OUTPUT SPECIFICATIONS
(2)
Description 45A
Operating Voltage (45-65Hz) [VRMS] 48-600
Transient Overvoltage [Vpk]
(3) 1200
Maximum Off-State Leakage Current @ Rated Voltage [mA
RMS] 1
Minimum Off-State dV/dt @ Maximum Rated Voltage [V/μsec] 500
Load Current, General Use UL508/LC A IEC62314 @ 40°C [A
RMS] 45
Minimum Load Current [mA
RMS] 100
Maximum 1 Cycle Surge Current (50/60Hz) [Apk] 716/750
Maximum On-State Voltage Drop @ Rated Current [V
RMS] 1.25
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec] 2563/2343
60A
48-600
1200
1
500
60
Load Current, Motor Starting UL508 FLA/LC B IEC62314 @ 40°C [ARMS] 14/7.6
26/14
150
1290/1350
1.15
8320/7593
Maximum Power Dissipation @ Rated Current [W] 52
69
Minimum Power Factor (at Maximum Load)
(4) 0.5
0.5
Motor Rating UL 508/IEC62314 [HP (kW)]: 120 VAC 1 (0.74)
2 (1.5)
Motor Rating UL 508/IEC62314 [HP (kW)]: 240 VAC 3 (2.2)
5 (3.73)
Motor Rating UL 508/IEC62314 [HP (kW)]: 480 VAC 5 (3.7)
10 (7.4)
INPUT SPECIFICATIONS
(2)
Description DR4560Axxx
Control Voltage Range 90-280 VAC/VDC
Maximum Reverse Voltage -
Minimum Turn-On Voltage 90 VAC/VDC
Must Turn-Off Voltage 5 VAC/VDC
Minimum Input Current (for on-state) 3 mA
Maximum Input Current 4 mA
Nominal Input Impedance Switch Mode
Maximum Turn-On Time [msec] 20
Maximum Turn-Off Time [msec] 30
DR4560Dxxx
4-32 VDC
-32 VDC
4 VDC
1 VDC
10 mA
15 mA
Current Limited
1/2 Cycle
1/2 Cycle
(5)
(6)
Page 2
Required for valid part number
For options only and not
required for valid part number
Series
Overvoltage Protection
Control Voltage (1)
Operating Voltage
Rated Load Current
Switching Type
Input Connector
DR45
60 A 45 R JP
60: 48-600 VAC
DR45
Blank: Not Included
P: Included
A: 90-280 VAC/VDC
D: 4-32 VDC
45: 45 Amps
60: 60 Amps
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On (Motor Rating Certified)
Blank: Screw Terminal
J: Spring Terminal
ORDERING OPTIONS
www.sensata.com
Copyright © 2017 Sensata Technologies Inc.