PSR-...-24UC/URM4/5X1/2X2/B
100517_en_03 PHOENIX CONTACT 3 / 14
Description Ty pe Order No. Pcs./Pkt.
Single or two-channel contact extension, 5 N/O contacts, 1 N/C contact, 1
confirmation current path, plug-in screw terminal blocks, width: 22.5 mm
PSR-SCP- 24UC/URM4/5X1/2X2/B 2981033 1
Single or two-channel contact extension, 5 N/O contacts, 1 N/C contact, 1
confirmation current path, plug-in spring-cage terminal block, width: 22.5
mm
PSR-SPP- 24UC/URM4/5X1/2X2/B 2981046 1
Documentation Ty pe Order No. Pcs./Pkt.
User manual, English, for applications for PSR safety relay UM EN SAFETY RELAY
APPLICATION
2888712 1
Hardware/firmware version
HW/FW ≥ 05/--
The technical data and safety characteristics are valid as of the specified HW/FW version.
Input data
Rated control circuit supply voltage U
S
24 V AC/DC -15 % / +10 %
Rated control supply current I
S
typ. 81 mA AC
typ. 71 mA DC
Typical inrush current 175 mA (Δt=5ms at U
s
)
Power consumption at U
S
typ. 1.94 W (AC)
typ. 1.7 W (DC)
Filter time 2 ms (at A1 in the event of voltage dips at U
s
)
Typical starting time with U
s
< 20 ms (when controlled via A1)
Typical release time with U
s
< 20 ms (when controlled via A1)
Recovery time < 1 s
Maximum switching frequency 1 Hz
Operating voltage display 1 x green LED
Protective circuit Surge protection Varistor
Output data
Contact type 5 enabling current paths
1 confirmation current path
1 signaling current path
Contact material AgSnO
2
Minimum switching voltage 5 V AC/DC
Maximum switching voltage 250 V AC/DC (Observe the load curve)
Limiting continuous current 6 A (N/O contact, pay attention to the derating)
6 A (N/C contact)
Maximum inrush current 20 A (Δt100ms)
Inrush current, minimum 10 mA
Sq. Total current
I
TH
2
= I
1
2
+ I
2
2
+ ... + I
N
2
72 A
2
(observe derating)
Interrupting rating (ohmic load) max. 144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
110 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)