E-RATED MEDIUM VOLTAGE FUSES
Description
E-rated fuses have time current characteristics designed to
provide current-limiting protection for power transformers,
potential transformers, power centers, feeder centers, and
unit sub stations. When properly applied, they can protect
against high and low fault currents.
NEMA Standards for E-rated medium voltage fuses require
that fuses rated 100E or less open within 300 seconds
(5 minutes) when subjected to an RMS value of 200-240%
of the fuse continuous current rating; and fuses with an
E rating larger than 100E must open within 600 seconds
(10 minutes) when subjected to an RMS current of 220-
240% of the fuse’s continuous current rating. These values
establish one point on the time-current curve.
Application Note
Since these fuses are used for the protection of general
purpose circuits which may contain transformers, motors,
and other equipment producing in-rush and/or overload
currents, fuses should generally be rated at 140% of the
normal full load current, and circuits should be analyzed
to ensure that system load currents will not exceed the
current rating of the fuse.
3"DIA
Dim.A
Clip
Center
6.38"
Dim.B
9.75"
A
D DD DDD
Figure 4 Figure 5 Figure 6
Characteristics
Voltage Ratings 2,750 V – 38,000 V
Current Range 10E – 600E
Options
Hermetically sealed for use in hazardous locations
(add “S” suffix to part number)
Clip-lock (CL) available.
E-RATED
ORDERING/CATALOG
NUMBER
SIZE DIM. A (INCHES) DIM. B (INCHES)
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE
NUMBER
2.75 MAX. KV
10E1C2.75 10E 7" 10.875" 80,000 4
15E1C2.75 15E 7" 10.875" 80,000 4
20E1C2.75 20E 7" 10.875" 80,000 4
25E1C2.75 25E 7" 10.875" 80,000 4
30E1C2.75 30E 7" 10.875" 80,000 4
40E1C2.75 40E 7" 10.875" 80,000 4
50E1C2.75 50E 7" 10.875" 80,000 4
65E1C2.75 65E 7" 10.875" 80,000 4
80E1C2.75 80E 7" 10.875" 80,000 4
100E-1C2.75 100E 7" 10.875" 80,000 4
125E1C2.75 125E 7" 10.875" 80,000 4
150E1C2.75 150E 7" 10.875" 80,000 4
200E1C2.75 200E 7" 10.875" 80,000 4
125E2C2.75 125E 7" 10.875" 80,000 5
150E2C2.75 150E 7" 10.875" 80,000 5
200E2C2.75 200E 7" 10.875" 80,000 5
250E2C2.75 250E 7" 10.875" 80,000 5
300E2C2.75 300E 7" 10.875" 80,000 5
350E2C2.75 350E 7" 10.875" 80,000 5
400E2C2.75 400E 7" 10.875" 80,000 5
450E2C2.75 450E 7" 10.875" 80,000 5
Dimensions
* RMS Asymmetrical amperes = RMS Symmetrical amperes x 1.6
POWR-GARD
®
Fuse Datasheet
littelfuse.com © 2016 Littelfuse POWR-GARD
®
Products
Rev: 120816
5 of 10
E-RATED MEDIUM VOLTAGE FUSES
E-RATED
ORDERING/CATALOG
NUMBER
SIZE DIM. A (INCHES) DIM. B (INCHES)
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE NUMBER
5.5 MAX. KV
10E1C5.5 10E 12" 15.875" 80,000 4
15E1C5.5 15E 12" 15.875" 80,000 4
20E1C5.5 20E 12" 15.875" 80,000 4
25E1C5.5 25E 12" 15.875" 80,000 4
30E1C5.5 30E 12" 15.875" 80,000 4
40E1C5.5 40E 12" 15.875" 80,000 4
50E1C5.5 50E 12" 15.875" 80,000 4
65E1C5.5 65E 12" 15.875" 80,000 4
80E1C5.5 80E 12" 15.875" 80,000 4
100E1C5.5 100E 12" 15.875" 80,000 4
125E1C5.5 125E 12" 15.875" 80,000 4
150E1C5.5 150E 12" 15.875" 80,000 4
175E1C5.5 175E 12" 15.875" 80,000 4
200E1C5.5 200E 12" 15.875" 80,000 4
125E2C5.5 125E 12" 15.875" 80,000 5
150E2C5.5 150E 12" 15.875" 80,000 5
175E2C5.5 175E 12" 15.875" 80,000 5
200E2C5.5 200E 12" 15.875" 80,000 5
250E2C5.5 250E 12" 15.875" 80,000 5
300E2C5.5 300E 12" 15.875" 80,000 5
350E2C5.5 350E 12" 15.875" 80,000 5
400E2C5.5 400E 12" 15.875" 80,000 5
450E2C5.5 450E 12" 15.875" 80,000 5
500E3C5.5 500E 12" 15.875" 80,000 6
550E3C5.5 550E 12" 15.875" 80,000 6
600E3C5.5 600E 12" 15.875" 80,000 6
E-RATED
ORDERING/CATALOG
NUMBER
