10
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 02
Technical data - NH size 02
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
35NHG02B 35NHG02BI 02 35 500 2400 11,800 4.7 0.40
40NHG02B 40NHG02BI 40 3300 16,500 5
50NHG02B 50NHG02BI 50 5600 27,800 6.4
63NHG02B 63NHG02BI 63 6600 26,100 5.5
80NHG02B 80NHG02BI 80 9800 38,900 7.3
100NHG02B 100NHG02BI 100 20,600 82,300 7.5
125NHG02B 125NHG02BI 125 25,000 100,000 12
160NHG02B 160NHG02BI 160 62,000 248,000 12
200NHG02B 200NHG02BI 200 96,900 367,900 15
224NHG02B 224NHG02BI 224 124,000 471,200 18
250NHG02B 250NHG02BI 250 151,300 574,900 19
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)
11
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 2
Technical data - NH size 2
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
250NHG2B 250NHG2BI** 2 250 500 170,000 437,000 23 0.63
300NHG2B 300NHG1BI** 300 500 320,000 840,000 20
315NHG2B 315NHG2BI 315 500 361,700 1,446,500 21
355NHG2B 355NHG2BI 355 500 446,500 1,785,800 27
400NHG2B 400NHG2BI 400 500 642,900 2,571,500 30
425NHG2B 425NHG2BI** 425 500 720,000 1,862,000 31
450NHG2B 450NHG2BI** 450 500 870,000 2,275,000 31
500NHG2B 500NHG2BI** 500 440 1,200,000 2,720,000 37
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
** Available upon request
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)
12
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 03
Technical data - NH size 03
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amp)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
250NHG03B 250NHG03BI 03 250 500 160,800 642,900 20 0.64
315NHG03B 315NHG03BI 315 361,700 1,446,500 21
355NHG03B 355NHG03BI 355 446,500 1,785,800 27
400NHG03B 400NHG03BI 400 642,900 2,571,500 30
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)

160NHG01B

Mfr. #:
Manufacturer:
Bussmann / Eaton
Description:
Specialty Fuses 160A 500V GL/GG SIZE 01 DUAL IN
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: