JLE-1-1-51-3-B3-200-V

Trip Free
Will trip open on overload, even when forcibly held on. This
prevents the operator from damaging the circuit by holding
the handle in the ON position.
Insulation Resistance
Will not be less than 100 megohms at 500 volts D.C.
Endurance
Test to be performed at rated current and rated voltage at
3mSec time constant DC. Rate of operation to be 5
operations per minute for breakers rated at 250 amps and
less and 4 per minute for breakers rated above 250 amps.
Breakers rated above 250 amps but 600 amps or less shall
be rated for 1000 loaded operations and 5000 mechanical
operations.
Auxiliary Switch
When supplied will be S.P.D.T. configuration with a
maximum rating of 10 amperes 250 VAC 1 amp 80 Vdc.
When optional metering shunt or parallel pole configuration
is specified, maximum rating is 1 amp 80 Vdc.
High-Low Temperature
Circuit breakers will operate in the range from -40°C to
+85°C. All agency testing is conducted with wire sized per
75°C chart of the National Electrical Code. In all cases the
breaker connections should be sized to limit the maximum
terminal temperature to 100°C absolute when the breaker is
operating in the maximum ambient temperature at the
maximum load current.
Overload
DC rated circuit breakers will withstand 50 operations at
600% of rated current. The current shall have no less than a
3mSec time constant at rated voltage. Units to be operated
in groups of five at the rate of operations per minute with
fifteen minutes between groups to allow for cool down.
Dielectric Strength
Circuit Breaker will withstand 1000 volts plus twice rated
voltage 60 Hz AC for 60 seconds from terminal to terminal.
Voltage Ratings
On all types, voltages up to and including 160 volts DC.
Multi-pole units can be supplied for 125/250 volts Vdc. All
units will be marked with the standard maximum voltage.
UL listed breakers will be labeled with the UL listed voltage.
DC Applications (typ)
A choice of delays is offered for DC applications. Delay 51
is a short delay for general purpose applications. Delay 52
is long enough to start certain types of motors and most
transformer and capacitor loads. Delay 53 is a long delay
for special motor applications.
All trip curves and trip currents are specified with the
breaker mounted in the normal vertical position at ambient
temperature of +25°C. For test and measurement purposes,
the breakers should not carry current prior to application
of overload for calibration test. For other than vertical
mount position, consult factory.
General notes for Agency Approvals
All supplementary protectors are of the overcurrent (OC) type
The family of protectors has been evaluated for end use application for use group (UG) A
The terminals (FW) – Terminals are coded as follows:
0 – Suitable for factory wiring only
1 – Line terminals evaluated for field wiring
2 – Load terminals evaluated for field wiring
3 – Line and load terminals evaluated for field wiring
The maximum voltage ratings for which the protectors have been tested are shown in the chart
The current is the amperage range that the protectors have been tested
The tripping current (TC) – Tripping current is coded as a percentage of the ampere rating
0 – Tripping current is less than 125% of ampere rating
1 – Tripping current is in the range of 125% to 135% of ampere rating
2 – Tripping current is more than 135% of ampere rating
3 – Tripping current is 135% and meets MCCB trip time requirements
The overload rating (OL) - designates whether the protector has been tested for general use or motor starting applications.
0 – tested at 1.5 times amp rating for general use
1 – tested at 6 times AC rating or 10 times DC rating for motor starting
The short circuit current rating (SC) – The short circuit rating in amperes following a letter and number designating the test conditions and any calibration following the
short circuit test is defined below:
C – Indicates short circuit test was conducted with series overcurrent protection
U – Indicates short circuit test was conducted without series overcurrent protection
