AXL E PN DI8 DO4 2A M12 6P
8449_en_04 PHOENIX CONTACT 13
10 PROFINET IO Device
The Axioline E PROFINET device operates as a PROFINET IO device based on PROFINET specification v2.2.
Slot 1 always contains the “Status module” with 4 bytes of IN process data. Slot 2 contains the IO module, which contains the
process data and startup parameters.
10.1 Status module
The status module cyclically provides the following diagnostics options via process data:
10.2 IO module
Assignment of the terminal points to the IN process data
The I/O data are mapped as follows:
Key:
Assignment of the terminal points to the OUT process data
The I/O data are mapped as follows:
Key:
Bit 31 ... bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Supply of the module electronics and sensors (U
S
) Supply of the actuators (U
A
)Outputs
Reserved Undervoltage Overload Undervoltage Short-circuit Overload Short-circuit
Input process data
Byte Byte 0
Bit 76543210
IN 07 06 05 04 03 02 01 00
Connection X04 X03 X02 X01
Pin 24242424
DI 87654321
Bit: Process data assignment
IN: LED marking
DI: Device input
Output process data
Byte Byte 0
Bit 76543210
OUT ----03020100
Connection ----X08X07X06X05
Pin ----4444
DO ----4321
Bit: Process data assignment
OUT: LED marking
DO: Device output
AXL E PN DI8 DO4 2A M12 6P
8449_en_04 PHOENIX CONTACT 14
10.3 Substitute value behavior
The substitute value behavior is set via the IO module in slot 2. The following parameters are available:
Parameter Possible values (bold = default) Description
Failsafe substitute
value behavior
0 = reset all outputs (default) Substitute value behavior for all outputs
1 = set all outputs
2 = hold last value
3 = substitute values
Failsafe substitute
values
0 = zero (default)
Possible values: 0 ... 65535
dec
Specification of a substitute value pattern for all outputs. In
order to use this parameter, you must first set the “Substitute
values” in the “Failsafe substitute value behavior” parameter.
AXL E PN DI8 DO4 2A M12 6P
8449_en_04 PHOENIX CONTACT 15
10.4 Diagnostic messages
PROFINET enables the PROFINET device to store diagnos-
tic information together with the error location and error type.
An incoming alarm informs the PROFINET controller that di-
agnostic information has been entered.
When the diagnostic information has been removed, an out-
going alarm is sent to the device.
If at least one piece of diagnostic information is stored, the
SF LED is on. If no diagnostic information is present, the SF
LED is off.
The following PROFINET diagnostic messages are indi-
cated by the PROFINET device:
Overtemperature of the device
–Surge voltage of U
S
Overload of U
S
–Surge voltage of U
A
Undervoltage of U
A
Short circuit of U
A
Short circuit of an output
–Output overload
10.5 LLDP - Link Layer Discovery Protocol
The device supports LLDP according to IEEE 802.1AB and
therefore enables topology detection of devices that also
have LLDP activated.
Advantages of using LLDP:
Improved error location detection
Improved device replacement
More efficient network configuration
The following information is received by or sent to neigh-
bors, as long as LLDP is activated:
The device sends its own management and connection
information to neighboring devices.
The device receives management and connection infor-
mation from neighboring devices.
Engineering tools can be used to represent the LLDP infor-
mation as a topology overview.
10.6 MRP - Media Redundancy Protocol
The device supports the role of a Media Redundancy Client
(MRC) in an MRP network.
11 FSU - Fast Startup
The device supports the Fast Startup function. This function
enables fast startup of the PROFINET device. The device is
ready to operate in < 500 ms.
11.1 Shared device
The device supports the shared device function. This en-
ables two controllers to simultaneously establish a cyclic
connection to the device and read input data. Writing out-
puts can only be activated by the first controller.
11.2 Device replacement
Devices can be replaced without having to reconfigure them
within the PROFINET network.
Device replacement is only then possible if the new device
is in its default state. The controller must support the device
replacement function.
The device name and the device address are assigned by
the controller to the newly added PROFINET device with the
help of the neighborhood detection function.
Channel diagnostics are always reported in
groups of 4.
Follow the instructions in the documentation
for your engineering tool and controller in or-
der to parameterize this function.
Follow the instructions in the documentation
for your engineering tool and controller in or-
der to parameterize this function.
Follow the instructions in the documentation
for your engineering tool and controller in or-
der to parameterize this function.