BCD.00060 Rev. AA July 07, 2011 Page 4 of 5 www.power-one.com
SLI 15 Inverter Series Data Sheet
1500 Watt, 1U Compact Inverters
Interface Signals/Controls
Parameter Conditions / Description Min. Nom. Max. Units
LCD Panel 2-line LCD panel with keypad for menu navigation.
LED Indicators 4 LED indicators:
Front panel GREEN LED indicates inverter is ON.
Front panel RED LED indicates a generic fault categorized as:
a. Overtemperature (OT),
b. Fan fail,
c. Input OV, UV, OC, or Output OV, UV, or OC.
General Alarm Signal Activated by an open photo-relay if in fault mode, available at rear signal connector
Serial link RS485 port, 500Vdc isolated, available at rear signal connector
Regulatory & Safety
Parameter Conditions / Description Min. Nom. Max. Units
cCSAus Approved.
Kema Approved.
CB Report Approval Approved.
CE Mark for LVD Approved.
RoHS Compliant.
Isolation Primary-to-Secondary: 3000 Vrms.
Primary-to-Ground: 1000 Vrms.
Secondary-to-Ground: 1500 Vrms.
Signal-to-Ground: 0 Vrms.
Mechanical Specifications
Parameter Conditions / Description Min. Nom. Max. Units
Dimensions Depth (inches) 14.94
in
Depth (mm) 379.5 mm
Width (inches) 19.00 in
Width (mm) 482.6 mm
Height (inches) 1.71 in
Height (mm) 43.5 mm
Weight Pounds 12.34 lb
Kilograms 5.6 kg
Connections DC input: back left, one 6mm diameter hole at each input bar; hot plug version has PCB bars with
pre charging system; subrack for -HP version hosts one inverter, separate purchasing part; plastic
DC input cover is available, separate purchasing part
AC output: back right, IEC320 plug is the standard; screw terminal blocks are with the option –SC;
-STS version has IEC320 socket marked “Grid Input”
Signal: back centre, female Sub-D 15 poles connector, Molex 89263-6062 or equivalent; general
failure alarm, serial port, synchronism for paralleling or three phase, remote on/off.
For paralleling inverters, up to 6, ask for paralleling kit, one per inverter, separate purchasing part
Important: -STS and -GN options are compatible just supplying Grind Input by means of an
isolation transformer, same indication if Neutral is tied to Ground at customer site.