62
Switching Power Supply S82K
Specifications Table PFC Models (S82K-Pjjj24) – continued from previous page
Item
Single output
Power Rating 90 W 100 W 240 W
Characteristics
Ambient temperature
Operating See the derating curve in the Engineering Data section (no condensation or icing)
p
Storage –25qC to 65qC (no condensation or icing)
Ambient humidity
Operating 25% to 85%
y
Storage 25% to 90%
Dielectric strength 3,000 VAC at 50/60 Hz for 1 min. (between all inputs and outputs)
2,000 VAC at 50/60 Hz for 1 min. (between all inputs and GR terminal)
1,000 VAC at 50/60 Hz for 1 min. (between all outputs and GR terminal)
Alarm current: 20 mA (90- and 100-W models) 25 mA (240-W models)
Insulation resistance 100 M: min. at 500 VDC (between all outputs and all inputs/GR terminal)
Vibration resistance Malfunction:10 to 55 Hz, 0.375-mm single
amplitude for 2 hrs each in X, Y,
and Z directions
Malfunction:10 to 55 Hz, 0.15-mm
single amplitude for 2 hrs
each in X, Y, and Z
directions
Shock resistance Malfunction:150 m/s
2
, 3 times each in rX,
rY, and rZ directions
Malfunction:300 m/s
2
, 3 times each in
rX, rY, and rZ directions
Screw tightening torque
0.74 N S m max. (See Note 2.)
Output indicator Yes (Green)
Electromagnetic interference
(See Note 1.)
Conforms to FCC class A
EMC (See Notes 3, 4.) 90-, 100-W Models
(EMI): EN50081-1
Harmonic Current: EN61000-3-2 (200 VAC input only)
Emission Enclosure: EN55022 class B
Emission AC Mains: EN55022 class B
Emission Output Ports: EN55022 class A (with a recommended optional filter) (See
Note 3.)
240-W Model
(EMI): EN50081-2
Harmonic Current: EN61000-3-2
Emission Enclosure: EN55011 class A (See Note 4.)
Emission AC Mains: EN55011 class A
Common to All Models
(EMS): EN50082-2
Immunity ESD: EN61000-4-2: 4-kV contact discharge (level 2)
8-kV air discharge (level 3)
Immunity Burst: EN61000-4-4: 2-kV power-line (level 3)
2-kV output line (level 4)
Immunity Surge: EN61000-4-5: between 2-kV lines (except for 240-W
models)
between 4-kV line and FG (except for
240-W models)
Approved standards UL508 (Listing)/1950
Class 2 (UL1310)/Class 2 (CSA C22.2 No.
950) (See Note 5.)
CSA C22.2 No. 14/No. 950, EN50178
(VDE160), EN60950
Conforms to VDE0106/P100
UL508 (Listing)/1012
CSA C22.2 No. 14/E.B. 1402C,
EN50178 (VDE160), EN60950,
Conforms to VDE0106/P100
Weight 1,000 g max. 2,200 g max.
(The notes below apply to this page only.)
Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC)
2. Do not press down on the terminal block with a force exceeding 75 N while tightening the terminals.
3. To ensure the Emission Enclosure ratings, a noise filter should be used on the output lines at the closest point. (90- and 100-W
models: S82Y-JF6-N)
4. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables.
5. To meet Class-2 requirements with the 100-W model, either a fuse or circuit breaker that is UL listed or CSA certified, and rated
at 4.2 A max. should be used in the output of the power supply. Only then can the power supply output be considered as meet-
ing Class 2.
63
Switching Power Supply S82K
J REFERENCE VALUE
Item Value Definition
Reliability (MTBF) 135,000 hrs min. MTBF stands for Mean Time Between Failures, which is calculated according to the
probability of accidental device failures, and indicates reliability of devices.
Therefore, it does not necessarily represent a life of the product.
Life expectancy 8 yrs. min. The life expectancy indicates average operating hours under the ambient
temperature of 40qC and a load rate of 50%. Normally this is determined by the life
expectancy of the built-in aluminum electrolytic capacitor.
En
g
ineerin
g
Data
J DERATING CURVE
Load (%)
Ambient temperature (qC)
3-/7.5-/15-/30-/50-/100-W Models
Load (%)
Ambient temperature (qC)
Load (%)
Ambient temperature (qC)
Installation A
Installation A
Installation B
S82K-03005
Installation A
S82K-P10024:
85-VAC input
100-W Models with PFC
S82K-P10024:
85-VAC input
Installation B
65
65
90
Note: When using the 7.5-W single-output
models within the input voltage range
between 90 and 110 VDC, the load
rate will become 90% or less.
Parallel-Unit Operation
100-W Models without PFC
Installation A
Installation B
Single-Unit Operation Parallel-Unit Operation
240-W Model
Parallel-Unit Operation
Note: 100-VAC input: 85 to 132 VAC
Load (%)
Ambient temperature (qC)
S82K-P24024:
100-VAC input
(See Note.)
Load (%)
Ambient temperature (qC)
Single-Unit Operation
S82K-P24024:
100-VAC input
(See Note.)
Installation A
Installation A
90-W Models
Load (%)
Ambient temperature (qC)
S82K-P09024:
85-VAC input
Installation A
Installation B
65
70
90
240-W Model
Single-Unit Operation
Note: 100-VAC input: 85 to 132 VAC
64
Switching Power Supply S82K
(A) Standard (Vertical) Installation (B) Horizontal Installation
Top
Top
Note: Horizontal installation is not
permitted for 240-W models.
Mounting Position
The derating curve can be ensured for these two kinds of installations.
J OVERLOAD PROTECTION
The Power Supply is provided with an overload protection function that protects the load and the power supply from possible damage by
overcurrent. When the output current rises above a set value (refer to the table below), the protection function is triggered, decreasing the
output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared.
Single output Dual
outputs
Single output
3 W 7.5 W 7.5 W 15 W 30 W 50 W 90 W 100 W 240 W
Set value 105% to 160% of rated
load current
(See Note 1.)
105% to
250% of
rated load
current
105% to 160% of rated load current 101% to
111% of
rated load
current
(See Notes
2 and 3.)
105% to 160% of rated
load current
(See Note 3.)
Operation Inverted L drop type, automatic reset Inverted L
drop/intermittent
operation type,
automatic reset
Inverted L drop type, automatic reset
Note: 1. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the overload protection
function will operate at currents from 95% to 160% of the rated load current.
2. When using the 90-W model at an ambient temperature exceeding 25qC, the overload protection function will operate at
currents from 92% to 111% of the rated load current.
3. When using the 100-W model with PFC in parallel operation, the overload protection function will operate at currents from
3.78 to 4.2 A.
Output voltage (V)
Output current (%)
Intermittent
operation
Note: Do not short-circuit the output terminals of the S82K or use the S82K with excessive output current for a long time, otherwise
the internal circuitry of the S82K may be deteriorated or damaged.
500 100
Output voltage (V)
Output current (%)
Rated voltage
3-/7.5-/15-/90-/100-/240-W Models
30-/50-W Models
Rated voltage
When Using Dual Output (+/–) Models
The +V output detects the total output power (+V output and -V output) to trigger the short-circuit protection against overcurrent. This
protection varies depending on the -V output state. The -V output independently triggers the short-circuit protection.