E5GN
E5GN
Protect Level
Operation/adjustment protection
Restricts display and modification of menus in the
operation and adjustment levels.
Initial setting/communications protection
Restricts display and modification of menus in the initial
setting, operation level and adjustment levels.
Setting change protection
Protects changes to setups by operating the front
panel keys.
Operation/Adjustment Protection
The following table shows the relationship between set values
and the range of protection.
Level
Set value
0 1 2 3
Operation
PV
level
PV/SP
Other X X
Adjustment level X X X
When this parameter is set to “0,” parameters are not protected.
Default setting: 0
:
Can be displayed and changed
: Can be displayed
: Cannot be displayed and move to other levels not possible
Initial Setting/Communications Protection
This protect level restricts movement to the initial setting level,
communications setting level and advanced function setting level.
Set
value
Initial setting
level
Communications
setting level
Advanced
function
setting level
0
1 X
2 X X X
Default setting: 1
: Move to other levels possible
: Move to other levels not possible
Setting Change Protection
This protect level protects setup from being changed by
operating the keys on the front panel.
Set value
Description
OFF Setup can be changed by key operation.
ON Setup cannot be changed by key operation.
(The protect level, can be changed.)
Default setting: OFF