IBS IL 24 RB-LK (-2MBD)
7181_en_00 PHOENIX CONTACT 9
Safety Equipment
None
Electrical Isolation/Isolation of the Voltage Areas
Common Potentials
The 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply, and 5 V communications power of the
branch terminal share a common potential.
Separate Potentials
The communications power ground is jumpered to the ground of the 7.5 V communications power for the bus coupler
power supply unit.
The I/O supply is always electrically isolated from the interface supplies.
Electrical Isolation/Isolation of the Voltage Areas When Combining a Bus Coupler and the IBS IL 24 RB-LK
Branch Terminal
Test Distance Test Voltage
5 V supply of incoming remote bus (bus coupler) electrically isolated from
5 V supply of outgoing remote bus (bus coupler) 500 V AC, 50 Hz, 1 min
7.5 V communications power, 24 V analog supply, 24 V bus coupler supply,
5 V communications power of branch terminal
500 V AC, 50 Hz, 1 min
24 V main supply, 24 V segment supply 500 V AC, 50 Hz, 1 min
Functional earth ground 500 V AC, 50 Hz, 1 min
5 V supply of outgoing remote bus (bus coupler) electrically isolated from
5 V supply of incoming remote bus (bus coupler) 500 V AC, 50 Hz, 1 min
7.5 V communications power, 24 V analog supply, 24 V bus coupler supply,
5 V communications power of branch terminal
500 V AC, 50 Hz, 1 min
24 V main supply, 24 V segment supply 500 V AC, 50 Hz, 1 min
Functional earth ground 500 V AC, 50 Hz, 1 min
7.5 V communications power, 24 V analog supply, 24 V bus coupler supply,
5 V communications power of branch terminal electrically isolated from
5 V supply of incoming remote bus (bus coupler) 500 V AC, 50 Hz, 1 min
5 V supply of outgoing remote bus (bus coupler) 500 V AC, 50 Hz, 1 min
24 V main supply, 24 V segment supply 500 V AC, 50 Hz, 1 min
Functional earth ground 500 V AC, 50 Hz, 1 min
24 V main supply, 24 V segment supply electrically isolated from
5 V supply of incoming remote bus (bus coupler) 500 V AC, 50 Hz, 1 min
5 V supply of outgoing remote bus (bus coupler) 500 V AC, 50 Hz, 1 min
7.5 V communications power, 24 V analog supply, 24 V bus coupler supply,
5 V communications power of branch terminal
500 V AC, 50 Hz, 1 min
Functional earth ground 500 V AC, 50 Hz, 1 min