https://www.phoenixcontact.com/pi/products/2701531
08/20/2018Page4/6
Distributed I/O device-AXL E EC IOL8 DI4 M12 6M-2701531
Technical data
Digital outputs
Type of protection Overload protection
Short-circuit protection
Behavior with overload Shutdown with automatic restart
Electrical isolation
Test section
24 V supply (communications power and sensor supply, IO-Link ports)/
bus connection (Ethernet1) 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, IO-Link ports)/
bus connection (Ethernet2) 500 V AC 50 Hz 1 min.
24 V supply (communications power and sensor supply, IO-Link ports)/
FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet1)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet2)/FE 500 V AC 50 Hz 1 min.
Bus connection (Ethernet1)/bus connection (Ethernet2) 500 V AC 50
Hz 1 min.
24 V supply (actuator supply)/24 V supply (communications power and
sensor supply, IO-Link ports) 500 V AC 50 Hz 1 min.
24 V supply (actuator supply)/bus connection (Ethernet1) 500 V AC 50
Hz 1 min.
24 V supply (actuator supply)/bus connection (Ethernet2) 500 V AC 50
Hz 1 min.
24 V supply (actuator supply)/FE 500 V AC 50 Hz 1 min.
Standards and Regulations
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g, 11 ms period,
half-sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings