8008_en_00
AUTOMATION
FLM BK PB M12 DI 8 M12-EF
Data Sheet
© PHOENIX CONTACT - 2010-04-30
1Description
The device connects a Fieldline modular station to
PROFIBUS-DP and is also used to acquire digital signals.
16 devices can be connected in any position to an existing
PROFIBUS DP system using the bus coupler.
Features
Connection to PROFIBUS-DP using M12 connectors
(B-encoded)
Opens the Fieldline modular local bus
using M12 connectors (B-encoded)
Length local bus max. 20 m
Data transmission speed max. 12 Mbps
(automatic detection)
Device description using GSD file
Dynamic configuration and empty spaces
Supported PROFIBUS addresses 1 to 126
Up to 16 PCP devices can be connected
–I & M functions
Connection of digital sensors using M12 connectors
Flexible voltage supply concept
LED diagnostic and status indicators for
bus operation and voltage supply
Short-circuit and overload protection of the sensor
supply
Channel-specific diagnostics for different I/O devices
IP65/IP67 protection
Additional features of EF versions
IO-Link call (firmware 2.0 or later)
Fieldline Modular Bus Coupler for PROFIBUS
With 8 Digital Inputs
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog. A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is only valid in association with the FLS FLM SYS INST UM E and FLS FLM PB SYS PRO UM E
user manuals.
7 0 0 8 A 0 0 1
FLM BK PB M12 DI 8 M12-EF
8008_en_00 PHOENIX CONTACT 2
2Ordering Data
2.1 Ordering Data Device and Accessories
2.2 Ordering Data for Documentation
3 Technical Data
Figure 1 Device Dimensions
Description Order Designation Order No. Pcs./Pkt.
Fieldline Modular Bus Coupler for PROFIBUS
With 8 Digital Inputs
FLM BK PB M12 DI 8 M12-EF 2773377 1
Protective caps (for unused sockets) IBS IP PROT-12 1680539 5
Protective caps (for unused male connectors) PROT-M12FS 1560251 5
5-pos. shielded metal socket, B-encoded,
for the incoming local bus
SACC-M12FSB-5SC SH 1513596 1
Shielded metal connector, 5-pos., B-encoded,
for the outgoing remote bus and local bus
SACC-M12MSB-5SC SH 1513570 1
Markers ZBF 12:UNBEDRUCKT 0809735 10
Bridging cable for power supply,
A-encoded, 5-pos., unshielded
SAC-5P-MS/ 0,13-186/FS SCO 1518481 1
Bridging cable for the local bus,
B-encoded, 5-pos., shielded
SAC-5P-MSB/0,13-PUR/FSB SCO SH 1518478 1
Assembly system for 5 devices FLM MP 5 2736660 1
Assembly system for 7 devices FLM MP 7 2736673 1
Additional accessories for connecting the sensors and actuators can be found in the Phoenix Contact PLUSCON catalog.
Description Order Designation
"Installing the Fieldline Product Range" user manual FLS FLM SYS INST UM E
"Configuring a PROFIBUS DP System Using Devices in the Fieldline Product Range" user manual FLS FLM PB SYS PRO UM E
3 1 m m
( 1 . 2 2 0 ' ' )
1 7 8 m m
( 7 . 0 0 8 ' ' )
4 0 m m
( 1 . 5 7 5 ' ' )
4 9 , 3 m m
(
1 . 9 4 1 ' '
)
1 6 8 m m
( 6 . 6 1 4 ' ' )
7 0 m m
( 2 . 7 5 6 ' ' )
7 0 0 8 A 0 0 6
0
2
4
6
9
8
0
2
4
6
8
1 2
1 0
1 0
x
1
x
General Data
Order Designation FLM BK PB M12 DI 8 M12-EF
Order No. 2773377
Housing dimensions (width x height x depth) 70 mm x 178 mm x 49.3 mm
Weight 285 g, approximately
Type of sensor connection 2, 3 or 4-wire technology
Permissible temperature (operation) -25°C to +60°C
Permissible temperature (storage/transport) -25°C to +85°C
Permissible humidity (storage/transport) 95%
FLM BK PB M12 DI 8 M12-EF
8008_en_00 PHOENIX CONTACT 3
Permissible air pressure (operation) 80 kPa to 106 kPa (up to 2,000 m above sea level)
Permissible air pressure (storage/transport) 70 kPa to 106 kPa (up to 3,000 m above sea level)
Degree of protection IP65/IP67 according to IEC 60529
Class of protection Class 3 according to VDE 0106, IEC 60536
Mechanical Requirements
Vibration test
Sinusoidal vibrations according to EN 60068-2-6
5g load in each space direction
Shock test according to EN 60068-2-27 30g load, half sinusoidal wave positive and negative in each space direction
General Data
For a short period, slight condensation may appear on the housing.
For additional information on mechanical requirements and ambient conditions, please contact Phoenix Contact.
Voltage Supply
Nominal value 24 V DC
Tolerable Range (EN 61131-2) 19 V DC to 30 V DC, ripple included
Current consumption at U
L
at 24 V DC
At 500 kbaud 35 mA, typical (100 mA, maximum)
At 2 Mbaud 40 mA, typical (100 mA, maximum)
Current consumption at U
S
at 24 V DC 10 mA + sensor current, typical (600 mA, maximum)
Voltages U
L
and U
S
at female connector U
LS
OUT can each only carry a maximum current of 2 A.
Digital Inputs
Number 8
Nominal input voltage 24 V DC
Range -30 V DC < U
IN
< + 30 V DC
Nominal input current 5 mA
Current flow Linear in the range 1 V < U
IN
< 30 V
Delay time t
ON
= 2.9 ms, typical
t
OFF
= 2.6 ms, typical
Permissible cable length to the sensor < 30 m
Input Characteristic Curve
Input Voltage (V) Typical Input Current (mA)
-30 < U
IN
< 0.7 0
3 0.5
6 1.0
9 1.5
12 2.2
15 3.0
18 3.6
21 4.4
24 5.1
27 5.8
30 6.6

2773377

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Connectors FLM BK PB M12 DI 8 M12-EF
Lifecycle:
New from this manufacturer.