AXL E PN DIO16 M12 6M
8443_en_04 PHOENIX CONTACT 10
7 Connection example
Figure 7 Example of connection of sensors and actua-
tors
8 Connection notes
IN/OUT 6
+24 V
IN/OUT 5
IN/OUT 12
+24 V
IN/OUT 11
Note: data corruption or loss
Implement the FE connection using mounting
screws, in order to ensure immunity to inter-
ference.
NOTE: device damage
To ensure IP65/IP67 protection, cover unused
sockets with protective caps.
NOTE: Damage to the electronics
Only supply the sensors with the voltage U
S
provided at the terminal points.
NOTE: Damage to the electronics
Observe the correct polarity of the supply volt-
ages U
S
and U
A
in order to prevent damage to
the device.
NOTE: Malfunction
When connecting the sensors and actuators,
observe the assignment of the connections to
the PROFINET input and output data.
Secure the device to a level surface or to a
profile. Do not use this device to bridge gaps,
in order to prevent forces being transmitted
via the device.
Use standard M5 screws with toothed lock
washer and self-locking nuts. Observe the
maximum torque of the screws.
AXL E PN DIO16 M12 6M
8443_en_04 PHOENIX CONTACT 11
9 Local status and diagnostic indicators
9.1 Indicators for Ethernet ports and power supply
Figure 8 Indicators for Ethernet ports and power supply
Designation Color Meaning State Description
LNK 1/2 Green Link Green
ON
Connection present at port 1/2.
OFF Connection not present at port 1/2.
ACT 1/2 Yellow Activity Yellow
flashing
Data transmission present at port 1/2.
OFF Data transmission not present at port 1/2.
RDY Green/
yellow/
red
Ready Green
ON
Device ready to operate
Yellow
flashing
Firmware update is being performed.
Flashing
green/
yellow
Over- or undervoltage at U
S
Temperature of the device is in the critical area.
And red US LED: sensor supply overload
OFF Device is not ready for operation.
BF Red Bus Fault Red ON No link status available on any port
Flashing SF LED not flashing: Link status available, no communication con-
nection to the PROFINET controller
Flashing SF LED flashing: hardware watchdog has been triggered.
OFF A PROFINET controller has established an active communication
connection to the PROFINET device.
SF Red Station Fail ON PROFINET diagnostics available
Flashing Flashes only together with the BF LED; watchdog triggered
OFF PROFINET diagnostics not available
US Green/
red
U
Sensorik
Green
ON
Communications power/sensor voltage present
OFF Communications power/sensor voltage not present or too low.
Red ON Sensor voltage overload
UA Green U
Aktorik
ON Actuator voltage present.
OFF Actuator voltage not present.
AXL E PN DIO16 M12 6M
8443_en_04 PHOENIX CONTACT 12
9.2 Input and output indicators
Figure 9 Input and output indicators
DIO1 ... DIO 16
Designation Color Meaning State Description
00 ... 07,
10 ... 17
Yellow Status of the inputs and outputs
when used as an input
ON Input is set.
OFF Input is not set.
00 ... 07,
10 ... 17
Yellow/red Status of the inputs and outputs
when used as an output
Yellow ON Output is set.
Red ON Output is short circuited or overloaded.
OFF Output is not set.
The numbering of the LEDs is as follows: the first number specifies the byte, the second number specifies the
bit.