MCR-C-UI-UI-DCI
100238_de_06 PHOENIX CONTACT 10
13 Specifying the Input Signal Range via DIP Switch 1
Select one of the possible signal ranges using the appropriate
configuration of DIP switch 1 according to the table.
Exception: Bipolar input signals are not permitted for the 4 ...
20 mA and 1 ... 5 V output signal ranges.
14 Specifying the Output Signal Range via DIP Switch 2
Output With Simple Adjustment (0 ... 5V/0 ...10V)
Set the output range via DIP switch 2. Please note the selec-
ted input range. Specify the initial and final value of the input
signal using a calibration device. Adjust the output value with
a digital multimeter.
Adjustment after specifying the initial and final value for the 0
... 5 V output: Set 0V ±0.5mV at the "ZERO" potentiometer
and 5V ±0.5mV at the "SPAN" potentiometer.
Adjustment after specifying the initial and final value for the 0
... 10 V output: Set 0V ±0.5mV at the "ZERO" potentiometer
and 10V ±0.5mV at the "SPAN" potentiometer.
Output With Adjustment Point Calculation (±5V/±10V/1
... 5V/0 ... 5mA/0 ... 10mA/0 ... 20mA/4 ... 20mA)
Set the output range via DIP switch 2. Please note the selec-
ted input range.
Specify the initial and final value of the input signal using a ca-
libration device.
Record the output value measured with a digital multimeter.
For adjustment with the calibration device, specify the final
value of the input signal range as follows:
"SPAN" potentiometer: Full-scale adjustment point A ± ad-
justment tolerance
"ZERO" potentiometer: Output final value ± adjustment tole-
rance
Calculation of full-scale adjustment point A: A=Measured
value 2xConstant/Measured value 2-Measured value 1
±5V, ±10V, 1 ... 5V, 4 ... 20mA output signal ranges: If the
initial value is specified at the input, measured value 1 is out-
put at the output. If the final value is specified at the input,
measured value 2 is output at the output.
0 ... 20mA output signal range: If the initial value +10% of the
range is specified at the input, measured value 1 is output at
the output. If the final value is specified at the input, measured
value 2 is output at the output.
For the values for the constant, output final
value, and adjustment tolerance, please refer
to the corresponding tables.
MCR-C-UI-UI-DCI
100238_de_06 11
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
15 Connection example
24V
0...20mA
1
2
3
U/I
GND 1
GND 1
MCR-C-UI-UI-DCI
POWER
SPAN
ZERO
OUT
T
U
GND 2
7
8
9
10
11
12
POWER
(+)
24V
GND 3
GND 3
0...10V
24V
Mains voltage
Control unit
Level sensor

2810887