AXL F DI16/1 HS 1H
8610_en_01 PHOENIX CONTACT 4
Connection data
Name Axioline plug
Connection method Spring-cage connection with direct plug-in method
Conductor cross section solid / stranded 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG] 24 ... 16
Interface AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Communications power
Communications power U
Bus
5 V DC (via bus base module)
Current consumption from U
bus
max. 120 mA
Power consumption at U
Bus
max. 600 mW
I/O supply
Supply of digital input modules U
I
24 V DC
Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption from U
I
20 mA
Power consumption at U
I
typ. 380 mW, max. 480 mW
Surge protection of the supply voltage Electronic (35 V, 0.5 s)
Polarity reversal protection of the supply voltage Parallel diode; with external 5A fuse (for startup only)
Protection max. 8 A (polarity reversal protection up to 5A)
When using for the first time, protect the module with a 5 A fuse. If all the modules are correctly connected in the system, the 5 A fuse can be
replaced by an 8 A fuse. you can now load the module up to 8A.
NOTE: Damage to the electronics
Provide the module with an external fuse to protect it against polarity reversal. The power supply unit must be able to supply four times the
nominal current of the external fuse, to ensure that it trips in the event of an error.
Digital inputs
Number of inputs 16
Connection method Direct plug-in method
Connection method 1-wire
Description of the input EN 61131-2 types 1 and 3
Nominal input voltage 24 V DC
Input voltage range -3 V DC ... 30 V DC
Nominal input current 2.3 mA
Current flow Linear until nominal current is reached, then constantly approximately 2.3mA
Input voltage range "0" signal -3 V DC ... 8.4 V DC
Input voltage range "1" signal 9.4 V ... 30 V DC
Input filter time < 5 µs
Process data update < 5 µs (bus-synchronous)
Polarity reversal protection of the inputs Parallel diode (30V, 5s)
The minimum update time of the module can only be fully utilized if the station is configured accordingly, as the runtime of the local bus de-
pends on the number of connected AxiolineF modules (see also Axioline system manual).
PROFIBUS telegram data
Required parameter data 3 Byte
Need for configuration data 6 Byte
AXL F DI16/1 HS 1H
8610_en_01 PHOENIX CONTACT 5
Error messages to the higher level control or computer system
I/O supply failure Yes
Electrical isolation/isolation of the voltage areas
5 V communications power (logic), 24 V supply (I/O) 500 V AC, 50 Hz, 1 min
5 V supply (logic)/functional earth ground 500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5 g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25 g, 11 ms period, half-sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10 g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022 Class B
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
AXL F DI16/1 HS 1H
8610_en_01 PHOENIX CONTACT 6
5 Internal circuit diagram
Figure 1 Internal wiring of the terminal points
Key:
6 Terminal point assignment
Figure 2 Terminal point assignment
7 Connection example
Figure 3 Example of a connection of sensors when
using external busbars
Ensure that GND of the sensors and GND for U
I
have the
same potential.
Microprocessor
Optocoupler
LED
Power supply unit
Electrically isolated area
Input circuit Input circuit
Local bus AxiolineF local bus
(hereinafter referred to as local bus)
µC
D
UI
2x
DI 1...16
U
24 V
I
U
Bus
Local bus
Input circuit
013233 00
00
32
0133
00
10
20
30
01
11
21
31
µC
Terminal
point
Color Assignment
Supply voltage input
a1, a2 Red 24 V DC (U
I
) Digital input module
supply (internally jump-
ered)
b1, b2 Blue GND Reference potential of
the supply voltage (in-
ternally jumpered)
Digital inputs
00 ... 03 Orange IN1 ... IN4 Digital inputs 1 ... 4
10 ... 13 Orange IN5 ... IN8 Digital inputs 5 ... 8
20 ... 23 Orange IN9 ... IN12 Digital inputs 9 ... 12
30 ... 33 Orange IN13 ...
IN16
Digital inputs 13 ... 16
0300
1310
2320
3330
a1
a2
b1
b2
00
10
20
30
01
11
21
31
02
12
22
32
03
13
23
33
a1
a2
b1
b2

2701722

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F DI16/1 HS 1H