WT30-FT001

4 FA Wireless SS Terminals WT30
Serial Communications Setting
Switch
Note: For example, if pins number 2, 3, and 4 are all ON, the total is
7, which corresponds to a baud rate of 115,200 bps.
Display
Note: When using the WD30 as the Serial Master Station, the ERR
indicator will light if normal I/O communications are not
possible due to an error in the host network.
No. Function ON OFF
1 Communications setting
selection
Detailed
settings
(settings for
No. 2 to 8
used)
Default settings
(baud rate: 9,600 bps;
data length: 7 bits;
parity: even; stop bits:
2)
Settings for No. 2 to 8
are ignored.
2 Baud rate (bps)
(See note.)
Total value = 0: 1,200
= 1: 2,400
= 2: 4,800
= 3: 9,600
= 4: 19,200
= 5: 38,400
= 6: 57,600
= 7: 115,200
10
3 20
4 40
5 Data length 8 bits 7 bits
6 Parity None Yes
7 Odd Even
8 Stop bits 1 bit 2 bits
Indicator Color Status Meaning (primary error)
PWR Green Lit Power is being supplied.
Not lit Power is not being supplied.
ERR
(Slave Station)
Red Lit Error output is ON:
Wireless device error or
wireless communications
error. (See note)
Not lit No wireless device error or
wireless communications
error.
COMM
(Master Station)
Yellow Lit Serial communications in
progress.
Not lit No serial communications.
0 to 15
(Slave Station)
Yellow Lit/Not lit ON/OFF status for input or
output signals
RSSI Red/
Yellow/
Green
Lit/
All not lit
Receiving Signal Strength
Indicator monitor: Number of
indicators lit (receiving signal
strength 1 to 9)
Receiving signal strength less
than 0 to 1.
MS
(Module Status)
Green Lit Communications are normal.
Flashing TEST mode or SET mode has
been activated.
Red Lit A fatal error has occurred that
cannot be recovered from.
Replace the Unit
Flashing A non-fatal error has occurred
that can be recovered from by
resetting the system.
--- Not lit Power is not being supplied or
the system is resetting.
WS
(Wireless
Status)
Green Lit The station has joined the
wireless network.
Flashing Permission to join wireless
network received from Serial
Master Station (Slave Station)
Red Lit A fatal error has occurred that
cannot be recovered from.
Flashing Error from which recovery is
possible
--- Not lit Wireless communications are
not in progress.
FA Wireless SS Terminals WT30 5
Wiring
Serial Master Station (WT30-M01-FLK)
I/O Characteristics
I/O Slave Station
RS-232C Connector
WT30
Power supply terminal
Supply power to the Unit
54321
9876
D-sub, 9-pin, Female End at WT30
Pin No. Signal I/O direction
1 --- ---
2RDOutput
3 SD Input
4 --- ---
5 SG ---
6 --- ---
7 --- ---
8 --- ---
9 --- ---
VG 01 2 3
COM
IN
IN
4567
COM ERRP
24 V DC
0 V 8 9 10 11
COM
12 13 14 15
COM
ERRN
Power supply Inputs Inputs
Inputs Inputs
Error output
(
NPN
)
Error output
power supply
Error output
(PNP)
Error output
(NPN)
OUT
24 V DC
0 V 0 1 2 3
COM
4567
COM ERRN
Power supply Outputs Outputs
VG0 1 2 3
COM
IN
4567
COM ERRP
Inputs Inputs
Error output/output
power supply
Error output
(PNP)
WT30-SID16
WT30-SMD16
WT30-SMD-16-1
Item Specifications
Input Characteristics
Input voltage 24 V DC
Allowable
voltage range
20.4 to 26.4 V DC
Input
impedance
4.7 k
(typical)
Input current 5 mA (typical)
ON voltage/
current
characteristics
17.4 V DC, 3.0 mA min.
OFF voltage/
current
characteristics
5.0 V DC, 1.0 mA max.
Input filter 10 ms/100 ms (Selected using switch.)
Output/Error Output
Characteristics
Input voltage 24 V DC
Allowable
voltage
20.4 to 26.4 V DC
Max.
switching
current
100 mA max. per output (at 20.4 to 26.4 V DC)
Simultaneous usage of error output NPN/PNP
is not possible.
Leakage
current
0.1 mA max.
Residual
voltage
1.0 V max.
Fuse One for every two outputs except for error
output circuits, which have one for every NPN/
PNP output. (No fuses can be replaced by the
user.)
6 FA Wireless SS Terminals WT30
Input Circuit Diagram
Error Output Circuit Diagram
Output Circuit Diagram (NPN)
Output Circuit Diagram (PNP)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Serial Master Station
WT30-M01-FLK
I/O Slave Station
WT30-SID16
WT30-SMD16
WT30-SMD16-1
IN 0
IN 1
IN 2
IN 15
COM (IN)
Secondary internal circuit
V
G
ERRN
ERRP
Fuse
Secondary internal circuit
Fuse
V
G
OUT 0
OUT 1
OUT 2
OUT 7
Secondary internal circuit
Fuse
Fuse
Fuse
V
G
OUT 0
OUT 1
OUT 2
OUT 7
Fuse
OUT
3
Secondary internal circuit
Fuse
Four, 5 dia.
(15)
(15)
60 40
13.3
105 13.3
120
Surface mounting bracket
WT30-FT003
105
90
7.3
DIN rail mounting bracket
WT30-FT001 or WT30-FT002

WT30-FT001

Mfr. #:
Manufacturer:
Omron Automation and Safety