RCP-1000-48-C

1000W Front End Power System
RCP-1000 series
File Name:RCP-1000-SPEC 2018-01-15
Industrial automation
Distributed power architecture system
Wireless/telecommunication solution
Redundant power system
Electric vehicle charger system
Constant current source system
Model Encoding / Order Information
Description
RCP-1000 is a 1KW single output rack mountable front end AC/DC power supply This series operates
for 90~264VAC input voltage and offers the models with the DC output mostly demanded from the industry.
Each model is cooled by the built-in DC fan with fan speed control, working for the temperature up to 60 .
RCP-1000 provides vast design flexibility by equipping various built-in functions such as the output
programming, active current sharing (up to 8000W via three 19 rack shelves, RCP-1U), remote control,
auxiliary power, alarm signal, etc.
Universal AC input / Full range
Built-in active PFC function
High efficiency up to 89%
Forced air cooling by built-in DC fan
Output voltage programmable
Built-in OR-ing diode, support hot swap (hot plug)
Active current sharing up to 3000W for one 19 rack shelf
Optiona I C interface
2
Protections: Short circuit / Overload / Over voltage /
Over temperature
Optional conformal coating
5 years warranty
Features
Applications
Output wattage
Output voltage
Interface option
24RCP - -1000
Safety: UL/EN/IEC 60950-1
EMC: EN 55022 / 55024
Certificates
{
Blank: Standard model, without I C interface
2
C : Optional model, with I C interface
2
Note: 19" rack shelf, RCP-1U, available. Details available on http://www.meanwell.com/
Bauar
Sicherheit
egel gema
t gepru ft
od
be
www.
ID 2000000000
tuv.com
wac g
os
5
Dimension
L
295
11.6
W
127
H
41 (1U)
(1U)
mm
inch1.61
*
*
*
*
*
*
Series name
SPECIFICATION
RCP-1000-12 RCP-1000-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE(SVR)
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
AC CURRENT (Typ.)
12V 24V
60A 40A
0 ~ 60A 0 ~ 40A
720W 960W
150mVp-p
11.6 ~ 12.4V
200mVp-p
23.2 ~ 24.8V
±1.0% ±1.0%
±0.5%
±0.5%
1000ms, 60ms/230VAC at full load
16ms/230VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
81%
COLD START 50A
8.5A/115VAC 4.5A/230VAC 10.5A/115VAC 5.5A/230VAC 11A/115VAC 5.5A/230VAC
<1.1mA / 230VAC
RCP-1000-48
48V
21A
0 ~ 21A
1008W
300mVp-p
46.3 ~ 49.7V
±1.0%
±0.5% ±0.5%
±0.5% ±0.5%
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
87% 89%
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER TEMPERATURE
OVERLOAD
OVER VOLTAGE
105 ~ 125% rated output power
13.2 ~ 16.2V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
26.4 ~ 32.4V 52.8 ~ 64.8V
PROTECTION
1000W Front End Power System
RCP-1000 series
File Name:RCP-1000-SPEC 2018-01-15
REMOTE SENSE
REMOTE ON-OFF CONTROL
AUXILIARY POWER
Compensate voltage drop on the load wiring up to 0.5V
By electrical signal or dry contact ON:short OFF:open
5V @ 0.3A
FUNCTION
SAFETY STANDARDS
WITHSTAND VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
±℃ 0.02%/ (0 ~ 50 )
ENVIRONMENT
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC
ISOLATION RESISTANCE
MTBF
DIMENSION
PACKING
OTHERS
274K hrs min. Telcordia SR-332 (Bellcore) ; 107.3K hrs min. MIL-HDBK-217F (25 )
295*127*41mm (L*W*H)
SAFETY &
EMC
(Note 5)
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
1.93Kg; 6pcs/12.6Kg/1.04CUFT
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Logic " High" for over temperature warning, Please refer to the Installation Manual, isolated signal
OVER TEMP WARNING
Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual.
OUTPUT VOLTAGE PROGRAMMABLE
AC OK SIGNAL
DC OK SIGNAL
The isolated TTL signal out, Please refer to the Installation Manual
The isolated TTL signal out, Please refer to the Installation Manual
EMC IMMUNITY
EMC EMISSION
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class B
-----
-----
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the derating curve for more details.
5. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.720 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
65
70
75
80
85
90
95
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
PFC fosc : 110KHz
PWM fosc : 90KHz
Block Diagram
Efficiency vs Load (48V Model)
EFFICIENCY (%)
LOAD
The curve above is measured at 230VAC.
MODEL
INPUT
12V
720W
720W
720W
648W
960W
960W
960W
864W
1008W
1008W
1008W
907.2W
60A
60A
60A
54A
40A
40A
40A
36A
21A
21A
21A
18.9A
180~264VAC
115VAC
100VAC
90VAC
24V 48V
Static Characteristics
LOAD (%)
LOAD (%)
INPUT VOLTAGE (VAC) 60Hz
90 95 100 115 264
90
100
80
70
60
50
40
Derating Curve
AMBIENT TEMPERATURE ( )
20
40
60
80
100
-20010203040506070
RCP-1000 series
&
PFC
FILTER
&
RECTIFIERS
AUX POWER
(5V/0.3A)
PFC
CONTROL
O.L.P.
AUX GND
ORING
DIODE
SHARE
CURRENT
CURRENT
V_TRIM
SHARE
O.V.P.
2
I C
REMOTE
ON-OFF
RECTIFIERS
CONTROL
ON/OFF
DETECTION
CIRCUIT
DC_OK
T_ALARM
AC_OK
OPTIONAL
I C FUNCTION
2
FAN
LIMITING
ACTIVE
CURRENT
INRUSH
CONTROL
ING
I/P
-V
+V
RECTIFIERS
&
FILTER
SWITCH-
POWER
RECTIFIERS
FILTER
EMI
PWM
-S
+S
CIRCUIT
DETECTION
POWER
AUX
1000W Front End Power System
File Name:RCP-1000-SPEC 2018-01-15