1 – Indicates a recalibration was not conducted as part of the short circuit testing
2 – Indicates a recalibration was performed as part of the short circuit testing
3 – Indicates recalibration was performed along with the dielectric and voltage withstand for “Suitable for Further Use” rating
OPERATING CHARACTERISTICS
JAE Series - Operating Characteristics
http://airpax.sensata.com
213
JRE/JRM/JREP/JRMP SUPPLEMENTARY PROTECTORS  AGENCY APPROVALS
Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps)
Voltage (V) Frequency (Hz) UG FW Phase Min. Poles TC OL UL/CSA TUV UL 508 & CSA TUV
65 DC A 0, 3
1 1 1 100-250
U2, 100000
65 DC A 0, 3
2 1 1 275-400
U2, 100000
65 DC A 0, 3
2 1 1 450
U2, 100000
65 DC A 0, 3
3 1 1 450-600
U2, 100000
65 DC A 0, 3
3 1 1 700
U2, 65000
65 DC A 0, 3
3 1 1 700
U2, 100000
80 DC
1
15-250
10000/25000
160 DC A 0, 3
1 1 1 100-250 15-250 U2, 10000 5000/10000
160 DC A 0, 3
2 1 1 251-400
U2, 10000
160 DC A 0, 3
3 1 1 401-600
U2, 10000
160 DC A 0, 3
3 1 1 700
U2, 10000
277/480 50/60 A 0, 3 3 3 1 1 150
U2, 5000
JTE/JTM/JTEP/JTMP COMMUNICATIONS EQUIPMENT CIRCUIT BREAKERS  AGENCY APPROVALS
Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps)
Voltage (V) Frequency (Hz) Phase Min. Poles UL/CSA TUV UL 489A TUV
65 DC 1 100 to 250 100000
65 DC 2 275 to 400 100000
65 DC 2 401 to 450 100000
65 DC 3 450 to 600 100000
65 DC 4 700 to 800 100000
65 DC 5 900 to 1000 65000
65 DC 6 1100 to 1200 65000
80 DC 1 15 to 250 25000
160 DC 1 100 to 250 15 to 250 10000 10000
160 DC 2 251 to 400 10000
160 DC 3 401 to 600 10000
160 DC 4 700 to 800 10000
JLE/JLM  AGENCY APPROVALS
Volts (Volts) Rated Current (Amps) Interrupting Capacity (Amps)
Voltage (V) Frequency (Hz) Phase Min. Poles UL/CSA TUV UL489 & CSA TUV
65 DC 1 .10 - 250 100000
80 DC 1
15 - 250
25000
160 DC 1 .10 - 250
15 - 250
10000
10000
125/250 DC 2 100 - 250 10000
240 50/60
1
1 .10 - 250 10000
240 50/60
1 & 3
2 .10 - 250 18000
JAE Series - Operating Characteristics
JAE (F-frame)
214
PERCENTAGE OF RATED CURRENT VS TRIP TIME IN SECONDS AT +2C
Delay 100% 125% (Note A) 150% 200% 400% 600% 800% 1000%
51 & 51F No Trip .5 to 10 .25 to 3 .15 to 9 .05 to .3 .015 to .15 .01 to .09 .01 to .04
52 & 52F No Trip 9 to 90 5 to 40 2 to 15 .5 to 3 .03 to 1 .01 to .28 .01 to .08
53 & 53F No Trip 100 to 1000 50 to 400 22 to 150 4 to 25 .5 to 5 .010 to 2 .01 to .1
61 & 61F No Trip .4 to 10 .25 to 3 .13 to .9 .03 to .2 .015 to .15 .01 to .09 .008 to .045
62 & 62F No Trip 9 to 95 5 to 40 2 to 15 .05 to 3 .03 to 1 .01 to .28 .008 to .08
63 & 63F No Trip 100 to 1100 48 to 400 20 to 150 4 to 25 .5 to 6 .01 to 2 .008 to .1
Inrush Pulse Tolerance
The table shown provides a comparison of inrush pulse
tolerance with and without the inertial delay feature for each
of the 50/60Hz delays. Pulse tolerance is defined as a single
pulse of half sine wave peak current amplitude of 8
milliseconds duration that will not trip the circuit breaker.
APPROXIMATE WEIGHT PER POLE
Pounds Grams
2.25 1020
RECOMMENDED TORQUE SPECIFICATIONS
Component Torque (in-lbs)
10-32 Mounting Inserts 10 to 12
M5 Mounting Inserts 8 to 10
3/8-16 and M10 x 1.5 Captive Nuts 220 to 230
3/8-16 and M10 x 1.5 Studs 220 to 230
Solderless Connectors 180
NOMINAL DCR / IMPEDANCE
Current Ratings
(Amps)
Resistance (ohms)
DC Delays
51, 52, 53
100 .000375
110 .000375
125 .000340
150 .000325
175 .000315
200 .000225
225 .000225
250 .000225
400 .000125
600 .000083
800 .000063
1,000 .000050
1,200 .000042
Notes:
Resistance is plus or minus 50%.
If a metering shunt option is provided it will add the shunts resistance to these
values (i.e. A 400 Amp metering shunt would add (R=V/I). 0000625 Ohms of
resistance to the non-metering shunt value of .000125 Ohms or .0001875 Ohms
for a 400 Amp unit with a metering shunt).
DC resistance values are based on measurements by the voltmeter ammeter
method. Rated current applied for one hour and at a voltage not less than 20
volts.
INRUSH PULSE TOLERANCE
Delay Pulse Tolerance
61, 62, 63 8 times rated current (approx)
61F, 62F, 63F 12 times rated current (approx)
OPERATING CHARACTERISTICS
JAE Series - Operating Characteristics