POWR-GARD
®
Fuse Datasheet
littelfuse.com © 2016 Littelfuse POWR-GARD
®
Products
Rev: 120816
1 of 10
MEDIUM VOLTAGE FUSES
2,400-38,000 VAC • Current-Limiting
Bolt-in Mount Fuses
Description
Littelfuse
®
offers a selection of E- and R-rated medium
voltage fuses for the protection of trans formers, potential
transformers, feeders, and motor circuits. Single, double,
and triple barrel designs are available to cover a wide range
of current, voltage, and interrupting ratings. Conventional
ferrule type, clip lock, and bolt-in mounting configurations
are available for virtually any application. Hermetically sealed
fuses for use in hazardous environments are also offered.
Contact the factory or your local Littelfuse representative for
additional fuse ratings or custom mounting configurations.
24-Hour Emergency Service - Call 800-227-0029
Applications
Power Transformer Protection
Potential Transformer Protection
Motor Controller Back-up Protection
Fused Switches
Feeder Circuits
General Information
The terms “Medium Voltage” and “High Voltage” have been
used interchangeably by many people to describe fuses
operating above 600 volts. Technically speaking, medium
voltage fuses are those intended for the voltage range from
2,400 to 38,000 Vac. High voltage fuses are for circuits
carrying voltages greater than 38,000 Vac.
E-rated fuses are considered to be general purpose fuses
and can be used to protect against low and high values
of fault current. R-rated fuses are designed for back-up
protection. They must be used in series with other devices
such as motor overload relays in order to achieve both
overload and short-circuit protection.
Medium voltage fuses are not intended to provide overload
protection in the same sense as fuses rated 600 volts or
less. Medium voltage fuse current ratings do not have the
same meanings as the ampere ratings of low voltage fuses.
All medium voltage fuses are limited in their ability to
interrupt low value overcurrents, especially those between
100% and 200% of the fuse’s continuous current rating.
They are designed to carry their rated current without
exceeding the temperature rise permitted by NEMA and
ANSI standards.
Current-limiting E- and R-rated
fuses are equipped with a
mechanical indicator or striker pin
that protrudes through the fuse
cap upon operation of the fuse.
This provides visual identification
of a blown fuse and can be used
as a trigger for external devices.
Note: Extension distance
1
/
2” minimum;
extension force 2 lb. minimum.
POWR-GARD
®
Fuse Datasheet
littelfuse.com © 2016 Littelfuse POWR-GARD
®
Products
Rev: 120816
2 of 10
Description
R-rated fuses provide required short-circuit protection for
medium voltage motors, motor controllers and associated
circuitry. These components have limited ability to absorb the
energy of large short-circuit currents. Medium voltage motor
controllers contain overload relays which provide both overload
protection and locked rotor protection to the motor. The
controllers are also intended to interrupt low value short-circuits
within the capability of the motor controller. This protects the
medium voltage fuse from sustained overcurrents which are
less than their minimum interrupting rating.
NEMA Standards for R-rated medium voltage power fuses
require they operate within 15-35 seconds when subjected
to an rms current 100 times the R rating. For example, a
fuse with a 2R rating will open within 15 to 35 seconds on
an applied current of 2 x 100 = 200 amperes.
Ordering Number
3"DIA
Dim.A
Clip
Center
6.38"
Dim.B
9.75"
A
D DD DDD
Figure 1 Figure 2 Figure 3
Hookeye Feature*
For hookeye attachment; add “W” suffix
to part number
* See web for Bolt Mount, Inverted Bolt Mount, and Bolt-In dimensions
Max Voltage (KV)
Style:
C (Cartridge)
B (Bolt Mount)
IB (Inverted Bolt Mount)
BI (Bolt-In Mount)
No. of Barrels
Rating (size)
Continuous Current
Characteristics
Voltage Ratings 2,750 V – 8,250 V
Current Range 2R – 36R
Options
Hermetically sealed for use in hazardous locations
(add “S” suffix to part number)
Bolt-in mounting configurations
Bolt Mount “B
Sample Part #: 130-4R-1B-5.5
Inverted-Bolt “IB”
Sample Part #: 130-4R-1IB-5.5
Bolt-In Mount “BI”
Sample Part #: 130-4R-1BI-5.5
Cartridge “C
Dimensions
Medium Voltage
Fuse Protection
POWR-GARD
®
medium
voltage fuses provide
short-circuit protection
for motors and
transformers rated
2,400 to 38,000 volts AC.
Visit littelfuse.com/MediumVoltage to
download the white paper featuring protection
tables, sizing recommendations, and applications.
