MAX15000/MAX15001
threshold), then startup has been accomplished and
sustained operation will commence. If V
IN
drops below
9.74V before startup is complete, the device goes back
to low-current UVLO. In this case, increase the value of
C1 to store enough energy to allow for the voltage at
the tertiary winding to build up.
UVLO Flag (UFLG)
The MAX15000/MAX15001 have an open-drain under-
voltage flag output (UFLG). When used with an opto-
coupler the UFLG output can serve to sequence a
secondary-side controller. An internal 210µs delay
occurs the instant the voltage on UVLO/EN drops
below 1.17V until NDRV stops switching. This allows for
the UFLG output to change state before the MAX15000/
MAX15001 shut down (Figure 3).
When the voltage at the UVLO/EN is above the thresh-
old, UFLG is high impedance. When UVLO/EN is below
the threshold, UFLG goes low. UFLG is not affected by
bootstrap UVLO (MAX15000).
Soft-Start
The MAX15000/MAX15001 soft-start feature allows the
output voltage to ramp up in a controlled manner, elimi-
nating voltage overshoot. The MAX15000/MAX15001
reference generator that is internally connected to the
error amplifier soft-starts to achieve superior control of
the output voltage under heavy and light load condi-
tions. Soft-start begins after UVLO is deasserted (V
IN
is
above 21.6V for the MAX15000, V
IN
is above 9.5V for
the MAX15001, and the voltage on UVLO/EN is above
1.23V). The voltage applied to the noninverting node of
the amplifier ramps from 0 to 1.23V in 1984 NDRV
switching cycles. Use the following formula to calculate
the soft-start time (t
SS
):
where f
NDRV
is the switching frequency at the NDRV
output. Figure 4 shows the soft-start regulated output of
a power supply using the MAX15000 during startup.
t
f
SS
NDRV
=
1984
Current-Mode PWM Controllers with
Programmable Switching Frequency
10 ______________________________________________________________________________________
MAX15000 fig02
100ms/div
V
CC
2V/div
V
IN
5V/div
0V
Figure 2. V
IN
and V
CC
During Startup When Using the
MAX15000 in Bootstrapped Mode (Figure 1)
V
UVLO/EN
LOW
LOW
Hi-Z
V
UFLG
V
NDRV
SHUTDOWN
SHUTDOWN
t
EXTR
3ms
1.23V
(±1%)
1.17V (typ)
t
EXTF
210µs
0.6µs
3µs
NDRV SWITCHING
Figure 3. UVLO/EN and UFLG Operation Timing
n-Channel MOSFET Switch Driver
The NDRV output drives an external n-channel MOSFET.
The internal regulator output (V
CC
), set to approximately
9V, drives NDRV. For the universal input voltage range,
the MOSFET used must withstand the DC level of the
high-line input voltage plus the reflected voltage at the
primary of the transformer. Most applications that use the
discontinuous flyback topology require a MOSFET rated
at 600V. NDRV can source/sink in excess of 650/1000mA
peak current; therefore, select a MOSFET that will yield
acceptable conduction and switching losses.
Oscillator/Switching Frequency
Use an external resistor at RT to program the
MAX15000/MAX15001 internal oscillator frequency
between 50kHz and 2.5MHz. The MAX15000A/
MAX15001A output switching frequency is one-half of
the programmed oscillator frequency with a 50% duty
cycle. The MAX15000B/MAX15001B output switching
frequency is one-quarter of the programmed oscillator
frequency with a 75% duty cycle.
The MAX15000A/MAX15001A and MAX15000B/
MAX15001B have programmable output switching fre-
quencies from 25kHz to 625kHz and 12.5kHz to
625kHz, respectively. Use the following formulas to
determine the appropriate value of the resistor R12
(see Figure 1) needed to generate the desired output
switching frequency (f
SW
) at the NDRV output:
where R12 is the resistor connected from RT to GND
(see Figure 1).
Connect an RC network in parallel with R12 as shown in
Figure 1. The RC network should consist of a 100nF
capacitor C6 (for stability) in series with resistor R15
which serves to further minimize jitter. Use the following
formula to determine the value of R15:
For example, if R12 is 4k, R15 becomes 707.
Internal Error Amplifier
The MAX15000/MAX15001 include an internal error
amplifier to regulate the output voltage in the case of a
nonisolated power supply (see Figure 1). For the circuit
in Figure 1, calculate the output voltage using the fol-
lowing equation:
where V
REF
= 1.23V. The amplifier’s noninverting input
is internally connected to a digital soft-start circuit that
gradually increases the reference voltage during start-
up applied to this input. This forces the output voltage
to come up in an orderly and well-defined manner
under all load conditions.
