https://www.phoenixcontact.com/pi/products/2701531
08/20/2018Page3/6
Distributed I/O device-AXL E EC IOL8 DI4 M12 6M-2701531
Technical data
Supply
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption max. 12 A
Typical current consumption 180 mA ±15 % (at 24 V DC)
Designation
Actuators (U
A
)
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumption max. 12 A
Typical current consumption 28 mA ±15 % (at 24 V DC)
Digital inputs
Description of the input IO-Link ports in digital input (DI) mode
Connection method M12 connector, X01 ... X04 have double occupancy
Connection technology 3-wire
Nominal input voltage U
IN
24 V DC
Input voltage range "0" signal -0.3 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input current typ. 3 mA
Sensor current per channel max. 200 mA (from L+/L-)
Total sensor current max. 1.6 A (from L+/L-)
Input filter time < 1000 µs
Input frequency 0.5 kHz
Type of protection Overload protection
Short-circuit protection for the sensor supply
Digital outputs
Output description IO-Link ports in digital output (DO) mode
Connection method M12 connector, X01 ... X04 have double occupancy
Connection technology 3-wire
Number of outputs max. 8
Nominal output voltage 24 V DC
Maximum output current per channel 150 mA
Maximum output current per device 1.2 A
Nominal load, ohmic 3.6 W (160 Ω, at nominal load)
Nominal load, inductive 3.6 VA (0.8 H, 160 Ω, at nominal load)
Signal delay max. 150 µs (when switched on)
max. 200 µs (when switched off)
Switching rate 1 per second, maximum (at nominal inductive load)
Limitation of the voltage induced on circuit interruption -15 V DC
Output voltage when switched off max. 1 V
Output current when switched off max. 300 µA