8433_en_03 PHOENIX CONTACT 13
10 Local status and diagnostic indicators
10.1 Indicators for bus and power supply
Figure 9 LEDs for bus and power supply
Designation Color Meaning State Description
RDY Green/
yellow/
red
Ready Green
ON
Device ready to operate
Yellow
flashing
Firmware update is being performed.
Flashing
green/
yellow
Over- or undervoltage at U
S
Temperature of the device is in the critical area.
Failure of the actuator supply U
A
Surge voltage/undervoltage of the actuator supply U
A
And red US LED: sensor supply overload
Red ON Rotary encoding switches are set to an invalid/reserved position.
OFF Device is not ready for operation.
BF Red Bus Fault Red ON No communication on PROFIBUS
Device is starting up.
No baud rate detected by device.
Red
flashing
Device has not been configured by the master.
Device configuration does not match.
Invalid parameter data received from the master.
Invalid bus address
The device is in the clear or stop state. The outputs are in the safe
state.
OFF No error
SF Red Group error Red ON Device-specific diagnostics present, e.g., short circuit at the I/O de-
vices.
Hardware is faulty.
Device data or parameter data do not match.
OFF No error
AXL E PB DI8 DO4 2A M12 6M
8433_en_03 PHOENIX CONTACT 14
10.2 Input and output indicators
Figure 10 Input and output indicators
US Green/
red
U
Sensorik
Green
ON
Communications power/sensor voltage present
OFF Communications power/sensor voltage not present or too low.
Red ON Sensor voltage overload
UA Green U
Aktorik
ON Actuator voltage present.
OFF Actuator voltage not present.
Designation Color Meaning State Description
Designation Color Meaning State Description
00 ... 07 Yellow Status of the inputs ON Input is set.
OFF Input is not set.
00 ... 03 Yellow/red Status of the outputs Yellow ON Output is set.
Red ON Output is short circuited or overloaded.
OFF Output is not set.
The numbering of the LEDs is as follows: the first number specifies the byte, the second number specifies the
bit.
AXL E PB DI8 DO4 2A M12 6M
8433_en_03 PHOENIX CONTACT 15
11 Process data
11.1 Assignment of the terminal points to the IN process data
The I/O data are mapped are follows:
Key:
11.2 Assignment of the terminal points to the OUT process data
The I/O data are mapped as follows:
Key:
11.3 Status module
The device has a status module in slot 1.
The status is mapped as follows.
Input process data
Byte Byte 0
Bit 76543210
IN 07 06 05 04 03 02 01 00
Connection X04 X03 X02 X01
Pin 24242424
DI 87654321
Bit: Process data assignment
IN: LED marking
DI: Input of the device
Output process data
Byte Byte 0
Bit 76543210
OUT - ---03020100
Connection ----X08X07X06X05
Pin ----4444
DO ----4321
Bit: Process data assignment
OUT: LED marking
DO: Output of the device
Bit 31 ... bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Supply of the module electronics and sensors
(U
S
)
Supply of the actuators (U
A
)Outputs
Reserved Undervoltage Overload Undervoltage Short-circuit Overload Short-circuit

2701507