The error amplifier may also be used to regulate the ter-
tiary winding output which implements a primary-side-
regulated, isolated power supply (see Figure 6). For the
circuit in Figure 6, calculate the output voltage using
the following equation:
where N
S
is the number of secondary winding turns, N
T
is the number of tertiary winding turns, and both V
D6
and V
D2
are the diode drops at the respective outputs.
V
N
N
R
R
VVV
OUT
S
T
REF D D
=+
+
1
1
2
62
V
R
R
V
OUT REF
=+
1
13
14
RR15 88 9 12
1
4
.
()
R
f
for the MAX A MAX A
R
f
for the MAX B MAX B
SW
SW
12
10
2
15000 15001
12
10
4
15000 15001
10
10
=
=
/.
/.
MAX15000/MAX15001
Current-Mode PWM Controllers with
Programmable Switching Frequency
______________________________________________________________________________________ 11
MAX15000 fig04
2ms/div
V
OUT
2V/div
100mA LOAD ON/V
OUT1
100mA LOAD ON/V
OUT2
Figure 4. Primary-Side Output Voltage Soft-Start During Initial
Startup for the Circuit in Figure 6
MAX15000/MAX15001
Current Limit
The current-sense resistor (R4 in Figure 1), connected
between the source of the MOSFET and ground, sets the
current limit. The current-limit comparator has a voltage
trip level (V
CS
) of 1V. Use the following equation to cal-
culate the value of R4:
where I
PRI
is the peak current in the primary side of the
transformer which also flows through the MOSFET.
When the voltage produced by this current (through the
current-sense resistor) exceeds the current-limit com-
parator threshold, the MOSFET driver (NDRV) termi-
nates the current on-cycle within 60ns (typ). Use a
small RC network to filter out the leading-edge spikes
on the sensed waveform when needed. Set the corner
frequency between 2MHz and 10MHz.
Applications Information
Startup Time Considerations for Power
Supplies Using the MAX15000
The bypass capacitor at IN, C1, supplies current imme-
diately after the MAX15000 wakes up (see Figure 1).
The size of C1 and the connection configuration of the
tertiary winding determine the number of cycles avail-
able for startup. Large values of C1 increase the start-
up time but also supply gate charge for more cycles
during initial startup. If the value of C1 is too small, V
IN
drops below 9.74V because NDRV does not have
enough time to switch and build up sufficient voltage
across the tertiary output which powers the device. The
device goes back into UVLO and does not start. Use a
low-leakage capacitor for C1 and C2.
Typically, offline power supplies keep startup times to
less than 500ms even in low-line conditions (85VAC
input for universal offline or 36VDC for telecom applica-
tions). Size the startup resistor, R1, to supply both the
maximum startup bias of the device (90µA) and the
charging current for C1 and C2. The bypass capacitor,
C2, must charge to 9.5V and C1 to 24V, all within the
desired time period of 500ms. Because of the internal
soft-start time of the MAX15000 (approximately 5.6ms
when f
SW
= 350kHz), C1 must store enough charge to
deliver current to the device for at least this much time.
To calculate the approximate amount of capacitance
required, use the following formula:
where I
IN
is the MAX15000’s internal supply current
(2mA) after startup, Q
gtot
is the total gate charge for
Q1, f
SW
is the MAX15000’s switching frequency
(350kHz), V
HYST
is the bootstrap UVLO hysteresis
(approximately 12V) and t
SS
is the internal soft-start
time (5.6ms).
Example: I
g
= (8nC) (350kHz) 2.8mA
Choose a 2.2µF standard value (assuming 350kHz
switching frequency).
Assuming C1 > C2, calculate the value of R1 as follows:
where V
IN(MIN)
is the minimum input supply voltage for
the application (36V for telecom), V
SUVR
is the boot-
strap UVLO wake-up level (23.6V max), I
START
is the IN
supply current at startup (90µA max).
For example:
Choose a 120k standard value.
()(.)
()
.
()()
(. ) ( )
.
I
VF
ms
mA
R
VV
mA A
k
C1
24 2 2
500
0 105
1
36 12
0 105 90
123 07
==
+
=
µ
µ
I
VC
ms
R
VV
II
C
SUVR
IN MIN SUVR
C START
1
1
1
500
1
=
+
()
()
C
mA mA ms
V
F1
22856
12
224=
+
=
(.)(.)
. µ
IQ f
C
IIt
V
g gtot SW
IN g SS
HYST
=
=
+
1
()()
R
V
I
CS
PRI
4 =
Current-Mode PWM Controllers with
Programmable Switching Frequency
12 ______________________________________________________________________________________

MAX15000BEUB+

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Switching Controllers w/Programmable Switching Frequency
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union