing
Ambient
Operating 25% to 85%
humidity
Storage 25% to 90%
Dielectric strength 3,000 VAC at 50/60 Hz for 1 min (between all inputs and outputs)
2,000 VAC at 50/60 Hz for 1 min (between all inputs and GR terminal)
1,000 VAC at 50/60 Hz for 1 min (between all outputs and GR terminal)
Alarm current: 10 mA (3- to 7.5-W models) 20 mA (15- to 100-W models) 25 mA (240-W models)
Insulation resistance 100 M: min. at 500 VDC (between all outputs and all inputs/GR terminal)
Vibration resistance Malfunction: 10 to 55 Hz, 0.375-mm (0.15-mm for 240-W model) single amplitude for 2 hrs each in X, Y,
and Z directions
Shock resistance Malfunction: 300 m/s
2
, 3 times each in rX, rY, and rZ directions
Screw tightening torque
0.74 N S m max. (See Note 8.)
Output indicator Yes (green)
Electromagnetic
interference
(See Note 3.)
Conforms to FCC class B Conforms to FCC class A
(This table continues on the next page.)
Note: 1. Use with DC voltage input is beyond the conditions of approval or conformance to applicable safety standards.
2. Use the 7.5-W single-output models under the load of 90% max. if the voltage range is between 90 and 110 VDC.
3. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
4. The output specification is defined at the power supply output terminals.
5. The settings for the output voltage must be within the following range:
+V: r1% of the rated value
–V: r5% of the rated value
6. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will
operate at a current of 95% to 160% of the rated load current. When using the 90-W model under the ambient temperature over
25qC, the protection function may operate at a current of 92% to 111% of the rated load current.
7. Circuit-breaker type. To reset, turn the input power supply OFF, then after 1 min has elapsed, turn the input power supply ON
again.
8. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
9. To ensure the emission ratings, a noise filter should be used on the output lines at the closest point.
(3- to 50-W models: S82Y-JF3-N, 90-W and 100-W models: S82Y-JF6-N)
10. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables (for S82K-P24024).
11. To meet Class 2 requirement with 100-W model, either a fuse or circuit breaker that is UL listed or CSA certified, and rated at
4.2 A max. should be used in the output of the power supply. Only then can the power supply output be considered as meeting
Class 2.