130-4R-1C-5.5
R-RATED MEDIUM VOLTAGE FUSES
POWR-GARD
®
Fuse Datasheet
littelfuse.com © 2016 Littelfuse POWR-GARD
®
Products
Rev: 120816
3 of 10
R
RATED
ORDERING/
CATALOG
NUMBER
SIZE
MAXIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
DIM. A
(INCHES)
DIM. B
(INCHES)
MINIMUM
INTERRUPTING
RATING RMS
AMPS
MAXIMUM
INTERRUPTING
RATING RMS
(ASYM)*
FIGURE
NUMBER
5.5 KV
702R1C5.5 2R 70 12" 15.875" 170 80,000 1
1003R1C5.5 3R 100 12" 15.875" 250 80,000 1
1304R1C5.5 4R 130 12" 15.875" 340 80,000 1
1505R1C5.5 5R 150 12" 15.875" 390 80,000 1
1706R1C5.5 6R 170 12" 15.875" 500 80,000 1
2009R1C5.5 9R 200 12" 15.875" 760 80,000 1
23012R1C5.5 12R 230 12" 15.875" 1000 80,000 1
39018R2C5.5 18R 390 12" 15.875" 1500 80,000 2
45024R2C5.5 24R 450 12" 15.875" 1950 80,000 2
48026R2C5.5 26R 480 12" 15.875" 2100 80,000 2
55030R2C5.5 30R 550 12" 15.875" 2400 80,000 2
60032R2C5.5 32R 600 12" 15.875" 2600 80,000 2
65036R2C5.5 36R 650 12" 15.875" 2900 80,000 2
55030R3C5.5 30R 550 12" 15.875" 2400 80,000 3
60032R3C5.5 32R 600 12" 15.875" 2600 80,000 3
65036R3C5.5 36R 650 12" 15.875" 2900 80,000 3
R
RATED
ORDERING/
CATALOG
NUMBER
SIZE
MAXIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
DIM. A
(INCHES)
DIM. B
(INCHES)
MINIMUM
INTERRUPTING
RATING RMS
AMPS
MAXIMUM
INTERRUPTING
RATING RMS
(ASYM)*
FIGURE
NUMBER
8.25 KV
702R1C8.25 2R 70 12" 15.875" 190 80,000 1
1003R1C8.25 3R 100 12" 15.875" 225 80,000 1
1304R1C8.25 4R 130 12" 15.875" 330 80,000 1
1505R1C8.25 5R 150 12" 15.875" 440 80,000 1
1706R1C8.25 6R 170 12" 15.875" 500 80,000 1
2009R1C8.25 9R 200 12" 15.875" 740 80,000 1
23012R1C8.25 12R 230 12" 15.875" 955 80,000 1
39018R2C8.25 18R 390 12" 15.875" 1440 80,000 2
45024R2C8.25 24R 450 12" 15.875" 1910 80,000 2
R
RATED
ORDERING/
CATALOG
NUMBER
SIZE
MAXIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
DIM. A
(INCHES)
DIM. B
(INCHES)
MINIMUM
INTERRUPTING
RATING RMS
AMPS
MAXIMUM
INTERRUPTING
RATING RMS
(ASYM)*
FIGURE
NUMBER
5.5 KV
14”CLIP CENTERS
702R1C5.5X 2R 70 14" 17.875" 170 80,000 1
1003R1C5.5X 3R 100 14" 17.875" 250 80,000 1
1304R1C5.5X 4R 130 14" 17.875" 340 80,000 1
1505R1C5.5X 5R 150 14" 17.875" 390 80,000 1
1706R1C5.5X 6R 170 14" 17.875" 500 80,000 1
2009R1C5.5X 9R 200 14" 17.875" 760 80,000 1
23012R1C5.5X 12R 230 14" 17.875" 1000 80,000 1
39018R2C5.5X 18R 390 14" 17.875" 1500 80,000 2
45024R2C5.5X 24R 450 14" 17.875" 1950 80,000 2
55030R2C5.5X 30R 550 14” 17.8 75 2400 80,000 2
R
RATED
ORDERING/
CATALOG
NUMBER
SIZE
MAXIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
DIM. A
(INCHES)
DIM. B
(INCHES)
MINIMUM
INTERRUPTING
RATING RMS
AMPS
MAXIMUM
INTERRUPTING
RATING RMS
(ASYM)*
FIGURE
NUMBER
2.75 KV
702R1C2.75 2R 70 7" 10.875" 170 80,000 1
1003R1C2.75 3R 100 7" 10.875" 250 80,000 1
1304R1C2.75 4R 130 7" 10.875" 340 80,000 1
1505R1C2.75 5R 150 7" 10.875" 390 80,000 1
1706R1C2.75 6R 170 7" 10.875" 500 80,000 1
2009R1C2.75 9R 200 7" 10.875" 760 80,000 1
23012R1C2.75 12R 230 7" 10.875" 1000 80,000 1
39018R2C2.75 18R 390 7" 10.875" 1500 80,000 2
45024R2C2.75 24R 450 7" 10.875" 1950 80,000 2
* RMS Asymmetrical amperes = RMS Symmetrical amperes x 1.6
For hookeye attachment add “W” suffix to part number
R-RATED MEDIUM VOLTAGE FUSES

2009R1C8.25

Mfr. #:
Manufacturer:
Littelfuse
Description:
Specialty Fuses V A Limiting 8.25kV
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union