E5GN
E5GN
Dimensions
Unit: mm (inch)
E5GN
Panel Cutout
* When carrying out maintenance on the E5GN, only the terminal plate can be drawn
out with the terminal leads still attached.
24
3
(48 number of units -2.5)60 min.
60 min.
+1.0
0
45
22
+0.3
0
+0.6
0
22
+0.3
0
Mounted Separately
Insert the Controller through the hole in the panel from the front and push the adapter on
from the rear. Push the adapter up to the back of the panel, ensuring that the controller
is pushed all the way in, and remove any gap between the Controller, the panel, and the
adapter. Finally, use the two screws on the adapter to secure the unit in place.
To mount the E5GN so that it is waterproof, insert the waterproof seal onto the E5GN.
When two or more E5GN Controllers are mounted, make sure that the surrounding
temperature does not exceed the allowable operating temperature given in the
specifications.
Group Mounted
Mounting separately does not allow waterproofing.
48
(1.89)
35
(1.38)
36.8
(1.45)
100
(3.94)
22
(0.87)
44.8
(1.76)
22
(0.87)
E5GN
E5GN
Installation
MOUNTING
1. Insert the E5GN into the mounting hole in the panel from the
front.
2. Push the adapter along the E5GN body from the terminals up
to the panel, and secure it temporarily.
3. Tighten the two fixing screws on the adapter. When tighten-
ing screws, tighten the two screws alternately (keeping the
torque to within approximately 0.29 to 0.39 N m).
Adapter
Panel
Waterproof seal
REMOVING AND ATTACHING THE
TERMINAL PLATE
The E5GN can be replaced by removing the terminal plate.
1. Press down hard on the fasteners on both sides of the termi-
nals to unlock the terminal plate and pull upward.
2. Pull to remove the terminal plate.
3. Before you insert the terminal plate again, make sure that the
pins match the positions of the holes in the terminal plate.
WIRING TERMINALS
The voltage output (control output) is not electrically insulated
from the internal circuits. When using a grounding thermocouple,
do not connect the control output terminals to the ground. If the
control output terminals are connected to the ground, errors will
occur in the measured temperature values, as a result of leakage
current.
Standard insulation is applied to the power supply I/O sections. If
reinforced insulation is required, connect the input and output
terminals to a device without any exposed current-carrying parts
or to a device with standard insulation suitable for the maximum
operating voltage of the power supply I/O section.
Analog input
Input power supply
Two input power supplies are available:
100 to 240 VAC or 24 VAC/VDC (no polarity).
Relay output
Voltage output
Communications
specification
RS-
485
Host
computer
Alarm output
WIRING PRECAUTIONS
E5GN
Connect the terminals as specified below.
Terminal No.
Cables Pin terminals
1to6 AWG24toAWG14 2.1 dia. max.
7to9 AWG28toAWG22 1.3 dia. max.
The exposed current-carrying part to be inserted into termi-
nals must be 5 to 6 mm.
Electrical wire
Pin terminal
5--6mm
5--6mm
Tighten the terminal screws to the torque specified below.
Terminal No.
Screw Maximum tightening torque
1to6 M2.6
0.24 N m (2.5 kgf cm)
7to9 M2
0.13 N m (1.4 kgf cm)
E5GN
E5GN
Operation
INITIAL SETUP
On previous Controllers, sensor input type, alarm type and
control period were set on DIP switches. These hardware
settings are now set in parameters in setup menus. The
and
keys are used to switch between setup menus, and the
amount of time that you hold the keys down determines which
setup menu you move to. This section describes two typical
examples.
Note: On the E5GN, the
Keyisthe Key.
1. ON/OFF Control
Typical Application Examples
Changing Parameters
indicates that there is a parameter.
Keep on pressing the mode key until
the desired parameter is selected.
Changing Set Values
Use the or keys to
change the set value displayed
in the setup menu.
Display
E5CN E5GN
No. 1 display
No. 2 display
No. 1 display
No. 2 display
Typical Example
Input type: 0 K thermocouple -200 to 1300
°
C
Control method: ON/OFF control
Alarm type: 2 upper limit
Alarm value 1: 20
°
C (For setting deviation)
Set point: 100
°
C
Change only the alarm value 1 and set point.
The rest must be left as default settings.
Setup procedure
Power ON
Set input
specifications
Set control
specifications
Set alarm type
Set alarm values
Start operation
Power ON
Process value/
set point
Input type
In ON/OFF
control
Alarm 1
type
Check input
type.
Check that con-
trol is ON/OFF
control.
Check alarm
type.
Press key for at least
three seconds.
Control stops.
Process value/
set point
Make sure that
control is running.
Press key for at
least one second.
During run
During stop
Alarm
value 1
Press keys
to set set point to
“100 C.”
Press keys
to set alarm value
to “20 C.”
Start operation
Set the set point
Check operation
state
Operation level
Initial setting level
Operation level