SIZE DIM. A (INCHES) DIM. B (INCHES)
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE NUMBER
5.5 MAX. KV
5NLE10E 10E 14 17
7
8
" 80,000 4
5NLE15E 15E 14” 17
7
8
" 80,000 4
5NLE20E 20E 14” 17
7
8
" 80,000 4
5NLE25E 25E 14” 17
7
8
" 80,000 4
5NLE30E 30E 14 17
7
8
" 80,000 4
5NLE40E 40E 14 17
7
8
" 80,000 4
5NLE50E 50E 14” 17
7
8
" 80,000 4
5NLE65E 65E 14” 17
7
8
" 80,000 4
5NLE80E 80E 14” 17
7
8
" 80,000 4
5NLE100E 100E 14” 17
7
8
" 80,000 4
5NLE125E 125E 14 17
7
8
" 80,000 4
5NLE150E 150E 14 17
7
8
" 80,000 4
5NLE175E 175E 14” 17
7
8
" 80,000 4
5NLE200E 200E 14” 17
7
8
" 80,000 4
5NLE2225E 225E 14” 17
7
8
" 80,000 5
5NLE2250E 250E 14” 17
7
8
" 80,000 5
5NLE2300E 300E 14” 17
7
8
" 80,000 5
5NLE2350E 350E 14” 17
7
8
" 80,000 5
5NLE2400E 400E 14” 17
7
8
" 80,000 5
5NLE2450E 450E 14” 17
7
8
" 80,000 5
* RMS Asymmetrical amperes = RMS Symmetrical amperes x 1.6
POWR-GARD
®
Fuse Datasheet
littelfuse.com © 2016 Littelfuse POWR-GARD
®
Products
Rev: 120816
6 of 10
E-RATED MEDIUM VOLTAGE FUSES
E-RATED
ORDERING/CATALOG
NUMBER
SIZE DIM. A (INCHES) DIM. B (INCHES)
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE NUMBER
15.5 MAX. KV
10E1C15.5 10E 15" 18.875" 80,000 4
15E1C15.5 15E 15" 18.875" 80,000 4
20E1C15.5 20E 15" 18.875" 80,000 4
25E1C15.5 25E 15" 18.875" 80,000 4
30E1C15.5 30E 15" 18.875" 80,000 4
40E1C15.5 40E 15" 18.875" 80,000 4
50E1C15.5 50E 15" 18.875" 80,000 4
65E1C15.5 65E 15" 18.875" 80,000 4
80E1C15.5 80E 15" 18.875" 80,000 4
100E1C15.5 100E 15" 18.875" 80,000 4
65E2C15.5 65E 15" 18.875" 80,000 5
80E2C15.5 80E 15" 18.875" 80,000 5
100E2C15.5 100E 15" 18.875" 80,000 5
125E2C15.5 125E 15" 18.875" 80,000 5
150E2C15.5 150E 15" 18.875" 80,000 5
175E2C15.5 175E 15" 18.875" 80,000 5
200E2C15.5 200E 15" 18.875" 80,000 5
200E3C15.5 200E 15" 18.875" 80,000 6
250E3C15.5 250E 15" 18.875" 80,000 6
300E3C15.5 300E 15" 18.875" 80,000 6
E-RATED
ORDERING/CATALOG
NUMBER
SIZE DIM. A (INCHES) DIM. B (INCHES)
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE NUMBER
8.25 MAX. KV
10E1C8.25 10E 12" 15
7
8
" 80,000, 4
15E1C8.25 15E 12" 15
7
8
" 80,000 4
20E1C8.25 20E 12" 15
7
8
" 80,000 4
25E1C8.25 25E 12" 15
7
8
" 80,000 4
30E1C8.25 30E 12" 15
7
8
" 80,000 4
40E1C8.25 40E 12" 15
7
8
" 80,000 4
50E1C8.25 50E 12" 15
7
8
" 80,000 4
65E1C8.25 65E 12" 15
7
8
" 80,000 4
80E1C8.25 80E 12" 15
7
8
" 80,000 4
100E1C8.25 100E 12" 15
7
8
" 80,000 4
125E1C8.25 125E 12" 15
7
8
" 80,000 4
150E1C8.25 150E 12" 15
7
8
" 80,000 4
125E2C8.25 125E 12" 15
7
8
" 80,000 5
150E2C8.25 150E 12" 15
7
8
" 80,000 5
200E2C8.25 200E 12" 15
7
8
" 80,000 5
250E2C8.25 250E 12" 15
7
8
" 80,000 5
300E2C8.25 300E 12" 15
7
8
" 80,000 5
350E3C8.25 350E 12" 15
7
8
" 80,000 6
400E3C8.25 400E 12" 15
7
8
" 80,000 6
E-RATED
ORDERING/CATALOG
NUMBER
SIZE DIM. A (INCHES) DIM. B (INCHES)
MAX INTERRUPTING
RATING RMS (ASYM)*
FIGURE NUMBER
8.25 MAX. KV
8NLE10E 10E 14" 17
7
8
" 80,000 4
8NLE15E 15E 14" 17
7
8
" 80,000 4
8NLE20E 20E 14" 17
7
8
" 80,000 4
8NLE25E 25E 14" 17
7
8
" 80,000 4
8NLE30E 30E 14" 17
7
8
" 80,000 4
8NLE40E 40E 14" 17
7
8
" 80,000 4
8NLE50E 50E 14" 17
7
8
" 80,000 4
8NLE65E 65E 14" 17
7
8
" 80,000 4
8NLE80E 80E 14" 17
7
8
" 80,000 4
8NLE100E 100E 14" 17
7
8
" 80,000 4
8NLE2100E 100E 14" 17
7
8
" 80,000 5
8NLE2125E 125E 14" 17
7
8
" 80,000 5
8NLE2150E 150E 14" 17
7
8
" 80,000 5
8NLE2200E 200E 14" 17
7
8
" 80,000 5
8NLE2250E 250E 14" 17
7
8
" 80,000 5
* RMS Asymmetrical amperes = RMS Symmetrical amperes x 1.6

2009R1C8.25

Mfr. #:
Manufacturer:
Littelfuse
Description:
Specialty Fuses V A Limiting 8.25kV
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union