DS1848
7 of 17
TEMPERATURE CONVERSION
The direct-to-digital temperature sensor measures temperature through the use of an on-chip temperature
measurement technique with an operating range from -40°C to +95°C. Temperature conversions are
initiated upon power-up, and the most recent result is stored in address locations E2h and E3h, which are
updated every 10ms. Temperature conversion will not occur during an active read or write to memory.
The value of each resistor is determined by the temperature-addressed look-up table that assigns a unique
value to each resistor for every 2°C increment with a 1°C hysteresis at a temperature transition over the
operating temperature range. This can be seen in Figure 2.
TEMPERATURE CONVERSION HYSTERESIS Figure 2
EXAMPLE TEMPERATURE READINGS Table 2
TEMP BINARY DATA HEX DATA
+95ºC 0010 1111 1000 0000 2F80h
+25.0625ºC 0000 1100 1000 1000 0C88h
-10.125ºC 1111 1010 1111 0000 FAF0h
-40ºC 1110 1100 0000 0000 EC00h
2 4 6 8 10 12
TEMPERATURE (C)
M6
M5
M4
M3
M2
M1
MEMORY LOCATION
Increasing temp
Decreasing temp
DS1848
8 of 17
2-WIRE OPERATION
Clock and Data Transitions: The SDA pin is normally pulled high with an external resistor or device.
Data on the SDA pin may only change during SCL low time periods. Data changes during SCL high
periods will indicate a start or stop conditions depending on the conditions discussed below. Refer to the
timing diagram (Figure 4) for further details.
Start Condition: A high-to-low transition of SDA with SCL high is a start condition that must precede
any other command. Refer to the timing diagram (Figure 4) for further details.
Stop Condition: A low-to-high transition of SDA with SCL high is a stop condition. After a read
sequence, the stop command places the DS1848 into a low-power mode. Refer to the timing diagram
(Figure 4) for further details.
Acknowledge: All address and data byte are transmitted via a serial protocol. The DS1848 pulls the SDA
line low during the ninth clock pulse to acknowledge that it has received each word.
Standby Mode: The DS1848 features a low-power mode that is automatically enabled after power-on,
after a stop command, and after the completion of all internal operations.
2-Wire Interface Reset: After any interruption in protocol, power loss, or system reset, the following
steps reset the DS1848.
1. Clock up to nine cycles.
2. Look for SDA high in each cycle while SCL is high.
3. Create a START condition while SDA is high.
Device Addressing: The DS1848 must receive an 8-bit device address word following a START
condition to enable a specific device for a read or write operation. The address word is clocked into the
DS1848 MSB to LSB. The address word consists of Ah (10106) followed by A2, A1, and A0 then the
R/W bit. If the R/W bit is high, a read operation is initiated. If the R/W is low, a write operation is
initiated. For a device to become active, the values of A2, A1 and A0 must be the same as the hard-wired
address pins on the DS1848. Upon a match of written and hard-wired addresses, the DS1848 will output a
zero for one clock cycle as an acknowledge. If the address does not match, the DS1848 returns to a low-
power mode.
Write Operations: After receiving a matching address byte with the R/W bit set low, the device goes
into the write mode of operation. The master must transmit an 8-bit EEPROM memory address to the
device to define the address where the data is to be written. After byte has been received, the DS1848 will
transmit a zero for one clock cycle to acknowledge the receipt of the address. The master must then
transmit an 8-bit data word to be written into this address. The DS1848 will again transmit a zero for one
clock cycle to acknowledge the receipt of the data. At this point, the master must terminate the write
operation with a STOP condition. The DS1848 then enters an internally timed write process t
w
to the
EEPROM memory. All inputs are disabled during this byte write cycle.
The DS1848 is capable of an 8-byte page write. A page write is initiated the same way as a byte write, but
the master does not send a STOP condition after the first byte. Instead, after the slave acknowledges
receipt of the data byte, the master can send up to seven more bytes using the same nine-clock sequence.
DS1848
9 of 17
The master must terminate the write cycle with a STOP condition or the data clocked into the DS1848
will not be latched into permanent memory.
Acknowledge Polling: Once the internally-timed write has started and the DS1848 inputs are disabled,
acknowledge polling can be initiated. The process involves transmitting a START condition followed by
the device address. The R/W bit signifies the type of operation that is desired. The read or write sequence
will only be allowed to proceed if the internal write cycle has completed and the DS1848 responds with a
zero.
Read Operations: After receiving a matching address byte with the R/W bit set high, the device goes
into the read mode of operation. There are three read operations: current address read, random read, and
sequential address read.
CURRENT ADDRESS READ
The DS1848 has an internal address register that maintains the address used during the last read or write
operation, incremented by one. This data is maintained as long as V
CC
is valid. If the most recent address
was the last byte in memory, then the register resets to the first address. This address stays valid between
operations as long as power is available.
Once the device address is clocked in and acknowledged by the DS1848 with the R/W bit set to high, the
current address data word is clocked out. The master does not respond with a zero, but does generate a
STOP condition afterwards.
RANDOM READ
A random read requires a dummy byte write sequence to load in the data word address. Once the device
and data address bytes are clocked in by the master and acknowledged by the DS1848, the master must
generate another START condition. The master now initiates a current address read by sending the device
address with the read/write bit set high. The DS1848 will acknowledge the device address and serially
clocks out the data byte.
SEQUENTIAL ADDRESS READ
Sequential reads are initiated by either a current address read or a random address read. After the master
receives the first data byte, the master responds with an acknowledge. As long as the DS1848 receives
this acknowledge after a byte is read, the master may clock out additional data words from the DS1848.
After reaching address FFh, it resets to address 00h.
The sequential read operation is terminated when the master initiates a stop condition. The master does
not respond with a zero.
For a more detailed description of 2-wire theory of operation, refer to the next section.

DS1848E-010+

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Digital Potentiometer ICs Dual Temp Controlled NV Variable Resistor
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet