B7AM-6BS
B7AM-6BS
2
Specifications
3
CHARACTERISTICS
General
Item Normal speed High speed
Communication method
Unidirectional, time-division multiplex
Transmission distance
500 m max. 100 m max. (See Note 1)
I/O delay
Typical: 19.2 ms; 31 ms max. Typical: 3 ms; 5 ms max.
Minimum input time
(See Note 2)
16 ms 2.4 ms
Operating voltage range
12 to 24 VDC (10.8 to 26.4 VDC)
Insulation resistance
100 M
Ω
min. at 500 V between each terminal and external parts
Dielectric strength
1,000 VAC, 50/60 Hz for 1 min between each terminal and external parts
Noise immunity
(See Note 3)
Noise level: 1.5 kV; pulse width: 100 ns to 1
μ
s
Vibration resistance
10 to 55 Hz, 1.5 mm double amplitude
Shock resistance
300 m/s
2
(approx. 30G)
Ambient temperature
Operating: --10
°
Cto55
°
C(14
°
Fto131
°
F) with no icing
Storage: --25
°
Cto65
°
C(--13
°
F to 149
°
F) with no icing
Ambient humidity
Operating: 35% to 85% with no condensation
Note: 1. A shielded transmission cable or a twisted pair or VCTF cable with a thickness of 0.75 mm
2
minimum must be used for signal
transmission. If the twisted pair or VCTF cable is used, however, the transmission distance will be 10 m maximum regardless of
whether or not independent power supplies for the Input and the Output Link Terminals are used.
2. The minimum input time is required for the B7AM to read an input signal.
3. As for the high-speed transmission setting, these values are possible without grounding the shielded line.
Mixed I/O Terminal Block
Item B7A-6BS
I/O delay
Standard (typical 19.2 ms); high-speed (typical 3 ms), switch selectable (See Note 4)
Current consumption
(See Note 1)
240 mA max. with all input/output terminals ON
Operating voltage range
12 to 24 VDC
Compatible inputs
(See Note 2)
Switches, two-wire sensors with DC output, three-wire NPN sensors
Input logic
Active low
Input voltage range
0 VDC to supply voltage
Input current range
--6 to --3 mA/point (current flowing from input terminals)
Minimum input time
Standard: 16 ms; high-speed: 2.4 ms
ON/OFF threshold
No--contact input:ON voltage: 4 V max.
OFF voltage: 6 V min.
Contact input: ON discrimination resistance: 660
Ω
max.
OFF discrimination resistance: 2 k
Ω
min.
Output configuration
NPN open collector
Rated load voltage
5to24VDC
Output residual voltage
0.8 V max.
Output current
Sink current, 100 mA max./ point
Error processing
HOLD/LOAD OFF is set using a selection switch (See Note 3)
Mounting strength
No damage when 5 kgf (49 N) pull is applied for 1 min each in all directions
Terminal strength
No damage when 5 kgf (49 N) pull is applied for 1 min each in all directions
Tightening torque
8to12kgf
:
cm (0.78 to 1.18 N
:
m)
Weight
Approx. 230 g
Note: 1. Consumption when all 16 input/output points are ON. Excludes external sensor current for Input Terminals and external load
current and error load current for Output Terminals.
2. Power must be supplied to the three-wire sensor via the positive power supply terminal or from an independent power supply.
Two-wire sensors must satisfy the following requirements:
Residual voltage: 4 V max.
Current leakage: 1.5 mA max.
The lower limit of control output: 3 mA (Use a bleeder resister to eliminate this restriction.)
3. Default settings are 19.2 ms and LOAD OFF.