RCP-2000-12

60
70
80
OUTPUT VOLTAGE(%)
90
100
110
Vout
0.50 1.5 3
EXTERNAL VOLTAGE (DC)
4.5 5
V
Function Manual
1.1 Remote Sense
1. Voltage Drop Compensation
The Remote Sense compensates voltage drop on the load wiring up to 0.5V
-V
+V
RCP-2000
+S
-S
LOAD
-V
+V
14
15
Sense lines should be twisted in pairs
+V
-V
+S
-S
RCP-2000
14
15
PIN14 +S
PIN14 +S
PIN15 -S
PIN15 -S
PV
-S
-V
+V
+S
RCP-2000
11
15
14
0~5V
-V Signal
9
LOAD
2000W Rack Mountable Front End Rectifier
RCP-2000 series
File Name:RCP-2000-SPEC 2018-04-19
1.2 Local Sense
The +S,-S have to be connected to the ,-V , respectively, as the following diagram, in order to get the correct output voltage if Remote+V(signal) (signal)
Sense is not used.
In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 90~110% of the nominal voltage by applying
EXTERNAL VOLTAGE.
2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
PIN9 -V(signal)
PIN11 PV
+S & +V, -S & -V also need to be connected on CN501
File Name:RCP-2000-SPEC 2018-04-19
2000W Rack Mountable Front End Rectifier
RCP-2000 series
3. Remote ON-OFF Control
switch
PIN29 +5V-AUX
PIN17 Remote ON-OFF
The power supply can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
4.PMBus Communication Interface
RCP-2000 supports PMBus Rev. 1.1 with maximum 100KHz bus speed, allowing information reading, status monitoring and output trimming. For
details, please refer to the Manual.Installation
Between andRemote ON-OFF +5V-AUX
Switch Short
Switch Open
Power Supply Status
ON
OFF
2000W Rack Mountable Front End Rectifier
RCP-2000 series
Mechanical Specification
Case No. 974A Unit:mm
direction
Air flow
295
SVR1
24
46
DC OK
5max.
41
7.1
12.5
127
61
26.2
3.6
62.4
Function
AC-OK
AC-NG
DC-OK
DC-NG
T-OK
T-ALARM
LED
GREEN
GREEN
GREEN
RED
RED
RED
Description
When input voltage 87V
When input voltage 75V
When output voltage 80% 5% of Vo rated.≧±
When output voltage 80% 5% of Vo rated.≦±
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
Signal
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
Power Supply
ON
OFF
ON
ON
ON
OFF
*
*Signal between function pin and "GND-AUX".
CN501
Input / Output Connector Pin No. Assignment( ) : Postronic PCIM34W13M400A1CN501
LED Status Indicators & Corresponding Signal at Function Pins
33
32 34
1357911 29
2468
10 13 31
12
13
11
15
16
14
18
19
17
21
22
20
24
25
23
27
28
26
30
31
29
Positive output voltage signal. For local sense only ; it cannot be connected directly to the load.
Negative output voltage signal. For local sense only ; it cannot be connected directly to the load.
Differential digital signal for parallel control. (Note.1)
The unit can turn the output on and off by electrical signal or dry contact between and . (Note.2)Remote ON-OFF +5V-AUX
Short (4.5 ~ 5.5V) : Power ON ; Open (0 ~ 0.5V) : Power OFF ; The maximum input voltage is 5.5V.
Serial Data used in the PMBus interface. (Note.2)
Serial Clock used in the PMBus interface. (Note.2)
Low (0 ~ 0.5V) : When the input voltage is 87Vrms.
High (4.5 ~ 5.5V) : When the input voltage in 75Vrms . The maximum sourcing current is 10mA and only for output. (Note.2)
Low (0 ~ 0.5V) : When Vout 80% 5%. The maximum sourcing current is 10mAand only for output. (Note.2)≧±
Low : When the internal fan is normal.(0 ~ 0.5V) The maximum sourcing current is 10mAand only for output(Note.2)
Connection for output voltage . (Note.1)
programming
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.(4.5 ~ 5.5V)
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature.(0 ~ 0.5V) The maximum sourcing
current is 10mA and only for output(Note.2)
Auxiliary voltage output, 4.5~5.5V, referenced to . The maximum load current is 0.3A.GND-AUX (pin 31)
Auxiliary voltage output, 10.8~13.2V, referenced to . The maximum load current is 0.8A.GND-AUX (pin 31)
This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
High (4.5 ~ 5.5V) : When the Vout 80% 5%. ±
High : When the internal fan fail.(4.5 ~ 5.5V)
PMBus interface address lines. (Note.1)
Positive output terminal.
Negative output terminal.
Retain for future use.
Positive sensing
for remote sense.
Negative sensing for remote sense.
Description
Pin No.
1,2,3,4
10
9
5,6,7,8
12,13
17
22
23
24
25
26
28
11
14
15
27
29
16,18,19,
20,21
Function
+V
+V(Signal)
-V(Signal)
-V
DA,DB
Remote
ON-OFF
NC
SDA
SCL
AC-OK
FAN-FAIL
PV
+S
-S
T-ALARM
+5V-AUX
A0,A1,A2,
A3,A4
Mating Housing
Postronic PCIM34W13F400A1
31 GND-AUX
Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
30 +12V-AUX
32 FG
AC Ground connection.
DC-OK
33
34
Note1: Non-isolated signal, referenced to
-V(signal).
Note2: Isolated signal, referenced to .GND-AUX
AC/L
AC/N
AC Line connection.
AC Neutral connection.
File Name:RCP-2000-SPEC 2018-04-19

RCP-2000-12

Mfr. #:
Manufacturer:
Description:
Rack Mount Power Supplies 1200W 12V 100A Front End PS W/PFC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union