10
LT3433
3433f
APPLICATIO S I FOR ATIO
WUUU
The requirement for avoiding current mode instability is
that the rising slope of sensed inductor ripple current (S1)
is greater than the falling slope (S2). At duty cycles greater
than 50% this is not true. To avoid the instability condition,
a false signal is added to the sensed current with a slope
(S
X
) that is sufficient to prevent current mode instability,
or S1 + S
X
≥ S2. This leads to the following relations:
S
X
≥ S2(2DC – 1)/DC
If the forward voltages of a converter’s catch and pass
diodes are defined as V
F1
and V
F2
, then:
S2 = (V
OUT
+ V
F1
+ V
F2
)/L
Solving for L yields a relation for the minimum inductance
that will satisfy slope compensation requirements:
L
MIN
= (V
OUT
+ V
F1
+ V
F2
)(2DC – 1)/(DC • S
X
)
The LT3433 maximizes available dynamic range using a
slope compensation generator that generates a continu-
ously increasing slope as duty cycle increases. The slope
compensation waveform is calibrated at 80% duty cycle to
generate an equivalent slope of at least 0.05A/µs. The
equation for minimum inductance then reduces to:
L
MIN
= (V
OUT
+ V
F1
+ V
F2
)(15e-6)
For example, with V
OUT
= 5V and using V
F1
+ V
F2
= 1.1V
(cold):
L
MIN
= (5 + 1.1)(15e-6) = 91.5µH
Converter Capabilities
The output current capability of an LT3433 converter is
affected by a myriad of variables. The current in the
switches is limited by the LT3433. Switch current is
measured coming from the V
IN
supply, and does not
directly translate to a limitation in load current. This is
especially true during bridged mode operation when the
converter output current is discontinuous.
During bridged mode operation, the converter output
current is discontinuous, or only flowing to the output
while the switches are off (not to be confused with discon-
tinuous switcher operation). As a result, the maximum
output current capability of the converter is reduced from
that during buck mode operation by a factor of roughly
1 – DC, not including additional losses. Most converter
losses are also a function of DC, so operational duty cycle
must be accurately determined to predict converter load
capabilities.
V
OUT
(V)
4
50
L
MIN
(µH)
100
150
200
250
812
16
20
3433 AI01
300
350
610
14
18
Slope Compensation Requirements
Typical Minimum Inductor Values vs V
OUT
SW_H
LT3433
V
IN
V
OUT
3433 AI02
SW_L
L
D1
D2
Application variables:
V
IN
= Converter input supply voltage
V
OUT
= Converter programmed output voltage
V
BST
= Boosted supply voltage (V
BST
– V
SWH
)
DC = Operational duty cycle
f
O
= Switching frequency
I
MAX
= Peak switch current limit
∆I
L
= Inductor ripple current
I
SW
= Average switch current or peak switch current
less half the ripple current (I
MAX
– ∆I
L
/2)
R
SWH
= Boosted switch “on” resistance
R
SWL
= Grounded switch “on” resistance
L = Inductor value