PSM-ME-RS232/TTY-P
100275_en_02 PHOENIX CONTACT 4 / 13
TTY interface, CL2 in acc. with DIN 66348-1
Connection method Pluggable screw connection
Conductor cross section 0.2 mm² ... 2.5 mm² (24 AWG ... 13 AWG)
Serial transmission speed 19.2 kbps
Transmission length 1000 m (shielded twisted pair)
Operating mode Active, semi active, passive
Load/output load, current output 500
Output current 2x 20 mA ±10 % (Loop current)
Impedance 117 (Output)
126 (Input)
General data
Degree of protection IP20
Dimensions (W/H/D) 22.5 mm x 99 mm x 118.6 mm
Housing material PA green
Bit distortion < 5 %
Bit delay < 3 µs
Noise emission according to EN 61000-6-4
Noise immunity according to EN 61000-6-2:2005
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Transmission channels 2 (1/1), RxD, TxD, full duplex
Ambient conditions
Ambient temperature (operation) 0 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Altitude 5000 m (For restrictions see manufacturer's declaration)
Approvals / Certificates
Conformance CE-compliant
EAC
UL, USA/Canada 508 recognized
Class I, Div. 2, Groups A, B, C, D
Class I, Zone 2, AEx nA IIC T4
Class I, Zone 2, Ex nA IIC T4 Gc X
Shipbuilding approval DNV
PSM-ME-RS232/TTY-P
100275_en_02 PHOENIX CONTACT 5 / 13
Conformance with EMC Directive 2014/30/EU
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Contact
discharge
± 6 kV (Test Level 3)
Discharge in air ± 8 kV (Test Level 3)
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Frequency range Test Level 3
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input ± 4 kV (5kHz)
Signal ± 2 kV (5kHz)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input ± 0.5 kV (2 )
Signal ± 2 kV (42Ω)
Comments Criterion B
Conducted interference EN61000-4-6
Voltage 10 V
Comments Criterion A
Emitted interference in acc. with EN 61000-6-4
Interference emission EN 55011
Class A, industrial applications
Criterion A Normal operating behavior within the specified limits
Criterion B Temporary impairment of operating behavior that is corrected by the device itself
PSM-ME-RS232/TTY-P
100275_en_02 PHOENIX CONTACT 6 / 13
5Safety notes
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the
installation instructions as described.
When installing and operating the device, the
applicable regulations and safety directives (including
national safety directives), as well as general technical
regulations, must be observed. The technical data is
provided in the package slip and on the certificates
(conformity assessment, additional approvals where
applicable).
With the exception of configuring the switches and
jumpers, opening or modifying the device is not
permitted. Do not repair the device yourself; replace it
with an equivalent device. Repairs may only be
performed by the manufacturer. The manufacturer is
not liable for damage resulting from noncompliance.
The IP20 protection (IEC 60529/EN 60529) of the
device is intended for use in a clean and dry
environment. The device must not be subject to
mechanical strain and/or thermal loads, which exceed
the limits described.
The switches of the device that can be accessed may
only be actuated when the power supply to the device is
disconnected.
The device is designed exclusively for SELV operation
according to IEC 60950/EN 60950/VDE 0805. The
device may only be connected to devices, which meet
the requirements of EN 60950.
5.1 UL Notes
WARNING:
Observe the following safety notes when
using the device.
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN
A)
B)
C)
D)
All wiring of these devices must be in accordance with the national electric code article
501.4(B) for Class 1, Division 2.
Product must be installed in Class I, Zone 2 certified at least an IP54 enclosure.
Product must be used in no more than a pollution degree 2 environment as defined by IEC 60664-1
Provisions must be made to provide transient protection to the product so that
voltage levels do not exceed 40% of the rated voltage at the power supply terminals.
Wire Range: 30-12 AWG,
Torque: 5-7 Lbs-Ins
Supply voltage range 24 V DC 20% 75 mA

2744458

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules PSM-ME-RS 232/TTY-P
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union