RCP-1000-48-C

Function Manual
2. Remote ON/OFF Control
The power supply can be turned ON/OFF together or separately by using the "Remote ON-OFF" function.
Between Remote ON-OFF and -S
Switch Short
Switch Open
Power Supply Status
ON
OFF
1.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
1. Voltage Drop Compensation
RCP-1000 series
1000W Front End Power System
File Name:RCP-1000-SPEC 2018-01-15
1.2 Local Sense
-V
+V
RCP-1000
+S
-S
LOAD
-V
+V
8
9
Sense lines should be twisted in pairs
+V
-V
+S
-S
RCP-1000
22
25
20
21
PIN8 +S
PIN7 REMOTE ON/OFF
PIN9 -S
The +S,-S have to be connected to the ,-V, respectively, as the following diagram, in order to get the correct output voltage if Remote Sense+V
is not used.
-S
REMOTE
ON-OFF
RCP-1000
7
9
RCP-1000 series
1000W Front End Power System
File Name:RCP-1000-SPEC 2018-01-15
3.1 RCP-1000-12
90
92
94
96
98
100
Vout (%) Vout (%)
180K 240K 350K 560K 1.2M NC
R1 ( )Ω
min. 0.1W
R2 ( )Ω
min. 0.1W
100
102
104
106
108
110
NC 300K 120K 62K 31K 13K
In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 90~110% of the nominal voltage by applying
EXTERNAL RESISTANCE.
+S & +V, -S & -V also need to be connected on CN501
3. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
3.3 RCP-1000-48
90
92
94
96
98
100
1.3M 1.7M 2.4M 3.6M 7.6M NC
100
102
104
106
108
110
NC 345K 140K 70K 36K 15K
3.2 RCP-1000-24
90
92
94
96
98
100
560K 750K 1M 1.6M 3.3M NC
100
102
104
106
108
110
NC 330K 130K 62K 30K 10K
Vout (%)
Vout (%)
Vout (%)
Vout (%)
R1 ( )Ω
min. 0.1W
R1 ( )Ω
min. 0.1W
R2 ( )Ω
min. 0.1W
R2 ( )Ω
min. 0.1W
4. I C Bus Interface Option
2
For the details of I C option, please refer to the Installation Manual.
2
+S
+V
RCP-1000 LOAD
8
-S
-V
13
9
R1
R2
V-TRIM
PIN8 +S
PIN 13 V-TRIM
PIN9 -S
RCP-1000 series
1000W Front End Power System
7.1
12.5
Mechanical Specification
Case No. 952A Unit:mm
direction
DC OK AC OK
Air flow
41
24
46
127
66
39.1
46.3
3.6
1
2
3
4
57
9
10
12
13
15
16
18
19
21
62224
23
295
SVR
5 max.
LED Status Indicators & Corresponding Signal at Function Pins
Function
AC-OK
AC-NG
DC-OK
DC-NG
T-OK
T-ALARM
LED
ON
OFF
ON
OFF
----
----
Description
When input voltage 82V 4V≧±
When input voltage 82V 4V≦±
When output voltage 80% 5% of Vo rated.≧±
When output voltage 80% 5% of Vo rated.≦±
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
Signal
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
PSU Output
ON
OFF
ON
ON
ON
OFF
*
*Signal between function pin and "-V".
CN501
Pin No. Function
Description
Input / Output Connector Pin No. Assignment( ) : Postronic PCIB24W9M400A1CN501
Mating Housing
Postronic PCIB24W9F400A1
12
CS
Current sharing signal.
When units are connected in parallel, the CS pins of the units should be connected to allow current balance between units.
7
10
11
13
14
16
17
15
Remote
ON-OFF
AC-OK
V-TRIM
T-ALARM
GND-AUX
SCL
+5V-AUX
Low : When input voltage is 82Vrms +/-4V.
High : When input voltage in 82Vrms +/-4V.
(Note.1)
(Note.1)
(Note.1)
Each unit can separately turn the output on and off by electrical or dry contact . Short: ON, Open:OFF.
High : When Vout 80%+/-5%.
Low : When Vout 80%+/-5%
Connection for output voltage programming.
High : When the internal temperature is within safe limit.
Low : 10 below the thermal shut down limit.
Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
Serial clock used in the I C interface option. Refer to the Instruction Manual. (Note.1)
Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7).
The maximum load current is 0.3A. This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
2
8
9
+S
-S
Positive sensing for Remote Sense.
Negative sensing for Remote Sense.
1,2,4 +V(signal)
Positive output voltage.
18
19,20,21
22
23
24
SDA
A0,A1,A2
FG
AC/L
AC/N
Serial data used in the I C interface option. Refer to the Instruction Manual. (Note.1)
I C interface address lines. Refer to the Instruction Manual.
AC Ground connection.
AC Line connection.
AC Neutral connection.
2
2
3,5,6 -V(signal)
Negative output voltage.
Note1: Non-isolated signal, referenced to the output terminal -V.
File Name:RCP-1000-SPEC 2018-01-15
DC-OK

RCP-1000-48-C

Mfr. #:
Manufacturer:
Description:
Rack Mount Power Supplies 1008W 48V 21A W/PFC & INTERFACE
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union