RCP-2000-12

Industrial automation
Distributed power architecture system
Wireless/telecommunication solution
Redundant power system
Electric vehicle charger system
Constant current source system
Model Encoding / Order Information
Description
RCP-2000 is a 2KW single output rack mountable front end AC/DC power supply with a 1U low profile
and a high power density up to 25W/inch . This series operates for 90~264VAC input voltage and offers
3
the models with the DC output mostly demanded from the industry. Each model is cooled by the built-in
DC fan with fan speed control, working for the temperature up to 70 . RCP-2000 provides vast design
flexibility by equipping various built-in functions such as the PMBus communication protocol, output
programming, active current sharing (up to 18000W via three 19 rack shelves, RKP-1U), remote control,
auxiliary power, alarm signal, external control/monitor via the control model RKP-CMU1, etc.
Universal AC input / Full range
(Withstand 300VAC surge input for 5 seconds)
Built-in active PFC function
High efficiency up to 92%
Forced air cooling by built-in DC fan
Output voltage programmable
Built-in OR-ing FET, support hot swap (hot plug)
Active current sharing up to 6000W for one 19 rack shelf
Built-in I C interface, PMBus protocol
2
Protections: Short circuit / Overload / Over voltage /
Over temperature
Optional conformal coating
5 years warranty
Features
Applications
2000W Rack Mountable Front End Rectifier
RCP-2000 series
Output wattage
Output voltage
24RCP - -2000
Safety: UL/EN/IEC 60950-1
EMC: EN 55022 / 55024
Certificates
File Name:RCP-2000-SPEC 2018-04-19
Note 1: 19" rack shelf, RKP-1U, available. Details available on http://www.meanwell.com/
Note 2: Control/Monitor unit, RKP-CMU1, available. Details available on http://www.meanwell.com/
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
5
Dimension
L
295
11.6
W
127
H
41 (1U)
(1U)
mm
inch1.61
*
*
*
*
*
*
Series name
SPECIFICATION
RCP-2000-12 RCP-2000-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5,6
FREQUENCY RANGE
EFFICIENCY (Typ.)
POWER FACTOR (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
AC CURRENT (Typ.)
12V 24V
100A 80A
0 ~ 100A 0 ~ 80A
1200W 1920W
150mVp-p
10.5 ~ 14V
200mVp-p
21 ~ 28V
±2.0% ±1.0%
±1.0%
±1.0%
1500ms, 60ms/230VAC at full load
16ms/230VAC at 75% load 10ms/230VAC at full load
90 ~ 264VAC 127 ~ 320VDC
47 ~ 63Hz
86%
0.98/230VAC at full load
COLD START 50A
13A/115VAC 7A/230VAC 16A/115VAC 10A/230VAC 16A/115VAC 10A/230VAC
<1.1mA / 230VAC
RCP-2000-48
48V
42A
0 ~ 42A
2016W
300mVp-p
42 ~ 56V
±1.0%
±0.5% ±0.5%
±0.5% ±0.5%
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.4
90.5% 92%
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
OVER TEMPERATURE
OVERLOAD
OVER VOLTAGE
105 ~ 125% rated output power
14.7 ~ 17.5V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
29.5 ~ 35V 57.6 ~ 67.2V
PROTECTION
REMOTE SENSE
REMOTE ON-OFF CONTROL
AUXILIARY POWER
Compensate voltage drop on the load wiring up to 0.5V
Please refer to the Function Manual
5V @ 0.3A, 12V @ 0.8A
FUNCTION
Logic " High" for over temperature warning, Please refer to the Installation Manual, isolated signal
The isolated TTL signal out, Please refer to the Installation Manual
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
non-condensing
±℃ 0.03%/ (0 ~ 50 )
ENVIRONMENT
OVER TEMP WARNING
FAN FAIL SIGNAL
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
File Name:RCP-2000-SPEC 2018-04-19
2000W Rack Mountable Front End Rectifier
RCP-2000 series
SAFETY STANDARDS
WITHSTAND VOLTAGE
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC
ISOLATION RESISTANCE
MTBF
DIMENSION
PACKING
OTHERS
145.1K hrs min. Telcordia SR-332 (Bellcore) ; 37.4K hrs min. MIL-HDBK-217F (25 )
295*127*41mm (L*W*H)
SAFETY &
EMC
(Note 7)
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
2Kg; 6pcs/13Kg/1.04CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
4. Tolerance : includes set up tolerance, line regulation and load regulation.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Please contact MEANWELL for 320~370VDC application.
7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.720 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual.
OUTPUT VOLTAGE PROGRAMMABLE
AC OK SIGNAL
DC OK SIGNAL
The isolated TTL signal out, Please refer to the Installation Manual
The isolated TTL signal out, Please refer to the Installation Manual
EMC IMMUNITY
EMC EMISSION
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class A
-----
-----
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
84
85
86
87
88
89
90
91
92
93
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
PFC fosc : 110KHz
PWM fosc : 90KHz
Block Diagram
Static Characteristics
LOAD (%)
LOAD (%)
INPUT VOLTAGE (VAC) 60Hz
90 100 115 180
24V,48V
12V
264
90
100
80
70
75
65
50
40
Derating Loads vs Input Voltage
Efficiency vs Load (48V Model)
EFFICIENCY (%)
LOAD
The curve above is measured at 230VAC.
MODEL
INPUT
12V
1200W
1080W
1020W
960W
1920W
1632W
1440W
1248W
2016W
1713.6W
1512W
1310.4W
100A
90A
85A
80A
80A
68A
60A
52A
42A
35.7A
31.5A
27.3A
180~264VAC
115VAC
100VAC
90VAC
24V 48V
230VAC
Input only
-40 -25 0-10 15 30 50 60 70
20
40
60
50
80
100
(HORIZONTAL)
Derating Curve
AMBIENT TEMPERATURE ( )
2000W Rack Mountable Front End Rectifier
RCP-2000 series
File Name:RCP-2000-SPEC 2018-04-19
LIMITING
ACTIVE
CURRENT
INRUSH
CONTROL
I/P
RECTIFIERS
&
FILTER
SWITCHING
POWER
RECTIFIERS
FILTER
EMI
PWM
CIRCUIT
DETECTION
POWER
AUX
&
PFC
FILTER
&
12V/0.8A
AUX POWER
PFC
CONTROL
5V/0.3A
AC-OK
MCU
DETECTION
CIRCUIT
O.V.P.
MCU
O.T.P.
DA/DB
PV
DC-OK
T-Alarm
SDA/SCL
REMOTE
ON-OFF
PM BUS
FAN FAIL
FAN
+V
-S
+S
RECTIFIERS
ORING
FET
-V
ORING FET
CONTROL
TRANSCEIVERS
DATA
ISOLATION

RCP-2000-12

Mfr. #:
Manufacturer:
Description:
Rack Mount Power Supplies 1200W 12V 100A Front End PS W/PFC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet